Key attributes

Brand ROCKWILL
Series RHP
Rated maximum voltage 40.5kV 72.5 kV 145 kV 170kV 245kV
Rated maximum current ≤5000 A
Rated short circuit breaking current 31.5-63 kA
Rated frequency 50/60 Hz
Description

The RHP type HGIS electrical apparatus is a new type of high-voltage power equipment. It retains the advantages of GIS combined electrical apparatus, such as compactness, high reliability, and low operation and maintenance requirements, while innovatively retaining the busbar as a conventional AIS arrangement for onsite installation and connection.

This design effectively overcomes the drawbacks associated with traditional AIS equipment, including large footprint, numerous connection points, and high inspection and maintenance workloads.

It is suitable for 40.5kV up to 245kV transmission and distribution systems in power plants, substations, railway stations, ports, and large industrial and mining enterprises. It is particularly well-suited for spaceconstrained projects such as mountainous substations and urban substations, and can be installed indoors, outdoors, or on rooftops. 

Product Showcase Video

 

Advantage Of Product

HGIS is a type of gas-insulated metal-enclosed switchgear that integrates the circuit breaker, disconnector/earthing switch combination, current transformer, and voltage transformer into a single unit.
This specific design confers the following key advantages over both conventional GIS and AIS:

  • High Operational Reliability & Minimal Maintenance: Requires very little maintenance, with an estimated maintenance-free service life of up to 25 years.

  • Simplified Outdoor Installation: Designed for direct outdoor installation with minimal civil engineering and electrical work, leading to a straightforward installation process.

  • Eco-Friendly with Low SF6 Usage: Consumes significantly less SF6 gas (only 20% of the amount used in a full GIS), making it a more environmentally friendly choice.

  • Low Life-Cycle Cost: Offers a lower total cost of ownership over its entire operational lifespan.

  • Compact, Lightweight & Resilient Design: Features a compact and lightweight construction (utilizing silicone rubber bushings and aluminum tanks) with excellent pollution resistance, hydrophobic properties, and high seismic withstand capability.

  • Rapid Deployment with Minimal Outage: The short installation time and reduced number of required power outages make it exceptionally well-suited for extension or retrofit projects in power plants and substations.

Hybrid Gas Insulated Switchgear 40.5kV up to 245kV

An HGIS unit is equipped with one three-position disconnector/earthing switch at each end of the circuit breaker. This configuration forms an independent, self-contained functional unit that operates without the need for any additional external three-position disconnector/earthing switches.

The HGIS employs a modular design philosophy. It can be customized with varying numbers of three-position disconnector/earthing switch modules to meet specific client requirements. Additionally, optional components such as voltage transformers (VTs) and surge arresters can be integrated.

Three-position disconnector/earthing switch

Three-position disconnector/earthing switch

Main technical parameters 

RHP-40.5 

Item Unit Parameters
Rated maximum voltage kV 40.5
Rated maximum current A ≤2000
Rated frequency Hz 50/60
First opening pole coefficient - 1.5
Rated short circuit breaking current kA 31.5
Rated short-circuit duration s 4
Rated out of step breaking current kA 7.9
Rated peak value withstand current kA 80
Rated 1min power frequency withstand voltage (Dry/Wet) kV To ground 95
Break 118
Rated lightning impulse voltage kV To ground 185
Break 215
Operation sequence - O-0.3s-CO-180s-CO
Opening time ms 50±10
Closing time ms 90±20
Close-open time ms ≤100
Main circuit resistance μΩ ≤150
Rated SF6 gas pressure (20℃ gauge pressure) Mpa 0.5
Alarm/blocking pressure(20℃ gauge pressure) Mpa 0.45/0.4
SF6 annual gas leakage rate % ≤0.5
Gas moisture content Ppm(v) ≤150
Mechanical life times 6000

