• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Three-Phase Pole Mounted SF6 Electronic Sectionalizer-40.5kV

  • Three-Phase Pole Mounted SF6 Electronic Sectionalizer-40.5kV

Key attributes

Brand ROCKWILL
Series RDK
Rated voltage 40.5 kV
Rated normal current 200 A
Rated frequency 50/60Hz
Description
The Rockwill RDK Series is a 40.5kV-class, air-insulated, pole-mounted electronic sectionalizer designed for automated fault isolation in overhead distribution networks. Coordinating with upstream reclosers or circuit breakers, the RDK automatically isolates permanent faults on branch lines while allowing the main feeder and healthy sections to remain in service — reducing outage scope and improving system reliability.

The RDK is entirely self-powered and maintenance-free. An integral current transformer detects main circuit current and feeds the signal to an electronic controller for digital processing. When a fault occurs, the upstream recloser opens and the RDK counts each loss-of-voltage event. Once the preset count (1 to 4) is reached, the sectionalizer trips within 180 ms, isolating the faulty section. The recloser then re-energises the healthy portion of the network. For temporary faults cleared before the count is reached, the RDK resets automatically to its original state.

Models Schematic Diagram

Models Schematic Diagram

Technical Specifications

Rated voltage (Ur) kV 40.5
Rated normal current (Ir) A 200
Rated frequency Hz 50/60
Overcurrent pick-up current range A 8 ... 400
Rated short-time withstand current (r.m.s.) kA 10
Rated short-circuit withstand duration (tk) s 1
Rated peak withstand current kA 20
Configurable fault counting sequence — 1, 2, 3, 4
Maximum fault memory hold time s 20
Maximum automatic reset delay time s 20
Permissible deviation of pick-up current for memory reset time % ± 10
Rated opening time ms ≤ 200
Main circuit resistance μΩ ≤ 400
Mechanical operating life Operations 500
Terminal horizontal pull-out force N 250
Manual opening torque N·m —
Manual opening force N ≤ 120
Rated lightning impulse withstand voltage (phase-to-earth) kV 185
Rated lightning impulse withstand voltage (isolating gap) kV 220
Rated power-frequency withstand voltage (phase-to-earth) — Dry test kV 95
Rated power-frequency withstand voltage (phase-to-earth) — Wet test kV 80
Rated power-frequency withstand voltage (isolating gap) — Dry test kV 110
Rated power-frequency withstand voltage (isolating gap) — Wet test kV 95
Rated power-frequency withstand voltage (auxiliary & control circuit) kV 2
Pollution class Class III
Maximum ice coating thickness mm ≤ 1
4-stage adjustable pick-up current & configurable fault counting sequence — Yes

Selection list

Please inform the order before ordering. For example:

Pick up current (A) Count/counts
I1 I2 I3 I4 I5 1.2.3.4

Note: Please view the label to know the section current(I1, I2, I3, I4, I5) .

Sectionalizer setting guide

1.Current setting
The sectionalizer current setting must be selected at 20% below the minimum associated recloser or circuit breaker trip current.
2.Number of count setting
Generally the number of count settings should be 'one' less than the number of trips to lockout of the recloser or circuit breaker.

Sectionalizer Setting Operation

Application

Normally, the sectionalizer is applied in conjunction with an upstream recloser or circuit breaker.For Example:
The recloser applied in the substation is set (1 fast and 3 slow) 4 shots to lockout and 6 units cutout sectionalizers (F1, F2, F3, F4, F5, F6) are applied in the four branch line to separate 7 section ( L1, L2, L3, L4, L5, L6, L7). The counts of F1 is set to 3 time, F2, F3, F5 are set to 2 times and F4, F6 are set to 1 time. As shown in the following figure:

Schematic Diagram

If there is a fault E1 in section L5, a fault current flow the recloser and sectionalizer F1, F3, F4, The recloser trip and all the line lost voltage, The sectionalizer F4 trip after it reach to the presetting "count" number 1 and isolate the fault section L5, the rescloser reclose and restore the healthy section L1, L2, L3, L4, L6, L7 to service.

sectionalizer

If a fault E2 in section L6, a fault current flow the recloser and sectionalizer F1, F5, the recloser trip, if the fault is temporary, the recloser reclose to restore the line in service, then the sectionalizer F1, F5 remains closed and resets to its original state after a presetting time since it does not reach the presetting count number,. if the fault is permanent, the recloser fail to reclose successfully and trip again, all the line lost voltage and the sectionalizer F5 trip to isolate fault section L6 after it reaches the presetting count number 2, the sectionalizer F1 remain closes state since it does not reach the presetting count number. The recloser reclose again and restore the healthy section L1, L2, L3, L4, L5 to service.

sectionalizer

If a fault E3 in section L2, a fault current flow the recloser and sectionalizer F1, the recloser trip. If the fault is temporary the recloser reclose to restore the line in service, then the sectionalizer F1 remains closed and resets to its orginal state after a presetting time since it does not reach the presetting count number. If the fault is permanent , the recloser fail to reclose successfully and trip again all the line lost voltage and the sectionalizer F1 trip to isolate fault section L2 after it reach the presetting count number 3, The recloser reclose again and restore the healthy section L1 to service.

sectionalizer

The count number of sectionalizer is set 1 time normally as it applied in the end of substation because almost fault occurring at the end of substation is permanent and is set 2 or 3 times applied on the overhead line because almost fault applied on the overhead line is temporary.
In this co-ordination, the sectionalizer can easily and optimized co-ordinate.

Documentation Resource Library Automatic Sectionalizer

Public.
Rockwill Electric Group Profile Rockwill Electric Group Profile
Brochure
English
Restricted
RDK Series Autolink Electronic Sectionaliser RDK Series Autolink Electronic Sectionaliser
Catalogue
English
PDF
Restricted
RDK Three-Phase Electronic Auto Sectionalizer RDK Three-Phase Electronic Auto Sectionalizer
Catalogue
English
PDF

Frequently asked questions

No external auxiliary power source is required. It takes energy from built‑in current‑transformer, completes fault‑current detection and counting logic by internal micro‑controller.

After permanent‑fault removal, operators can manually close it by insulated operating rod. No spare‑parts replacement is required. It will auto‑reset if fault is temporary without reaching count threshold.

Three conditions must be met simultaneously: fault current exceeds pickup setting; preset counting‑times (1‑4 times) are reached; line loses voltage and residual current below 300 mA.

Know your supplier

Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m² Total staff: 700+ Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: Medium and High Voltage Switchgear/Power and Distribution Transformers/Instrument Transformers and Sensors/Lightning Protection and Electrical Insulation/Substations and E-Houses/Electrical Panel and Controlgear
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Login
or continue with
New here?
Register