Live tank SF6 gas circuit breaker Manufacturer 40.5kV to 362kV

  • Live tank SF6 gas circuit breaker Manufacturer 40.5kV to 362kV

Key attributes

Brand ROCKWILL
Series RHB
Rated voltage 40.5kV/52kV/123kV/145kV/363kV
Rated current up to 4000A
Rated peak withstand current up to 158kA
Rated frequency 50/60Hz
Description

The RHB type Live tank SF6 gas circuit breaker is specifically designed for outdoor high - voltage environments. Utilizing self - blast arc - extinguishing technology and taking advantage of the excellent insulating and arc - extinguishing properties of SF₆ gas.

It can quickly quench arcs, ensuring the efficient interruption of fault currents. With a compact and robust structure, it can adapt to various harsh weather conditions. 

It boasts high reliability and a long service life, which can significantly reduce maintenance frequency, making it a key device for enhancing the safety and stability of power systems.

Main function introduction:

  • SF6 gas is used for arc extinguishing

  • Monitor with a pointer-type density relay

  • Adopt the self-blast arc extinguishing principle

  • Adopt pointer-type density relays for pressure and density monitoring

Operating‑schematic Diagram of Circuit‑breaker Contacts

Operating‑schematic Diagram of Circuit‑breaker Contacts

Technology parameters:

RHB-52

Item Unit Parameter
Rated voltage kV 52
Rated frequency Hz 50/60
Rated current A up to 4000
Rated short-time withstand current, up to 3 s kA up to 63
Rated peak withstand current kA up to 158
Rated short-duration power-frequency withstand voltage, 1 min kV 95
Power-frequency withstand voltage, 1 min across open contacts kV 95
Rated lightning impulse withstand voltage, 1.2/50 μs kV 200
Rated lightning impulse withstand voltage, 1.2/50 μs, across open contacts kV 250
Rated filling pressure (abs. at 20 °C) circuit-breaker/other components MPa 0.5
Minimum functional pressure (abs. at 20 °C) circuit-breaker/other components MPa 0.4

RHB-123/145

Item Unit 123kV 145kV
Rated voltage kV 123 145
Rated frequency Hz 50/60
Rated current A up to 4000
Rated short-time withstand current, up to 3 s kA up to 63
Rated peak withstand current kA up to 158
Rated short-duration power-frequency withstand voltage,1min kV 230 275
Power-frequency withstand voltage,1min across open contacts kV 265 315
Rated lightning impulse withstand voltage,1.2/50 μs kV 550 650
Rated lightning impulse withstand voltage,1.2/50 μs,across open contacts kV 650 750
Rated filling pressure (abs. at 20℃) circuit-breaker MPa 0.6
Minimum functional pressure (abs. at 20℃) circuit-breaker MPa 0.5
Temperature range (ambient) -30~+40
Type of installation- —— outdoor
Partial discharge capacity pC <5
SF₆ leakage rate per year —— <0.5%
Maintenance cycle Year 30

RHB-363 

Item Unit Parameter
Rated voltage kV 362
Rated frequency Hz 50/60
Rated current A up to 4000
Rated short-time withstand current, up to 3 s kA up to 63
Rated peak withstand current kA 158
Rated short-duration power-frequency withstand voltage, 1 min kV 450
Power-frequency withstand voltage, 1 min across open contacts kV 520
Rated lightning impulse withstand voltage, 1.2/50  μs kV 1175
Rated lightning impulse withstand voltage, 1.2/50 μs, across open contacts kV 1380
Rated filling pressure (abs. at 20 ℃) circuit-breaker MPa 0.6
Minimum functional pressure (abs. at 20 ℃) circuit-breaker MPa 0.5

Device structure:

RHB-40.5

RHB type Live tank SF6 gas circuit breaker.png

RHB-72.5

72.5kV RHB type Live tank SF6 gas circuit breaker.jpg

RHB-123/145

123/145kV RHB type Live tank SF6 gas circuit breaker.jpg

RHB-170

170kV RHB type Live tank SF6 gas circuit breaker.jpg

RHB-252

252kV RHB type Live tank SF6 gas circuit breaker.jpg

RHB-362

363kV RHB type Live tank SF6 gas circuit breaker.png

Service environment

Ambient temperature ‑30°C ~ +40°C
Altitude <1000m
Wind speed <34m/s
Daily temperature difference <25°C
Solar irradiance < 0.1W/cm²
Monthly average relative humidity <90%
Ice‑coating thickness <10mm
Seismic acceleration resistance Horizontal <0.2g, vertical <0.1g
Installation location Outdoor

Solutions - Live tank

  • SF6 Circuit Breaker Seal Failure Analysis and HNBR Upgrade Strategy for Venezuela 24kV Network
    Core Challenge: The 24kV outdoor SF6 circuit breakers operated by Venezuela's National Electric Corporation (CORPOELEC), under the C5-M high salt mist corrosion environment along the Lake Maracaibo coast and an annual average temperature of 32°C, experience accelerated O-ring compression set, causing the SF6 annual leakage rate to deteriorate from the design value of ≤0.1% to over 1% in actual operation, frequently triggering low-pressure lockout alarms. This is one of the key contributin

Documentation Resource Library Live tank

Restricted
RHB Hybird Switchgear Catalog RHB Hybird Switchgear Catalog
Selection Guide
English
PDF
Public.
RHB-72.5 Live tank SF6 gas circuit breaker FLYER RHB-72.5 Live tank SF6 gas circuit breaker FLYER
Brochure
English
Public.
RHB-145 Live tank SF6 gas circuit breaker FLYER RHB-145 Live tank SF6 gas circuit breaker FLYER
Brochure
English
Public.
RHB-252 Live tank SF6 gas circuit breaker FLYER RHB-252 Live tank SF6 gas circuit breaker FLYER
Brochure
English
Public.
RHB-170 Live tank SF6 gas circuit breaker FLYER RHB-170 Live tank SF6 gas circuit breaker FLYER
Brochure
English
Public.
RHB-52 Live tank SF6 gas circuit breaker FLYER RHB-52 Live tank SF6 gas circuit breaker FLYER
Brochure
English
Restricted
RHB Type Live tank SF6 gas circuit breaker 11kV…550kV RHB Type Live tank SF6 gas circuit breaker 11kV…550kV
Catalogue
English
PDF
Public.
Rockwill Electric Group Profile Rockwill Electric Group Profile
Brochure
English
Restricted
RHB-330kV Live tank SF6 gas circuit breaker RHB-330kV Live tank SF6 gas circuit breaker
Drawings
English
PDF

Frequently asked questions

The core difference is the arc-extinguishing medium. A VCB uses a high vacuum inside a sealed ceramic or glass envelope — the vacuum rapidly diffuses ions and metal vapor after current zero, achieving arc extinction in <10 ms. An SF₆ CB uses sulfur hexafluoride gas, which has strong electron affinity — it captures free electrons to form heavy negative ions, quickly depleting the arc channel's conductivity.

In a live tank breaker, the arc chamber is mounted at the top or side of the column, exposed to ambient air. In a dead tank breaker, the arc chamber is placed inside the metal tank, fully sealed.

 Live tank breakers are well-suited for outdoor high-voltage distribution with a dispersed layout. Dead tank breakers flexibly adapt to both indoor and outdoor applications, especially in space-constrained substations or where compact installation is required.

Know your supplier

Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m² Total staff: 700+ Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: Medium and High Voltage Switchgear/Power and Distribution Transformers/Instrument Transformers and Sensors/Lightning Protection and Electrical Insulation/Substations and E-Houses/Electrical Panel and Controlgear
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Login
or continue with
New here?
Register