| Brand | ROCKWILL |
| Model NO. | Customizable SF6 Ring Main Unit for ring main power supply-12kV |
| Rated voltage | 12kV |
| Rated frequency | 50/60Hz |
| Series | XGN |
The XGN15-12 is a 12kV-class SF₆-insulated ring main unit (RMU) designed for secondary distribution networks. Sealed stainless steel enclosure with SF₆ gas insulation protects against moisture, pollution, corrosive atmospheres, and dust. Rated at 630A with a short-circuit making capacity of 50kA, it supports ring main and radial configurations for industrial, commercial, and residential applications.
The unit is equipped with SF₆ switch-disconnectors or switch-fuse combinations, capable of making and breaking rated load current, making rated short-circuit current, and interrupting transformer no-load current. When combined with a fuse, the unit can interrupt 31.5kA short-circuit current, providing full system control and protection.
Sealed tank construction: All live parts enclosed in SF₆ gas-no exposure to moisture, dust, or corrosive gases
Plug-in solid busbars: Between-unit connections via insulated plug-in busbars, eliminating exposed conductors
External resin-cast fuses: Single-phase fuses mounted outside the enclosure, preventing phase-to-phase faults
Modular design: Single-cabinet fully-enclosed construction, factory or site configurable
Compact footprint: 375mm (W) ×1400mm (H)×980mm (D)
CNC-fabricated cabinet: Aluminum-zinc coated steel plates, riveted construction for airtightness
Maintenance-free design: No on-site SF₆ filling required during service life
| Parameter | Unit | Value |
|---|---|---|
| Rated Voltage (Ur) | kV | 12 |
| Rated Frequency | Hz | 50/60 |
| Rated Current (busbar) | A | 630 |
| Rated Short-time Withstand Current (Ik) | kA/3s | 20 / 25 |
| Rated Peak Withstand Current (Ip) | kA | 50 / 63 |
| Rated Active Load Breaking Current | A | 630 |
| Rated Cable Charging Breaking Current | A | 10 |
| Rated Short-circuit Making Current | kA | 50 / 63 |
| 1min Power Frequency Withstand (phase-to-earth) | kV | 28 |
| 1min Power Frequency Withstand (across isolating distance) | kV | 32 |
| Lightning Impulse Withstand (phase-to-earth) | kV peak | 75 |
| Lightning Impulse Withstand (across isolating distance) | kV peak | 85 |
| SF₆ Gas Pressure (20°C, gauge) | MPa | 0.15 |
| Mechanical Endurance | operations | 2000 |
| Degree of Protection (enclosure) | IP | IP67 |
| Cabinet Dimensions (W×H×D) | mm | 375 ×1400 × 980 |
| Ambient Temperature | -25°C ~ +40°C |
| Humidity | ≤95% monthly average |
| Altitude | ≤1000m (higher options available) |
| Pollution Level | Class II (IEC 60815) |
Yes. With fuse combination, the unit can interrupt 31.5kA short-circuit current. External resin-cast fuses are mounted outside the enclosure to prevent phase-to-phase faults.
Yes. No on-site SF₆ gas filling required. Fully sealed structure encloses all live parts in SF₆ gas, requiring no routine maintenance.
Insulated plug-in busbar connectors — no exposed conductors, ensuring convenient and safe installation.