Product specification for RE1605 Air-cooling Battery Pack
RE1605 air-cooling battery pack: 51.2VDC rated, 140A charge-discharge, 280Ah, operating 40-58.4VDC. No switchgear parameters (lightning impulse, short-time withstand, making).
RE1605 air-cooling battery pack: 51.2VDC rated, 140A charge-discharge, 280Ah, operating 40-58.4VDC. No switchgear parameters (lightning impulse, short-time withstand, making).
Adopts 1P16S LFP cells, air‑cooling TRM thermal runaway management, integrated BMU, 4 hanging lugs & 4 M8 mounting holes, weight 110±5kg. No explicit IEC number in datasheet, generally complies with IEC 62619, IEC 63056 energy‑storage battery standards.
It has BAT+/BAT‑ high‑power DC terminals, fan interface and BMU communication interface. Fan model: Tesoer TX8038H24B‑G; BMU model: BMSer BMU‑B30‑16‑504.
Keep rain‑proof and moisture‑proof during transport; forbid throwing, rolling, inversion and co‑transport with corrosive substances. Storage environment shall be dry, ventilated and cool; long‑term storage temperature 0‑35℃, humidity ≤85% without condensation.
Do not short‑circuit BAT+ and BAT‑, do not immerse in water, do not puncture cells or disassemble randomly. Never mix batteries of different brands or types. Stop using immediately if smell, heating, swelling or deformation occurs.