• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Low-loss Oil-immersed Power distribution transformer 6kV 7.2kV 12kV

  • Low-loss Oil-immersed Power distribution transformer 6kV 7.2kV 12kV

Key attributes

Brand Vziman
Model NO. Low-loss Oil-immersed Power distribution transformer 6kV 7.2kV 12kV
Rated voltage 12kV
Rated frequency 50/60Hz
Rated capacity 1250kVA
Series S22
Description
This Oil-immersed Power distribution transformer, with its core advantages of energy efficiency, environmental friendliness, and safety and reliability, has become an ideal Power distribution transformer for factory production, rural power supply, and urban power transmission and distribution network scenarios. It is also a trusted choice for users in the field of power supporting facilities.
To create this high-performance Oil-immersed Power distribution transformer, our company deeply integrates two key directions: new material R&D and new process application. At the same time, we combine independent innovation technology with the introduction of advanced industry technologies, and have carried out multiple rounds of optimization and innovative design for the Power distribution transformer’s core structure and coil layout. Ultimately,
we not only achieved a significant reduction in no-load loss, effectively cutting long-term operational energy consumption costs, but also successfully controlled the equipment’s operating noise—making this Oil-immersed Power distribution transformer more suitable for various scenarios with environmental noise requirements. It is an independently developed Power distribution transformer that embodies technological upgrading and practical value.

Product Showcase Video

Core Advantages

  • Multi-Voltage Adaptability:This Oil-immersed Power distribution transformer covers 6kV, 7.2kV, and 12kV rated voltage levels, fitting diverse scenarios (urban grids, industrial parks, rural power networks) without additional voltage-matching equipment. It serves as a versatile Power distribution transformer for different power grid systems.
  • Ultra-Low Energy Loss:The Oil-immersed Power distribution transformer adopts optimized core & coil design, achieving 30%-40% lower no-load/load loss than standard Power distribution transformer models, slashing long-term operational electricity costs for users.
  • Reliable Oil-Immersed Structure:The sealed oil insulation of this Oil-immersed Power distribution transformer ensures excellent heat dissipation and insulation performance, withstanding harsh environments (high temperature/humidity) and boasting a 20+ year service life—far exceeding the durability of many conventional Power distribution transformer variants.
  • Low Noise Operation:Precision winding and structural optimization control the noise of the Oil-immersed Power distribution transformer below 50dB(A), making it suitable for noise-sensitive areas (residential zones, urban built-up districts) where standard Power distribution transformer may fail to meet noise requirements.
  • Strong Short-Circuit Resistance:Equipped with high-quality copper coils and reinforced body structure, the Oil-immersed Power distribution transformer resists short-circuit impacts, maintaining stable operation even under grid fluctuations—a critical safety advantage for any Power distribution transformer in complex grid environments.
  • Easy Installation & Maintenance:This Oil-immersed Power distribution transformer features compact size, lightweight design, and complete accessories (oil level gauge, temperature controller) for quick on-site installation; its sealed structure reduces daily maintenance workload, making it a user-friendly Power distribution transformer for on-site teams.

Technical Specifications

Model and Its Meaning

S
22
-M
-□
/□
NX2
Three-phase
Performance level code
Fully sealed
Rated capacity kVA
Voltage class kV
Energy efficiency level

Performance Parameters

Rated Capacity (kVA)
 
Connection Group Symbol
 
Voltage Combination (kV)
 
 
No - load Loss (W)
 
Dyn11/Yzn11 Load Loss (W)
 
Yyn0 Load Loss (W)
 
Short - circuit Impedance (%)
 
 High Voltage
Tap Range
Low Voltage
30
Yyno or Dyn11
10kV
6.3kV
6kV
±5%/±2×2.5%
0.4
65
455
430
4.0
50
80
655
625
4.0
63
90
785
745
4.0
80
105
945
900
4.0
100
120
1140
1080
4.0
125
135
1360
1295
4.0
160
160
1665
1585
4.0
200
190
1970
1870
4.0
250
230
2300
2195
4.0
315
270
2760
2630
4.0
400
330
3250
3095
4.0
500
385
3900
3710
4.0
630
460
4460
-
4.5
800
560
5400
-
4.5
1000
665
7415
-
4.5
1250
780
8640
-
4.5
1600
940
10440
-
4.5
2000
1085
13180
-
4.5
2500
1280
13360
-
4.5

 Operating Conditions 

This Oil-immersed Power distribution transformer is designed to operate under the following conditions, ensuring stable performance as a professional Power distribution transformer:

Ambient Temperature

  • Maximum ambient temperature: ≤40°C (daily average ≤30°C)
  • Minimum ambient temperature: ≥-25°C (for cold regions, customizable to -40°C)
  • Maximum daily temperature variation: ≤25°C

Altitude

  • Applicable to areas with altitude ≤1000m; for areas above 1000m, derating operation or customized insulation design is required (to adapt to low air pressure) to ensure the Oil-immersed Power distribution transformer functions normally.

