| Brand | ROCKWILL |
| Numero ng Modelo | 66kV Tatlong Phase na Oil-Immersed Earthing Transformer |
| Nararating na Voltase | 66kV |
| bilang ng phase | Three-phase |
| Serye | JDS |
Product Overview
Ang Rockwill ay nagbibigay ng maasahan at mataas na pagganap na mga earthing transformers na idinisenyo para sa 66kV power systems. Ang aming mga oil-immersed transformers ay ininyong gawin upang magbigay ng matatag na neutral grounding solutions habang sinisigurado ang operational safety at system protection. Ginawa ito ayon sa mga international standards kasama ang IEC at GB, ang mga transformers na ito ay sumasaklaw ng premium materials at mahigpit na quality control sa buong proseso ng produksyon.
Pangunahing Impormasyon

Pangunahing Katangian
Voltage Class: 66kV system voltage (200 BIL)
Capacity Range: Standard units mula 100kVA hanggang 10,000kVA
Winding Configuration: Optimized zigzag (ZNyn) disenyo
Cooling System: ONAN/OFAF cooling options
Insulation: Mineral oil o synthetic ester fluid
Construction:
Corrugated tank o radiator cooling
Hermetically sealed o conservator tank options
CRGO silicon steel core
Copper/aluminum windings
Teknikal na mga Pabor
Enhanced Safety: Built-in Buchholz relay at pressure relief device
Low Impedance: Zero-sequence impedance <15Ω para sa epektibong fault current management
Durability: Corrosion-resistant paint system para sa outdoor installations
Efficiency: Reduced no-load losses through optimized core design
Flexibility: Off-circuit tap changer (±5% in 2.5% steps)
Typical Applications
Utility Networks:
Neutral grounding para sa 66kV transmission systems
Arc suppression coil connections
Resistance grounding systems
Industrial Plants:
Petrochemical facilities
Mining operations
Steel manufacturing plants
Renewable Energy:
Wind farm collector stations
Solar PV substations
Hydroelectric plants
Performance Specifications
Temperature Range: -30°C hanggang +40°C ambient
Humidity: ≤95% monthly average
Altitude: Up to 2000m ASL
Sound Level: ≤75dB at 1m
Efficiency: ≥99.2% at full load
Testing Protocol
All units undergo comprehensive testing including:
Zero sequence impedance measurement
Induced overvoltage test (260Hz)
Lightning impulse test (350kV)
Temperature rise test (65K max.)
Oil dielectric strength test (≥50kV)
Service Conditions
Suitable for indoor/outdoor installation
Wind resistant up to 35m/s
Non-explosive environments
Seismic capability: 0.3g horizontal acceleration