Actual Capacitor kVAR Calculator – Under Non-Rated Voltage and Frequency

In certain power networks, a significant difference may exist between the rated voltage and the service voltage. For example, a capacitor rated at 400 V may be used in a 380 V system. In such cases, the actual reactive power output of the capacitor varies with voltage and frequency. This tool calcul
V
Hz
V
Hz

Current calculation formulas

Qr = Qc * (U_in / Uc)² * (f_in / fc)

Qc = Qr * (Uc / U_in)² * (fc / f_in)

Definitions

Qr = Capacitor power at different voltage (kVAr)
Qc = Capacitor power (kVAr)
U_in = In voltage (V)
Uc = Capacitor voltage (V)
f_in = Supply frequency (Hz)
fc = Capacitor frequency (Hz)

Description

In certain power networks, a significant difference may exist between the rated voltage and the service voltage. For example, a capacitor rated at 400 V may be used in a 380 V system. In such cases, the actual reactive power output of the capacitor varies with voltage and frequency. This tool calculates the real reactive power delivered by a capacitor under non-rated conditions.

Application Scenarios

1. Industrial substation reactive power compensation

2. Capacitor bank selection verification

3. System voltage fluctuation analysis

4. Capacitor lifespan evaluation (overvoltage/undervoltage)

Parameter Description

Parameter Description
Input Voltage Actual operating voltage of the network (e.g., 380V, 400V), unit: Volts (V)
Supply Frequency Operating frequency of the network (e.g., 50 Hz or 60 Hz), unit: Hertz (Hz)
Capacitor Rated Power Nominal reactive power rating of the capacitor, unit: kVAR
Capacitor Rated Voltage Rated voltage specified on the capacitor nameplate, unit: Volts (V)
Capacitor Rated Frequency Design frequency of the capacitor, typically 50 Hz or 60 Hz

Calculation Principle

The reactive power output of a capacitor is proportional to the square of the applied voltage:

Q_actual = Q_rated × (U_in / U_rated)² × (f_supply / f_rated)

Where:
Q_actual: Actual reactive power output (kVAR)
Q_rated: Rated reactive power of the capacitor (kVAR)
U_in: Input voltage (V)
U_rated: Rated voltage of the capacitor (V)
f_supply: Supply frequency (Hz)
f_rated: Rated frequency of the capacitor (Hz)

A 10% increase in voltage results in approximately 21% higher reactive power (due to quadratic relationship)
Overvoltage can cause overheating, insulation breakdown, or reduced lifespan

Usage Recommendations

1. Avoid long-term operation above the capacitor's rated voltage

2. Select capacitors with slightly higher rated voltage than system voltage (e.g., 400V for 380V systems)

3. Use step-by-step switching in multi-level capacitor banks to prevent overcompensation

4. Combine with power factor controllers for dynamic reactive power management