Geographic environment: The project is located in a typical industrial mining environment in South Africa. The local grid infrastructure is relatively aged, and the site is characterized by heavy dust and large diurnal temperature variations, placing stringent demands on the ingress protection and insulation performance of electrical equipment.
Application conditions and load characteristics: As the core power center of the site, this facility carries impact loads from large crushing equipment, conveyor belts, and mine winders. Such loads draw high starting currents and generate significant harmonic content, and the production process is highly continuous — unplanned outages are absolutely not permitted.
Legacy pain points: The existing distribution system was outdated, with low enclosure ingress protection that could not cope with the site's dusty environment. The old switchgear also lacked comprehensive five-prevention interlocking (preventing breaker misoperation, isolator operation under load, earthing switch closure on a live circuit, breaker closure with the earthing switch closed, and entry into an energized compartment), resulting in low operational safety. With capacity expansion underway, a medium-voltage distribution solution with high short-circuit withstand capability, safe and flexible operation, and a high degree of intelligence was urgently required.

Figure 1: Project team with panoramic view of the distribution room
Based on South African grid standards (complying with IEC or SANS standards), high reliability requirements, and ease of maintenance, the project conducted a systematic comparison between fixed-type switchgear and KYN28 withdrawable switchgear:
| Comparison Dimension | Conventional Fixed-Type / Ring Main Unit | KYN28 Metal-Clad Withdrawable Switchgear (adopted) | Technical Note |
|---|---|---|---|
| Maintenance flexibility | Breakers are fixed-mounted; maintenance requires long outages and spare parts replacement is complex | Truck-type design; core modules can be fully withdrawn for rapid replacement using a spare truck, greatly shortening outage time | Suited to continuous-process industrial and mining enterprises |
| Safety protection | Relatively simple compartment separation with higher arc fault risk | Rigorous metal-clad compartmentalization (busbar, breaker, cable, and instrument compartments independent) with comprehensive mechanical and electrical five-prevention interlocking | Protects the personal safety of O&M personnel |
| Intelligent expansion | Limited instrument compartment space, unable to accommodate large integrated protection relays | Ample instrument compartment space, readily accommodating advanced feeder protection relays with event recording and communications | Meets digital O&M requirements |
| Insulation performance | Air insulation distances constrained by enclosure dimensions | High-grade SMC insulation components and composite insulation technology with large specific creepage distance, suited to dusty and humid environments | Improves operational stability |
| Compatibility | Compatible only with specific legacy breaker models | High compatibility; successfully adapted to mainstream vacuum breaker trucks and load-break switch trucks | Reduces full-lifecycle spare parts cost |
Selection conclusion: Given the rigorous requirements for supply reliability and maintenance efficiency in South African industrial projects, the KYN28 metal-clad withdrawable switchgear — with its flexible interchangeability, exceptionally high safety, and powerful intelligent interfaces — proved the optimal solution for this project.

Figure 2: Panoramic internal view of the switchgear in the distribution room

Figure 3: KYN28 switchgear view

Figure 4: Close-up of the protection device screen

Figure 5: Internal connections in the cable compartment

Figure 6: Side view of the distribution room
Compared with conventional fixed cubicles or low-end ring main units, the high-specification KYN28 solution adopted in this project offers advantages in the following respects:
| Cost Dimension | Advantage of the High-Specification KYN28 Solution |
|---|---|
| Outage loss cost | Truck interchangeability shortens fault recovery from hours to minutes. For mining and industrial production, the reduction in lost output is substantial. |
| O&M efficiency cost | Intelligent relays reduce manual inspection and troubleshooting time; maintenance-free breakers reduce overhaul frequency. |
| Asset life cost | The metal-clad structure and high-quality materials (aluminum-zinc coated steel sheet, SMC insulation components) give the equipment a service life of over 30 years with high residual value. |
| Safety risk cost | Comprehensive five-prevention and arc flash protection design minimizes the risk of personal injury and equipment explosion, avoiding potentially enormous liability exposure. |
Technical level: This project successfully validated the performance of the "KYN28 cubicle + high-performance vacuum breaker + intelligent protection" combination in a South African heavy-industry environment. It not only resolved supply reliability issues but also improved O&M transparency through digital means.
Economic level: Although the initial equipment investment is somewhat higher than for ordinary switchgear, its extremely low failure rate, very short repair time, and long service life make its Total Cost of Ownership (TCO) highly competitive.
Replication value: This case sets a benchmark for medium-voltage distribution upgrades in mines, cement plants, and chemical plants across South Africa and the wider Southern African region. Particularly in aging grid upgrade projects, this highly compatible and highly safe withdrawable switchgear solution merits broad adoption. When replicating this solution, it is recommended to focus on the local altitude correction factor and industry-specific explosion-proof requirements.

[Practical Summary] Faced with the demanding operating conditions of high dust and heavy impact loads at a South African mining site, "the high ingress protection of the KYN28 cubicle + the rapid fault-recovery capability of truck-type design + the precise traceability of intelligent relay protection" are the three critical elements for safeguarding continuous production. This case demonstrates that in harsh industrial environments, appropriately raising the initial equipment specification level can significantly reduce full-lifecycle O&M risk and cost.
For high-dust mining environments, we provide dedicated maintenance standards: full cabinet dust cleaning every 4 months to prevent creepage and flashover; annual inspection of heaters, controllers, secondary circuits and mechanical interlocks; comprehensive withstand voltage test, loop resistance test and mechanical characteristic test every 2 years to ensure long-term operational stability.
Old-style integrated cabinets have no independent compartment separation and reliable interlocks. Arc faults easily spread across the entire cabinet, causing explosion and electric shock hazards.
KYN28 features fully separated metal compartments with independent pressure relief channels, confining arc faults locally. Dual mechanical and electrical five-prevention interlocks completely eliminate dangerous mal-operations, achieving comprehensive safety upgrades.
Altitude insulation correction is mandatory for altitudes above 1000m in accordance with IEC 62271. Air insulation strength decreases with altitude.
The standard correction rule is a 1% increase in external insulation withstand voltage for every 100m elevation rise. We will recalculate creepage distance, insulation specifications and air clearance according to actual site altitude to prevent flashover and insulation breakdown in high-altitude mining environments.
The standard IP4X cabinet only meets basic indoor dustproof requirements and cannot withstand heavy floating dust and extreme day-night temperature differences in South African mining areas.
For harsh mining conditions, targeted upgrades are mandatory: intelligent temperature and humidity heaters eliminate internal condensation; high-density sealing strips and cable inlet sealing block fine dust ingress; reinforced dust-proof treatment is applied to the secondary terminal compartment.
These customized modifications effectively prevent insulation degradation, flashover discharge and malfunctions caused by dust and moisture, ensuring long-term stable operation all year round.