• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Rockwill Smart Auto Recloser Quick Operation Guide

Rockwill
Field: Manufacturing
China

1. Local Quick Operation Procedure (On-site Panel)

Step 1: Open the Control Cabinet
Use the standard cabinet key to unlock the controller and open the door.

Step 2: Power Check and System Status

  • Ensure the controller is powered (battery level is sufficient or external AC/DC is connected).

  • Observe the LED indicators or HMI screen:

    • Breaker status (Open/Closed)

    • Fault or Lockout indicators

    • Communication and battery indicators

Step 3: Manually Open or Close the Recloser

  • To open (trip) the circuit: press the “OFF” button.

  • Wait for the LED or screen to confirm the recloser is open.

  • After clearing the fault, press the “ON” button to reclose.

Step 4: Switch Operation Mode

  • Use the mode selector switch or HMI setting to choose “Manual” or “Auto” mode.

  • In “Auto” mode, the recloser will automatically execute its reclosing logic after faults.

Step 5: Reset After Lockout (if applicable)

  • If a fault lockout has occurred, press the “RESET” button.

  • Confirm that lockout indicators are cleared before re-energizing.

2. Remote Quick Operation Procedure (Via SCADA/RTU)

Step 1: Confirm Connection
Ensure the recloser is communicating via SCADA using GPRS, 4G, or fiber. The remote interface (SCADA/DMS) must show online status.

Step 2: Send Remote Control Commands

  • Use the SCADA interface to issue “Open” or “Close” command.

  • Confirm that the recloser changes status and feedback is updated.

Step 3: Monitor Live Data

  • Observe real-time values such as current, voltage, fault alarms, and breaker position from the SCADA interface.

Step 4: Remote Reset (if available)

  • If lockout occurs and remote reset is enabled, send the “Reset” command.

  • Otherwise, reset must be performed locally.

3. Summary of Key Actions

  • To Open (Trip): Press “OFF” on HMI or send “Open” via SCADA

  • To Close (Reclose): Press “ON” on HMI or send “Close” via SCADA

  • To Switch Mode: Set the selector to “Auto” for automatic reclose, “Manual” for local control

  • To Reset Fault Lockout: Press “RESET” on HMI after fault clearance

  • To Monitor Status: Check HMI screen or SCADA dashboard for live breaker status and fault indicators

4. Important Notes

  • Always confirm the system is free from faults before reclosing.

  • In Auto mode, the recloser may automatically reclose based on configured time-delay sequences.

  • Ensure safety protocols and PPE are followed at all times.

  • Protection settings and reclosing sequences should be pre-configured using authorized software tools.

Give a tip and encourage the author!

Recommended

Impact of DC Bias in Transformers at Renewable Energy Stations Near UHVDC Grounding Electrodes
Impact of DC Bias in Transformers at Renewable Energy Stations Near UHVDC Grounding ElectrodesWhen the grounding electrode of an Ultra-High-Voltage Direct Current (UHVDC) transmission system is located close to a renewable energy power station, the return current flowing through the earth can cause a rise in ground potential around the electrode area. This ground potential rise leads to a shift in the neutral-point potential of nearby power transformers, inducing DC bias (or DC offset) in their
01/15/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Distribution Equipment Transformer Testing, Inspection, and Maintenance
1.Transformer Maintenance and Inspection Open the low-voltage (LV) circuit breaker of the transformer under maintenance, remove the control power fuse, and hang a “Do Not Close” warning sign on the switch handle. Open the high-voltage (HV) circuit breaker of the transformer under maintenance, close the grounding switch, fully discharge the transformer, lock the HV switchgear, and hang a “Do Not Close” warning sign on the switch handle. For dry-type transformer maintenance: first clean the porcel
12/25/2025
How to Test Insulation Resistance of Distribution Transformers
In practical work, insulation resistance of distribution transformers is generally measured twice: the insulation resistance between thehigh-voltage (HV) windingand thelow-voltage (LV) winding plus the transformer tank, and the insulation resistance between theLV windingand theHV winding plus the transformer tank.If both measurements yield acceptable values, it indicates that the insulation among the HV winding, LV winding, and transformer tank is qualified. If either measurement fails, pairwise
12/25/2025
Send inquiry
+86
Click to upload file

IEE Business will not sell or share your personal information.

Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.