General Protection Device
Operating Instruction · Rw Energy

General Protection Device

General‑purpose feeder protection‑control device. Primary setting up to 42kV, ‑10℃~+55℃ operating, ‑25℃~+70℃ storage. 3‑stage overcurrent, sensitive earth‑fault, max 4 auto‑reclose, SOE logging for integrated functions.

Add us on Google
Updated2026.10
LanguageEnglish
FilePDF · 2 MB
General Protection Devicemicrocomputer protection device (MPPD)microcomputer protection unit

Document description

This document describes general‑purpose feeder protection & control device complying with IEC 60255‑1:2022, IEC 60255‑26:2023, IEC 60255‑27:2023, with mechanical tests IEC 60255‑21‑1and climatic tests IEC 60068‑2‑1, IEC 60068‑2‑78.

It integrates three‑stage phase overcurrent and sensitive earth‑fault protection with directional earth‑fault, cold‑load pickup, reclose‑acceleration, manual close‑acceleration, over‑voltage & under‑voltage functions. The maximum primary‑side setting value for over‑/under‑voltage protection reaches 42 kV. It supports up to 4 auto‑reclosing shots, manual reset is required after fault lockout. It is equipped with LCD‑keypad HMI and optional RF remote controller. Hardware supports 2‑phase / 3‑phase CT wiring, 7 binary inputs and 2 binary outputs. Communication ports RS485, RS232, RJ45 support IEC60870‑5‑101/104, DNP3.0 and Modbus‑RTU. Non‑volatile flash memory stores minimum 100 historical fault & SOE records without data loss after power‑off. It adapts to AC/DC operating circuits for various breakers, applied in cabinet‑mount and pole‑mount distribution automation.

Related Products

Frequently asked questions

Reclose‑acceleration activates after auto‑reclosing operation. Manual‑close acceleration applies for local /remote manual closing onto faulted feeder. Their exit‑time parameters can be set independently.

Optional RF remote only supports trip, close and alarm reset; unlock long‑press is mandatory before closing. No protection‑setting modification is allowed. Parameters can only be edited via local keypad or remote SCADA. Metal cabinet attenuates radio signal, operate with cabinet door open.

Minimum 100 historical events are stored. Fault, SOE and alarm records are saved in non‑volatile flash and retained at power‑off. Password‑protected manual partial or full clearing is available when storage is full.

No. Non‑directional earth‑fault is factory default. Directional logic shall be specified during ordering, zero‑sequence current and angle parameters need correct site configuration.