| Category |
Parameters |
Specifications |
| Power Characteristics |
Input Voltage (Uin) |
300VDC - 800VDC ±10% |
| Output Voltage (Uout) |
Uin |
| Efficiency |
99.7% |
| Protection Features |
Short-circuit Instantaneous Protection |
250% - 400% Rated Current |
| Instantaneous Protection Time |
< 5μs |
| Short-delay Short-circuit Protection |
110% Rated Current (110% - 230% Adjustable) |
| Short-delay Protection Time |
< 50μs |
| Long-delay Overload Protection |
110% Rated Current (105% - 120% Adjustable) |
| Long-delay Protection Time |
10s (1 - 60s Adjustable) |
| Under-voltage Protection |
280VDC |
| Over-voltage Protection |
900VDC ± 5% |
| Over-temperature Protection |
85°C Alarm / 90°C Trip |
| Fault Record |
32 Groups |
| Control & Connectivity |
Digital Inputs (DI) |
5* Programmable DI, PNP (For 70A/100A: 3* Programmable DI, PNP) |
| Relay Outputs |
3* Programmable (For 70A/100A: 2* Programmable) |
| Communication |
Built-in RS485, Modbus RTU |
| Control Mode |
Communication, I/O Terminal, Local Panel |
| Environmental Conditions |
IP Rating |
IP20 |
| Humidity |
5% - 95%, Non-condensing |
| Altitude |
< 1000m: No derating; > 1000m: Derating required (1.5% per 100m) |
| Operating Temperature |
-20°C to 40°C: No derating |