Negative Sequence Relay

Encyclopedia
04/22/2025

Definition

A negative sequence relay, also known as an unbalance phase relay, is designed to safeguard the electrical system against negative sequence components. Its primary function is to protect generators and motors from unbalanced loads, which typically arise due to phase - to - phase faults. When such faults occur, the negative sequence components can cause excessive heating and mechanical stress in electrical machines, potentially leading to severe damage if not properly addressed.

Working Principle and Features

The negative sequence relay incorporates a specialized filter circuit that selectively responds only to negative sequence components present in the electrical system. Given that even a relatively small magnitude of overcurrent caused by negative sequence components can create hazardous operating conditions, the relay is configured with a low current setting. This enables it to detect and react promptly to subtle imbalances before they escalate into major problems.

Although the negative sequence relay is earthed, this grounding primarily serves to protect against phase - to - earth faults. However, it does not directly mitigate phase - to - phase faults; instead, its role is to detect the negative sequence components that are symptomatic of such faults and trigger appropriate protective actions.

Construction

The construction of the negative sequence relay is illustrated in the figure below. It features four impedances, denoted as Z1, Z2, Z3, and Z4, which are interconnected in a bridge configuration. These impedances are energized by current transformers, which sample the electrical current from the system under protection. The relay's operating coil is connected to the midpoints of this bridge circuit. This specific arrangement allows the relay to accurately sense the presence and magnitude of negative sequence components by analyzing the voltage differences across the bridge arms, facilitating reliable and precise operation for the protection of electrical systems.

image.png

In the circuit of the negative sequence relay, Z1 and Z3 exhibit purely resistive characteristics, while Z2 and Z4 possess both resistive and inductive properties. The values of impedances Z2 and Z4 are meticulously adjusted so that the currents passing through them consistently lag behind the currents flowing through Z1 and Z3 by an angle of 60 degrees.

When the current reaches junction A, it divides into two branches, namely I1 and I4. Significantly, the current I4 lags the current I1 by precisely 60 degrees. This specific phase - difference relationship is fundamental to the proper functioning of the negative sequence relay, enabling it to accurately detect and respond to negative sequence components within the electrical system.

image.png

Similarly, current from phase B split at junction C into two equal components I3 and I2, I2 lagging behind I3 by 60º.

image.png

The current I4 lags behind I1 by an angle of 30 degrees. Likewise, I2 lags behind IB by 30 degrees, while I3 leads IB by the same 30 - degree margin. The current flowing through junction B is equivalent to the algebraic sum of I1, I2, and IY. This precise angular relationship and current summation at junction B are critical for the proper functioning of the negative sequence relay, ensuring its ability to accurately detect unbalanced conditions within the electrical system by analyzing the phase and magnitude differences among these currents.image.png

Flow of Positive Sequence Current

The phasor diagram depicting the positive sequence components is illustrated in the figure below. In a scenario where the load is in a balanced state, the negative sequence current remains absent. Under such circumstances, the current passing through the relay can be described by the following equation. This relationship between the balanced load condition, the absence of negative sequence current, and the current through the relay is fundamental to understanding the normal operation and protective functions within the electrical system.

image.png

Operation Under Balanced Conditions

Consequently, the relay remains active during the operation of a balanced electrical system, ensuring continuous monitoring and readiness to respond to any potential anomalies.

Flow of Negative Sequence Current

As illustrated in the figure above, currents I1 and I2 exhibit equal magnitudes. Due to their equal and opposing nature, they effectively cancel each other out. As a result, only the current IY traverses the operating coils of the relay. To safeguard against the detrimental effects of even minor overloads, which can rapidly escalate into severe system issues, the relay's current setting is deliberately kept lower than the normal full - load rating current. This sensitive calibration allows the relay to promptly detect and react to unbalanced conditions caused by negative sequence components.

