40.5 to 800kV Grounding Switch
JW5/JW8/JW10 (TV70) earthing switch: 40.5-800kV, 630-4000A, lightning impulse 200-2100kV, 3s short-time 20-63kA, making peak 50-165kA. For HV substation earthing protection.
JW5/JW8/JW10 (TV70) earthing switch: 40.5-800kV, 630-4000A, lightning impulse 200-2100kV, 3s short-time 20-63kA, making peak 50-165kA. For HV substation earthing protection.
TV70 earthing switch supports single‑pole / three‑group operation with manual crank, swing‑handle or motor drive. Blade moves parallel or perpendicular to base; mechanical & electrical interlock with disconnector is available. It refers to ANSI C37.30.1 Annex D, aligned with relevant IEC earthing‑switch standards for various site‑installation conditions.
Tek kutuplu bağımsız çalışmayı veya üç kutuplu grup işletim modunu destekler; tahrik seçenekleri manuel krank, salınım kolu ve motorlu tahrik ünitesini içerir. Bıçak tabana paralel veya dik olarak hareket edebilir.
Hat ayırıcı ve topraklama ayırıcısının aynı anda kapatılmasını önlemek amacıyla mekanik ve elektriksel kilitler takılabilir. Kilit aksesuarları, doğru montaj sırası izlenerek dikey kumanda borusuna monte edilmelidir.
Kurulum, ayar ve bakım, yüksek gerilim iletim ve dağıtım ekipmanları konusunda kapsamlı eğitim almış ve ilgili güvenlik prosedürlerine aşina nitelikli personel tarafından yapılmalıdır.