Environmental Humidity

  • Monthly average relative humidity: ≤90% (at 25°C)
  • Daily average relative humidity: ≤95% (no condensation on Power distribution transformer surface)

Applications

  • Urban Distribution: Residential, commercial, high-rise buildings; low-noise design.
  • Rural Power: Rural stations, irrigation, township supply; multi-voltage adaptability.
  • Industrial Parks: Factory production, workshop distribution; strong short-circuit resistance.
  • Power Facilities: Box substations, switching stations, distribution rooms; easy installation.
  • Renewable Energy: Solar, wind, railway, airport, mining infrastructure.
  • Noise-Sensitive Areas: Residential, hospitals, schools; noise below 50dB(A).

Solutions - Power distribution transformer

  • Choosing Vizman Distribution Transformers: Innovative Customization to Meet Diverse Power Needs
    Distribution transformers are the heart of local electricity distribution systems. They step down voltage, enabling safe and efficient power supply to homes and businesses.At Vizman Electric Power Technology Co., Ltd., we understand the critical role of distribution transformers in the energy ecosystem. That's why we specialize in manufacturing high-quality distribution transformers, providing tailored solutions to meet diverse energy needs.1.Solutions Offered by Vizman Electric Power Technology
  • Intelligent Drive: The Efficient Transformation Path for Distribution Transformers above 10kV
    1.Introduction1.1 Urgent Need for Upgrading Distribution Transformers Rising Load DensityDuring peak hours, transformers often operate overloaded, raising temperatures (by 15–25°C in extreme cases). Prolonged heat speeds up insulation degradation (like in paper-oil systems), boosting failure risks—overloaded units have up to 40% higher failure rates. Power Quality DisturbancesVoltage fluctuations > ±10% of nominal values disrupt sensitive gear (medical devices, data centers).Harmonic pollutio
  • 10 kV Distribution Transformer and Microgrid Collaborative Operation Product Solution
    1. Challenges1.1 Insufficient Adaptability to Bidirectional Power Flow Voltage Fluctuation & Overload RisksBidirectional power flow exacerbates voltage instability and equipment overload, endangering transformers and grid integrity. Enhanced adaptive design is imperative. Unidirectional Design LimitationsConventional 10 kV distribution transformers, designed for unidirectional power flow, struggle to accommodate distributed generation integration in microgrids. Power Quality & Equipment

Documentation Resource Library Power distribution transformer

Restricted
Dimension and installation for S11-XXXX/10.5 Oil-immersed distribution transformers Dimension and installation for S11-XXXX/10.5 Oil-immersed distribution transformers
Drawings
English
DWG
Restricted
H61 HV/LV distribution transformer H61 HV/LV distribution transformer
Catalogue
English
PDF
Restricted
H59 HV/LV distribution transformer H59 HV/LV distribution transformer
Catalogue
English
PDF

Frequently asked questions

The Oil-immersed Power distribution transformer stands out as a high-performance option compared to ordinary Power distribution Transformer, especially for  grids. Its low-loss design cuts 30%-40% of no-load/load loss, reducing long-term operational costs—an advantage ordinary Power distribution Transformer rarely match. As an Oil-immersed Power distribution transformer, it uses sealed oil insulation for superior heat dissipation and harsh environment resistance, ensuring stable operation in urban and rural scenarios. Unlike dry-type Power distribution Transformer, this Oil-immersed Power distribution transformer also features low noise (≤50dB(A)) and strong short-circuit resistance, making it adaptable to noise-sensitive and complex grid environments, thus becoming a reliable Power distribution Transformer for diverse power supply needs.

Standard design is suitable for altitude ≤1000m and ambient temperature ≥-25°C. For altitudes above 1000m, derating or customized insulation design is required. For cold regions, customization down to -40°C is available.

Yes. We can dispatch experienced engineers for on-site installation guidance, commissioning, and operator training. Remote technical support is also available 24/7.

Yyn0 is suitable for distribution scenarios with basically balanced three-phase loads. Dyn11 is suitable for scenarios with more single-phase loads and higher harmonic content, with stronger resistance to unbalanced loads. Please select based on actual load characteristics.

Know your supplier

Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 10000m² Total staff: 300 Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: Medium and High Voltage Switchgear/Lighting and Monitoring Equipment/Power and Distribution Transformers/IT and AI Support Equipment/Lightning Protection and Electrical Insulation/Substations and E-Houses/Power Electronic Equipment/Electrical Panel and Controlgear
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Login