RHD-145 SF6 Gas Dead tank Circuit Breaker
чертежи · ROCKWILL

RHD-145 SF6 Gas Dead tank Circuit Breaker

RHD-145 dead-tank SF6 circuit breaker: 145kV, 2500-4000A, lightning impulse 650/750kV, short-time 31.5-50kA, making peak 100-125kA. For HV grid switching and short-circuit faults.

Последнее обновление2026.09
ЯзыкEnglish
ФайлPDF · 428.9 KB
Dead tank Circuit BreakerSF6 Gas Circuit Breaker
Загрузить

Описание документа

This circuit breaker adopts self‑blast arc‑extinction technology and three‑phase post‑type porcelain insulator design, equipped with pointer density relays, with mechanical life up to 10 000 times and customized manufacturing available. It complies with IEC 62271‑100 and GB/T 1984 standards, featuring high safety, reliability and easy installation, and provides complete solutions for design, assembly and test.

Связанные продукты

Часто задаваемые вопросы

Номинальное давление газа SF₆ 0,5–0,6 МПа, годовой уровень утечки газа ≤0,5%; механический ресурс достигает 10 000 циклов срабатывания, номинальная длительность короткого замыкания составляет 3 с.

Соответствует стандартам IEC 62271‑100 и GB/T 1984. Доступны индивидуальное производство и комплексные решения, включая проектирование, сборку и испытания.

Электродвигатель привода взвода и цепь управления питаются от сети постоянного тока 110 В / 220 В; питание нагревателя осуществляется от сети переменного тока 220 В.