RHP-72.5 

Item Unit Parameters
Rated maximum voltage kV 72.5
Rated maximum current A ≤3150
Rated frequency Hz 50/60
First opening pole coefficient - 1.5
Rated short circuit breaking current kA 40
Rated short-circuit duration s 4
Rated out of step breaking current kA 10
Rated peak value withstand current kA 100
Rated 1min power frequency withstand voltage (Dry/Wet) kV To ground 140
Break 160
Rated lightning impulse voltage kV To ground 325
Break 375
Operation sequence - O-0.3s-CO-180s-CO
Opening time ms 32±7
Closing time ms 85±10
Close-open time ms ≤60
Main circuit resistance μΩ ≤100
Rated SF6 gas pressure (20℃ gauge pressure) Mpa 0.5
Alarm/blocking pressure(20℃ gauge pressure) Mpa 0.55/0.5
SF6 annual gas leakage rate % ≤0.5
Gas moisture content Ppm(v) ≤150
Mechanical life times 6000

RHP-145 

Item Unit Parameters
Rated maximum voltage kV 145
Rated maximum current A ≤3150
Rated frequency Hz 50/60
First opening pole coefficient - 1.5
Rated short circuit breaking current kA 40
Rated short-circuit duration s 4
Rated out of step breaking current kA 10
Rated peak value withstand current kA 100
Rated 1min power frequency withstand voltage (Dry/Wet) kV To ground 275
Break 315
Rated lightning impulse voltage kV To ground 650
Break 750
Operation sequence - O-0.3s-CO-180s-CO
Opening time ms 32±7
Closing time ms 85±10
Close-open time ms ≤60
Main circuit resistance μΩ ≤100
Rated SF6 gas pressure (20℃ gauge pressure) Mpa 0.5
Alarm/blocking pressure(20℃ gauge pressure) Mpa 0.55/0.5
SF6 annual gas leakage rate % ≤0.5
Gas moisture content Ppm(v) ≤150
Mechanical life times 6000

 RHP-170 

Item Unit Parameters
Rated maximum voltage kV 170
Rated maximum current A ≤4000
Rated frequency Hz 50/60
First opening pole coefficient - 1.3
Rated short circuit breaking current kA ≤50
Rated short-circuit duration s 4
Rated out of step breaking current kA 10
Rated peak value withstand current kA ≤125
Rated 1min power frequency withstand voltage (Dry/Wet) kV To ground 325
Break 375
Rated lightning impulse voltage kV To ground 750
Break 850
Operation sequence - O-0.3s-CO-180s-CO
Opening time ms 32±7
Closing time ms 85±10
Close-open time ms ≤60
Main circuit resistance μΩ ≤100
Rated SF6 gas pressure (20℃ gauge pressure) Mpa 0.5
Alarm/blocking pressure(20℃ gauge pressure) Mpa 0.55/0.5
SF6 annual gas leakage rate % ≤0.5
Gas moisture content Ppm(v) ≤150
Mechanical life times 6000

RHP-245 

Item Unit Parameters
Rated maximum voltage kV 245
Rated maximum current A ≤5000
Rated frequency Hz 50/60
First opening pole coefficient - 1.3
Rated short circuit breaking current kA ≤63
Rated short-circuit duration s 4
Rated out of step breaking current kA 7.9
Rated peak value withstand current kA ≤158
Rated 1min power frequency withstand voltage (Dry/Wet) kV To ground 460
Break 530
Rated lightning impulse voltage kV To ground 1050
Break 1200
Operation sequence - O-0.3s-CO-180s-CO
Opening time ms 50±10
Closing time ms 90±20
Close-open time ms ≤100
Main circuit resistance μΩ ≤150
Rated SF6 gas pressure (20℃ gauge pressure) Mpa 0.5
Alarm/blocking pressure(20℃ gauge pressure) Mpa 0.45/0.4
SF6 annual gas leakage rate % ≤0.5
Gas moisture content Ppm(v) ≤150
Mechanical life times 6000

Normal Service Conditions

Item Unit Parameter
Altitude m <1000*
Ambient Temperature °C -40 to +40**
Maximum Daily Temperature Difference °C 30
Maximum Relative Humidity % 100

Note :

  • For installations at altitudes exceeding 1000 meters, the manufacturer must be consulted during the ordering process to implement necessary insulation reinforcement measures.

