HV Live tank SF6 gas circuit breaker 252kV 420kV 550kV

  • HV Live tank SF6 gas circuit breaker 252kV 420kV 550kV

Key attributes

Brand ROCKWILL
Series RHB
Rated voltage 252kV-550kV
Rated current up to 5000 A
Rated short-time withstand current up to 63
Rated peak withstand current up to 158
Description

Equipped with CT-type spring mechanism, this outdoor live tank SF₆ breaker serves 50Hz three-phase grid for circuit control and protection, allowing single/three-pole switching and auto-reclosing.

With three-phase post porcelain structure and self-blast arc extinction, SF₆ fills all poles for insulation and arc quenching. Pointer density relay tracks gas status. Compact, low-power, low-noise and easy to install; customization supported.

Core Advantages

  • Three-phase post porcelain construction: Single shared spring mechanism for synchronized three-pole operation, neat compact layout for outdoor installation.

  • Integrated SF₆ gas system: Interconnected gas chambers across three poles; SF₆ serves as insulation & arc-quenching medium to guarantee steady performance.

  • Pointer density relay: Real-time SF₆ pressure & density monitoring for early fault warning and safe running.

  • Self-blast arc extinction: Lower required operating power and improved mechanical efficiency.

  • Customization available: Tailored design to satisfy individual project requirements, consult our sales team for details.

Main technical parameters

RHB-252

 

Item Unit Parameter
Rated voltage kV 252
Rated frequency Hz 50/60
Rated current A up to 5000
Rated short-time withstand current, up to 3 s kA up to 63
Rated peak withstand current kA up to 158
Rated short-duration power-frequency withstand voltage, 1 min kV 460
Power-frequency withstand voltage, 1 min across open contacts kV 530
Rated lightning impulse withstand voltage, 1.2/50 μs kV 1050
Rated lightning impulse withstand voltage, 1.2/50 μs, across open contacts kV 1200
Rated filling pressure (abs. at 20 ℃) circuit-breaker MPa 0.6
Minimum functional pressure (abs. at 20 ℃) circuit-breaker MPa 0.5
Temperature range (ambient) -30~+40
Type of installation outdoor
Partial discharge pC <5
Annual SF₆ leakage rate <0.5%
Maintenance cycle Year 30

 

RHB-420

 

Item Unit Parameter
Rated voltage kV 420
Rated frequency Hz 50/60
Rated current A up to 5000
Rated short-time withstand current, up to 3 s kA up to 63
Rated peak withstand current kA up to 158
Rated short-duration power-frequency withstand voltage, 1 min kV 740
Power-frequency withstand voltage, 1 min across open contacts kV 850
Rated lightning impulse withstand voltage, 1.2/50 μs kV 1425
Rated lightning impulse withstand voltage, 1.2/50 μs, across open contacts kV 1550
Rated filling pressure (abs. at 20 ℃) circuit-breaker MPa 0.6
Minimum functional pressure (abs. at 20 ℃) circuit-breaker MPa 0.5
Temperature range (ambient) -30~+40
Type of installation outdoor
Partial discharge pC <5
Annual SF₆ leakage rate <0.5%
Maintenance cycle Year 30

 

 

RHB-550

Item Unit Parameter
Rated voltage kV 550
Rated frequency Hz 50/60
Rated current A up to 5000
Rated short-time withstand current, up to 3 s kA up to 63
Rated peak withstand current kA up to 158
Rated short-duration power-frequency withstand voltage, 1 min kV 830
Power-frequency withstand voltage, 1 min across open contacts kV 950
Rated lightning impulse withstand voltage, 1.2/50 μs kV 1675
Rated lightning impulse withstand voltage, 1.2/50 μs, across open contacts kV 2125
Rated filling pressure (abs. at 20 ℃) circuit-breaker MPa 0.6
Minimum functional pressure (abs. at 20 ℃) circuit-breaker MPa 0.5
Temperature range (ambient) -30~+40
Type of installation outdoor
Partial discharge pC <5
Annual SF₆ leakage rate <0.5%
Maintenance cycle Year 30

Service Conditions

  • Ambient temperature: -30℃~+40℃

  • Altitude: <1000m

  • Max wind speed: <34m/s

  • Daily temperature variation: <25℃

  • Solar irradiance: <0.1W/cm²

  • Monthly average RH: <90%

  • Ice coating: <10mm

  • Seismic resistance: Horizontal<0.2g, Vertical<0.1g

  • Mounting: Outdoor

Outline Dimension Drawing

RHB-245

HV Live tank SF6 gas circuit breaker 252kV 420kV 550kV

 


Documentation Resource Library HV SF6 circuit breaker

Restricted
Outdoor live tank SF6 circuit breaker Outdoor live tank SF6 circuit breaker
Catalogue
English
PDF
Public.
RHB-145 Live tank SF6 gas circuit breaker FLYER RHB-145 Live tank SF6 gas circuit breaker FLYER
Brochure
English
Public.
RHB-252 Live tank SF6 gas circuit breaker FLYER RHB-252 Live tank SF6 gas circuit breaker FLYER
Brochure
English
Public.
RHB-170 Live tank SF6 gas circuit breaker FLYER RHB-170 Live tank SF6 gas circuit breaker FLYER
Brochure
English
Restricted
RHB Type Live tank SF6 gas circuit breaker 11kV…550kV RHB Type Live tank SF6 gas circuit breaker 11kV…550kV
Catalogue
English
PDF
Public.
Rockwill Electric Group Profile Rockwill Electric Group Profile
Brochure
English
Public.
RHB-245 Live tank SF6 gas circuit breaker RHB-245 Live tank SF6 gas circuit breaker
Drawings
English

Frequently asked questions

In a live tank breaker, the arc chamber is mounted at the top or side of the column, exposed to ambient air. In a dead tank breaker, the arc chamber is placed inside the metal tank, fully sealed.

ABB’s high-voltage live-tank vacuum breakers are reliable but costly with long lead times. Hitachi Energy is mature yet lacks local high-voltage track records and smart features. Schneider Electric excels in 40.5kV distribution but is limited in voltage range and extreme performance. In contrast, Rockwill offers up to 363kV SF₆-free vacuum solutions with fast local service and spare parts delivery. Featuring robust mechanisms, full smart functions, and superior resistance to extreme cold, heavy salt fog, and short-circuit currents, our breakers ensure long maintenance-free service and lower LCC.

Q:Can Rockwill custom-engineer or modify Live tank Vacuum circuit breaker specifications to meet project-specific requirements?

A:
Rockwill provides comprehensive customized design and parameter modification for live tank vacuum circuit breakers to meet diverse project requirements. Backed by our professional R&D team, we flexibly adjust product structures, technical parameters and environmental adaptability, delivering exclusive tailored solutions in line with various on-site conditions and project standards.

Know your supplier

Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m² Total staff: 700+ Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: Medium and High Voltage Switchgear/Power and Distribution Transformers/Instrument Transformers and Sensors/Lightning Protection and Electrical Insulation/Substations and E-Houses/Electrical Panel and Controlgear
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Login
or continue with
New here?
Register