| Marca | ROCKWILL |
| Numerus Modeli | 12kV 24kV 36kV Purus aeris/Nitrogeni Insulatus Ring Main Unit (RMU) Certans Stabilitatem Electricitatis |
| Votum nominatum | 36kV |
| currus electricus nominatus | 630A |
| Frequenta nominata | 50/60Hz |
| Series | REC |
Descripio:
ROCKWILL® magnam pondus adhibet qualitati producti et technologiae manufacturae, singulosque gradus productionis producti cum exactitudine et diligentia tractat. Solum gas insulans ad comparationem completa caloris sicci aeris, nitrogenii, carbonis dioxidici, et puri aeris utitur. Purus aer compositus cum contentu humiditatis extrema minimo et puritate maxima pro electo gas insulante substituto SF6. Nucleus unitatis commutatoriae producti novam processum fundendi vacui camarae extinguendi arcus in moli molliter castigata adhibet, coniunctus cum interruptore triplici positione curate designato, structura tota simplex et compacta; Cista gasea perfecte clausa SF6 purum aerem substituit, cum designamento distributionis electrici campi valde ad vantage, et emissio partialis totius cistae infra 5pC est; Testum resistendi salinis nubibus mechanismo operativo processu superficiei alligatae zinco excedit 168 horas, et longissima vita utilitatis potest ad 30000 vice attingere.
Praestantia:
Ring main unit insulatus puro aere/nitrogenio
Gas amicum ambienti
Emissiones carbonis nullae, residua nulla
Productio intensiva et diligens, quaerens qualitatem finiorem
Conformitas standardibus IEC/ANSI
Fabricatio customizata praebita
Solutiones integrales pro designo, assemblagio, test...
Solutio responsabilis pro securitate et fide
Latus ambitus offert, negotium facile et installatio commoda
Parametri principales technici (tria phasa):
12kV
N |
Item |
Unit |
Data |
1 |
Rated maximum voltage |
kV |
12 |
2 |
Rated maximum current |
A |
630/1250 |
3 |
Rated frequency |
Hz |
50/60 |
4 |
Method of Arc Suppressing |
Vacuum |
|
5 |
Method of Insulation |
Pure air/Nitrogen |
|
6 |
Rated short circuit breaking current |
kA |
20/25 |
7 |
Rated peak value withstand current |
kA |
50/63 |
8 |
Rated 1min power frequency withstand voltage |
kV |
42 |
9 |
Rated lightning impulse voltage |
kV |
75 |
10 |
Operation sequence |
/ |
C-0.3-CO-180-CO |
12 |
Resistance loop |
µΩ |
≤140 |
13 |
Rated gas pressure (20℃ gauge) |
Mpa |
0.02 |
14 |
Minimum operating gas pressure |
Mpa |
0 |
15 |
Mechanical life - Circuit breaker |
N |
10000 |
Mechanical life - Load break switch |
N |
3000/6000 |
|
Mechanical life - Disconnector |
N |
3000/6000 |
|
Mechanical life - Earthing switch |
N |
3000/6000 |
|
16 |
Protection grade - Gas tank |
IP67 |
|
Protection grade - Shell |
IP4X |
||
17 |
Rated annual air leakage rate |
% |
0.01 |
XXIVkV
N |
Item |
Unit |
Data |
1 |
Rated maximum voltage |
kV |
24 |
2 |
Rated maximum current |
A |
630/1250 |
3 |
Rated frequency |
Hz |
50/60 |
4 |
Method of Arc Suppressing |
Vacuum |
|
5 |
Method of Insulation |
Pure air/Nitrogen |
|
6 |
Rated short circuit breaking current |
kA |
20/25 |
7 |
Rated peak value withstand current |
kA |
50/63 |
8 |
Rated 1min power frequency withstand voltage |
kV |
50 |
9 |
Rated lightning impulse voltage |
kV |
125 |
10 |
Operation sequence |
/ |
C-0.3-CO-180-CO |
12 |
Resistance loop |
µΩ |
≤150 |
13 |
Rated gas pressure (20℃ gauge) |
Mpa |
0.04 |
14 |
Minimum operating gas pressure |
Mpa |
0 |
15 |
Mechanical life - Circuit breaker |
N |
10000 |
Mechanical life - Load break switch |
N |
3000/6000 |
|
Mechanical life - Disconnector |
N |
3000/6000 |
|
Mechanical life - Earthing switch |
N |
3000/6000 |
|
16 |
Protection grade - Gas tank |
IP67 |
|
Protection grade - Shell |
IP4X |
||
17 |
Rated annual air leakage rate |
% |
0.01 |
XXXVIkV
N |
Item |
Unit |
Data |
1 |
Rated maximum voltage |
kV |
36 |
2 |
Rated maximum current |
A |
630/1250 |
3 |
Rated frequency |
Hz |
50/60 |
4 |
Method of Arc Suppressing |
Vacuum |
|
5 |
Method of Insulation |
Pure air/Nitrogen |
|
6 |
Rated short circuit breaking current |
kA |
20/25 |
7 |
Rated peak value withstand current |
kA |
50/63 |
8 |
Rated 1min power frequency withstand voltage |
kV |
70 |
9 |
Rated lightning impulse voltage |
kV |
170 |
10 |
Operation sequence |
/ |
C-0.3-CO-180-CO |
12 |
Resistance loop |
µΩ |
≤160 |
13 |
Rated gas pressure (20℃ gauge) |
Mpa |
0.04 |
14 |
Minimum operating gas pressure |
Mpa |
0 |
15 |
Mechanical life - Circuit breaker |
N |
10000 |
Mechanical life - Load break switch |
N |
3000/6000 |
|
Mechanical life - Disconnector |
N |
3000/6000 |
|
Mechanical life - Earthing switch |
N |
3000/6000 |
|
16 |
Protection grade - Gas tank |
IP67 |
|
Protection grade - Shell |
IP4X |
||
17 |
Rated annual air leakage rate |
% |
0.01 |
Typus compactus puri aeris/azoti insulatus unitatis anuli principalis

Typus |
Summa extensio unius panelis |
Latus extensio unius panelis |
Unius panelis magnitudo compacti moduli |
Circuit Breaker Panel |
390 * 850 * 1950 |
390 * 850 * 1950 |
390 * 850 * 1950 |
Load Break Switch Panel |
390 * 850 * 1950 |
390 * 850 * 1950 |
390 * 850 * 1950 |
PT Panel (with 3phase, 5 columns) |
600 * 850*1950 |
600 * 850 * 1950 |
600 * 850 * 1950 |
PT Panel (single phase) |
420 * 850 * 1950 |
420 * 850 * 2000 |
420 * 850 * 1600 |
Bus Riser |
375 * 850 * 1950 |
375 * 850 * 2000 |
375 * 850 * 1600 |
Metering panel |
750 * 850 * 1950 |
750 * 850 * 2000 |
750 * 850 * 1600 |