1. Solution Overview
2. Core Technical Specifications
Parameter |
Value |
Rated Voltage (kV) |
3.6 / 7.2 / 12 / 24 |
Rated Frequency (Hz) |
50 / 60 |
Rated Current (A) |
630 / 1250 / 1600 / 2000 / 2500 / 3150 / 4000 |
Rated Short-Circuit Breaking Current (kA) |
20 / 25 / 31.5 / 40 |
Rated Short-Time Withstand Current (4s) (kA) |
20 / 25 / 31.5 / 40 |
Power Frequency Withstand (1 min) |
Dry: 34-65kV (varies by voltage) |
Lightning Impulse Withstand (kV) |
75-125kV (varies by voltage) |
Protection Class (Housing) |
IP4X |
Ambient Temperature |
-15°C to +40°C |
Max. Installation Altitude |
1000m |
Mechanical Life (Circuit Breaker) |
VS1/VD4: 10,000 ops |
3. Key Design Features
4. Physical Layout & Dimensions
(Select based on Rated Current & Configuration)
Cabinet Width (A) |
Depth (B) (mm) |
Height (mm) |
Typical Weight (kg) |
Recommended Use Case |
650 mm |
1400 mm |
2200 mm |
700 |
<1250A, Compound Insulation, Front Cable Access |
800 mm |
1500 mm |
2200 mm |
800 |
<1250A, Air Insulation, Front Cable Access |
800 mm |
1600 mm |
2200 mm |
900 |
<1250A, Rear Overhead Line |
1000 mm |
1500 mm |
2200 mm |
1100 |
**>1250A, Front Cable Access** |
1000 mm |
1600 mm |
2200 mm |
1200 |
**>1250A, Rear Overhead Line** |
900 mm |
1700 mm |
2200 mm |
1000 |
Specific config (e.g., with Siemens 3AH5) |
Note: Height may reduce to 1660mm for 1000mm wide cabinets with rear overhead lines >1600A.
5. Component Selection
6. Implementation & Service
7. Why Choose This Solution?