  • When operating in regions with ambient temperatures of -40&deg;C, measures must be taken to prevent the liquefaction of SF6 gas.

Ingress Protection (IP) Rating & Pollution Severity Class:The HGIS is designed with an IP54 protection rating and is suitable for a Class IV polluted atmosphere.

Construction Type:The HGIS features a three-phase, segregated tank construction.

Dimension Diagram

RHP-40.5

Compact Hybrid Gas Insulated Switchgear 40.5kV

RHP-72.5

Compact Hybrid Gas Insulated Switchgear 72.5kV

RHP-245

Hybrid Gas Insulated Switchgear 245kV

Service environment

Air temperature
Maximum temperature: +40°C;
Minimum temperature: -40°C
Humidity Daily average humidity 100%.
Above sea level Maximum installation altitude: 1000m.

Documentation Resource Library Gas Insulated Switchgear

Restricted
RHP type Hybrid Gas Insulated Switchgear catalogue RHP type Hybrid Gas Insulated Switchgear catalogue
Catalogue
English
PDF
Public.
Rockwill Electric Group Profile Rockwill Electric Group Profile
Brochure
English
Restricted
RHP-245 Hybrid Gas Insulated Switchgear RHP-245 Hybrid Gas Insulated Switchgear
Drawings
English
PDF
Restricted
RHP-72.5 Hybrid Gas Insulated Switchgear RHP-72.5 Hybrid Gas Insulated Switchgear
Drawings
English
PDF
Restricted
RHP-72.5+PT Hybrid Gas Insulated Switchgear RHP-72.5+PT Hybrid Gas Insulated Switchgear
Drawings
English
PDF
Restricted
RHP-145 Hybrid Gas Insulated Switchgear RHP-145 Hybrid Gas Insulated Switchgear
Drawings
English
PDF
Restricted
RHP-145+PT Hybrid Gas Insulated Switchgear RHP-145+PT Hybrid Gas Insulated Switchgear
Drawings
English
PDF
Restricted
RHP-145-2000A-40kA Hybrid Gas Insulated Switchgear RHP-145-2000A-40kA Hybrid Gas Insulated Switchgear
Drawings
English
PDF
Restricted
RHP-170 Hybrid Gas Insulated Switchgear RHP-170 Hybrid Gas Insulated Switchgear
Drawings
English
PDF
Restricted
RHP-245(T) type Hybrid Gas Insulated Switchgear RHP-245(T) type Hybrid Gas Insulated Switchgear
Drawings
English
PDF
Restricted
RHP-245 type Hybrid Gas Insulated Switchgear RHP-245 type Hybrid Gas Insulated Switchgear
Drawings
English
PDF

Frequently asked questions

RHP HGIS integrates circuit breaker, three‑position disconnector‑earthing switch, CT/VT into gas‑filled tank units, while retaining conventional open‑type AIS busbars for on‑site connection. Compared with full GIS, it consumes only 20% SF₆ gas, lowers equipment investment. Compared with conventional AIS, it greatly reduces footprint, connection points and maintenance workload. It balances compactness, cost and installation flexibility.

The modular gas‑tank main units feature high reliability with up to 25‑year maintenance‑free service life. Annual SF₆ leakage rate ≤0.5%. Mechanical life reaches 6000 times. Only open‑type busbar part needs regular inspection. Overall maintenance workload is far lower than traditional AIS. For altitude over 1000 m or‑40 °C extreme cold area, please inform us for customized insulation or anti‑liquefaction measures.

Yes. Rockwill provides OEM & ODM service for RHP‑type HGIS. We select qualified regional partners with solid high‑voltage engineering capability and local after‑sales capacity. We focus on technical‑oriented cooperation rather than simple resale business.

Know your supplier

Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m² Total staff: 700+ Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: Medium and High Voltage Switchgear/Power and Distribution Transformers/Instrument Transformers and Sensors/Lightning Protection and Electrical Insulation/Substations and E-Houses/Electrical Panel and Controlgear
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Login
or continue with
New here?
Register