Flow of Zero Sequence Current

In the case of zero sequence current, currents I1 and I2 are phase - displaced from one another by an angle of 60 degrees. The resultant of these two currents aligns in phase with the current IY. Consequently, the operating coil of the relay experiences a total current that is precisely twice the magnitude of the zero sequence current. It is important to note that by connecting the current transformers (CTs) in a delta configuration, the relay can be rendered inoperative for zero sequence currents. In this delta connection setup, zero sequence currents do not flow through the relay, providing a means to selectively filter out or bypass certain types of fault currents depending on the system's protection requirements.

image.png

Induction Type Negative Sequence Relay

The construction of an induction type negative phase sequence relay closely resembles that of an induction type overcurrent relay. It features a metallic disc, typically fabricated from an aluminium coil, which rotates between two electromagnets: an upper electromagnet and a lower electromagnet.

The upper electromagnet is equipped with two windings. The primary winding of the upper electromagnet is linked to the secondary side of the current transformer (CT) connected to the line under protection. Meanwhile, the secondary winding of the upper electromagnet is connected in series with the windings of the lower electromagnet.

Owing to the presence of a centre tapping, the primary winding of the relay has three terminals. Phase R, with the assistance of CTs and an auxiliary transformer, energizes the upper half of the relay, while phase Y energizes the lower half. The auxiliary transformer is specifically adjusted such that its output lags by an angle of 120º rather than the conventional 180º.

Operation with Positive Sequence Currents

When positive sequence currents are present, currents IR and IY flow through the primary windings of the relay in opposite directions. The currents I’R and I’Y have equal magnitudes. This balanced current flow ensures that the relay remains in an inactive state, as there is no net force to trigger its operation.

Operation with Negative Sequence Currents

In the event of a fault, negative sequence current I is induced to flow through the primary winding of the relay. This negative sequence current disrupts the equilibrium within the relay, setting in motion a series of events that lead to the relay's activation and subsequent protective action.

image.png

The relay will initiate its operation once the magnitude of the fault current surpasses the pre - set value of the relay. This means that when the fault current becomes large enough to exceed the specific threshold determined for the relay, the relay is triggered into action to perform its protective function within the electrical system.

Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

How to Design and Install a Solar PV System?
How to Design and Install a Solar PV System?
Design and Installation of Solar PV SystemsModern society relies on energy for daily needs like industry, heating, transport, and agriculture, mostly met by non-renewable sources (coal, oil, gas). However, these cause environmental harm, are unevenly distributed, and face price volatility due to limited reserves—driving demand for renewable energy.Solar energy, abundant and capable of meeting global needs, stands out. Standalone PV systems (Fig 1) offer energy independence from utilities.
Edwiin
07/17/2025
Load Frequency Control (LFC) & Turbine Governor Control (TGC) in Power System
Load Frequency Control (LFC) & Turbine Governor Control (TGC) in Power System
Brief Introduction to Thermal Generating UnitsElectricity generation relies on both renewable and non - renewable energy resources. Thermal generating units represent a conventional approach to power production. In these units, fuels such as coal, nuclear energy, natural gas, biofuel, and biogas are combusted within a boiler.The boiler of a generating unit is an extremely complex system. In its simplest conception, it can be visualized as a chamber whose walls are lined with pipes, through which
Edwiin
06/06/2025
Why 3-Phase Power? Why Not 6, 12 or More for Power Transmission?
Why 3-Phase Power? Why Not 6, 12 or More for Power Transmission?
It is well-known that single-phase and three-phase systems are the most prevalent configurations for power transmission, distribution, and end-use applications. While both serve as fundamental power supply frameworks, three-phase systems offer distinct advantages over their single-phase counterparts.Notably, multi-phase systems (such as 6-phase, 12-phase, etc.) find specific applications in power electronics—particularly in rectifier circuits and variable frequency drives (VFDs)—wher
Edwiin
06/05/2025
How Many Poles and Towers are Situated Within a 1-km Span?
How Many Poles and Towers are Situated Within a 1-km Span?
The number of distribution poles and transmission towers within a 1-kilometer stretch of overhead lines varies significantly based on multiple factors, including voltage level, power line type, supporting structure, geographical location, local regulations, and specific grid requirements.In urban areas, distribution utility poles are typically positioned at closer intervals, while in rural regions, they are spaced farther apart. Additionally, the use of taller structures for higher-voltage trans
Edwiin
06/05/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!