| Brand | ROCKWILL |
| Numero sa Modelo | 10kV (Pleksibl na Kombinasyon sa Mga Uri ng Gabinet) Normal na Presyon na Siguradong Air-Insulated Switchgear / Ring Main Unit |
| Naka nga boltahang rated | 12kV |
| Nasodnong peryedyo | 50/60Hz |
| Serye | XGN |
Ang 10kV (Flexible Combination of Multiple Cabinet Types) Normal Pressure Sealed Air-Insulated Switchgear / Ring Main Unit usa ka versatile medium-voltage power distribution system nga gihimo aron molambo sa diverse operational needs. Operasyon sa 10kV uban normal-pressure sealed structure, kini naggamit og air isip insulating medium (eliminating reliance on SF₆ gas) ug adunay modular cabinet designs nga mahimong flexibly combined. Kini nga switchgear nagsama sa power distribution, protection, ug control functions, makapadaghan kini sa mga scenario nga gibutangan og customized configurations— sama sa industrial zones, urban grids, commercial complexes, ug renewable energy facilities— diin ang adaptability sa varying load demands ug spatial constraints kay importante.
Name |
Unit |
Parameter Value |
|
Rated Voltage (Ur) |
kV |
12 |
|
Rated Frequency (fr) |
Hz |
50 |
|
Rated Current (Ir) |
A |
630 |
|
Short - time Power Frequency Withstand Voltage (Ud) |
Between Fractures |
kV |
48 |
Between Phases |
kV |
42 |
|
Phase to Ground |
kV |
42 |
|
Lightning Impulse Withstand Voltage (Up) |
Between Fractures |
kV |
95 |
Between Phases |
kV |
75 |
|
Phase to Ground |
kV |
75 |
|
Rated Short - time Withstand Current (Ik) |
kA |
20/25 |
|
Rated Short - circuit Duration (tk) |
s |
4 |
|
Rated Peak Withstand Current (Ip) |
kA |
50/63 |
|
Rated Short - circuit Breaking Current (Isc) |
kA |
20/25 |
|
Rated Short - circuit Making Current (Ima)
|
Vacuum Interrupter |
kA |
50/63 |
Earthing Switch |
|||
Auxiliary Circuit and Control Circuit |
Rated Voltage (Ua) DC/AC |
V |
≤400 |
Power Frequency Withstand Voltage (1min) |
V |
2000 |
|
Mechanical Life
|
Circuit Breaker |
Times |
10000 |
Disconnecting Switch |
Times |
3000 |
|
Earthing Switch |
Times |
3000 |
|
Electrical Life |
Circuit Breaker |
Class |
E2 |
Earthing Switch |
Class |
E2 |
|
Protection Grade of Cabinet Enclosure |
IP4X |
||
Protection Grade of Sealed Box |
IP65 |
||
Normal Service Conditions