RHB-123 Live tank SF6 gas circuit breaker
Drawings · ROCKWILL

RHB-123 Live tank SF6 gas circuit breaker

RHB-123 outdoor HV circuit breaker: 123kV, 2000-3150A, lightning impulse 550/650kV, short-time 31.5-40kA, making peak 80-100kA. For 123kV grid switching and fault conditions.

Add us on Google
Updated2026.09
LanguageEnglish
FilePDF · 302.5 KB
Live tank circuit breakerSF6 gas circuit breaker
Download

Document description

RHB‑123 is a 123 kV outdoor high‑voltage circuit breaker with robust mechanical structure, strict requirements for foundation static/dynamic load and installation height difference. It complies with IEC 62271‑100 for high‑voltage switchgear, suitable for outdoor power transmission projects.

Related Products

Frequently asked questions

It complies with IEC 62271‑100 high‑voltage switchgear standard for outdoor transmission applications.

Unit weight:13000KG. Package‑1: 2920×1300×2300 (1pc, 10000KG); Package‑2:1100×580×2300 (1pc, 3000KG).

Foundation static load:150000N; horizontal dynamic load 50000N, vertical dynamic load 230000N (including equipment self‑weight). The height difference of each foundation surface shall not exceed 2 mm.