Vacuum Circuit Breakers for Capacitor Bank Switching

Oliver Watts
Oliver Watts
Larangan: Inspection and testing
China

Reactive Power Compensation and Capacitor Switching in Power Systems

Reactive power compensation is an effective means to increase system operating voltage, reduce network losses, and improve system stability.

Conventional Loads in Power Systems (Impedance Types):

  • Resistance

  • Inductive reactance

  • Capacitive reactance

Inrush Current During Capacitor Energization

In power system operation, capacitors are switched in to improve power factor. At the moment of closing, a large inrush current is generated. This occurs because, during the first energization, the capacitor is uncharged, and the current flowing into it is limited only by the loop impedance. Since the circuit condition is close to a short circuit and the loop impedance is very small, a large transient inrush current flows into the capacitor. The peak inrush current occurs at the instant of closing.

If the capacitor is re-energized shortly after disconnection without sufficient discharge, the resulting inrush current can be up to twice that of the initial energization. This happens when the capacitor still holds residual charge, and re-closing occurs at the moment when the system voltage is equal in magnitude but opposite in polarity to the capacitor’s residual voltage, resulting in a large voltage difference and thus a high inrush current.

Key Issues in Capacitor Switching

  • Re-ignition

  • Re-strike

  • NSDD (Non-Sustained Destructive Discharge)

Re-ignition is permitted during capacitive current switching tests. Circuit breakers are classified into two categories based on their re-strike performance:

  • C1 Class: Verified by specific type tests (6.111.9.2), exhibiting low probability of re-strike during capacitive current switching.

  • C2 Class: Verified by specific type tests (6.111.9.1), exhibiting very low probability of re-strike, suitable for frequent and high-demand capacitor bank switching.

Improving Success Rate of Vacuum Circuit Breakers for Capacitor Switching

1. Enhance Dielectric Strength of Vacuum Interrupters

The vacuum interrupter is the heart of a vacuum circuit breaker and plays a critical role in successful capacitor switching. Manufacturers must optimize the design and materials to achieve:

  • Uniform electric field distribution

  • High resistance to welding

  • Lower current chopping level

Structural and material improvements are essential to ensure reliable interruption.

2. Control Vacuum Interrupter Manufacturing Process

  • Minimize and remove burrs during metal part machining; improve surface finish and cleanliness.

  • Perform ultrasonic cleaning of components before assembly to remove micro-particles.

  • Control humidity and airborne particles in the assembly room.

  • Reduce storage time of contact components and assemble promptly to minimize oxidation and contamination.

VCB..jpg

3. Improve Circuit Breaker Design and Assembly Quality

Ensure mechanical characteristics are within optimal ranges:

  • Conducting rod alignment and vertical installation to avoid stress.

  • Proper operating mechanism output energy.

  • Closing and opening speeds within acceptable limits.

  • Minimize closing bounce and opening rebound.

  • Strict control of component quality and assembly precision.

4. No-Load Operation and Conditioning (Burn-in)

After assembly, perform 300 no-load operations to stabilize mechanical characteristics. Conduct voltage and high-current conditioning on the complete switch to eliminate microscopic protrusions and reduce re-ignition rate during capacitor switching.

Parallel capacitor conditioning can rapidly enhance the dielectric strength of the product.

5. Optimize Opening Speed

After interruption, the contact gap of a vacuum circuit breaker must withstand twice the system voltage (2×Um) for up to 13 ms. The contacts must reach a safe open distance within this time. Therefore, the opening speed must be sufficient — especially for 40.5 kV circuit breakers.

6. Conditioning (Aging) of Vacuum Interrupters

  • Low-effect methods: High-voltage/low-current, low-voltage/high-current, or impulse voltage conditioning have limited effect in reducing re-ignition during capacitor switching.

  • Effective method: High-voltage and high-current single-phase conditioning can significantly improve performance.

  • Synthetic test circuit conditioning is also used to simulate real capacitor switching conditions.

For general applications, standard conditioning is applied. However, for capacitor switching duty, special conditioning is required to enhance electrical performance and initial breaking capability.

Conditioning Parameters:

  • Current Conditioning:
    3 kA to 10 kA, 200 ms half-wave, 12 shots per polarity (positive and negative).

  • Pressure Conditioning:

    • Static pressure (for axial magnetic field contacts): Apply 15–30 kN for 10 seconds.

    • Make-break conditioning (for transverse magnetic field contacts): Perform closing and opening operations on a test rig simulating actual breaker motion.

  • Voltage Conditioning:
    Apply 50 Hz AC voltage far exceeding rated voltage (e.g., 110 kV for a 12 kV interrupter) for 1 minute.

Test Parameters for Capacitor Switching

  • GB/T 1984: Back-to-back capacitor banks, inrush current 20 kA, frequency 4250 Hz.

  • IEC 62271-100 / ANSI Standards:

    • Capacitor bank switching: current 600 A, inrush 15 kA, frequency 2000 Hz

    • Switching current 1000 A, inrush 15 kA, frequency 1270 Hz

    • ANSI allows up to 1600 A for capacitor switching.

After proper conditioning, a 12 kV vacuum circuit breaker can typically pass:

  • 400 A back-to-back capacitor bank switching

  • 630 A single capacitor bank switching

However, for 40.5 kV systems, this is extremely challenging. Common solutions include:

  • Using SF₆ circuit breakers with gentler interruption characteristics

  • Using double-break vacuum circuit breakers, where two interrupters are connected in series. This significantly improves dielectric recovery strength, allowing it to exceed the rate of transient overvoltage rise during capacitor switching, thereby achieving successful arc extinction.

Magbigay ng tip at hikayatin ang may-akda!
Inirerekomenda
A Guide to the Latest Transformer Testing Technologies
A Guide to the Latest Transformer Testing Technologies
Transformers come in many types, primarily oil-immersed and dry-type. Their fault manifestations are diverse, but most failures are concentrated in the windings, core, connecting components, and oil contamination. For example, winding insulation damage, open circuits, short circuits, and inter-turn short circuits at connection points. Common external symptoms of transformer faults include severe overheating, excessive temperature rise, abnormal noise, and three-phase imbalance.Routine transforme
Oliver Watts
10/20/2025
Inspection of transformers can be performed without any detection tools.
Inspection of transformers can be performed without any detection tools.
Transformers are electrical devices that change voltage and current based on the principle of electromagnetic induction. In power transmission and distribution systems, transformers are essential for stepping up or stepping down voltages to reduce energy losses during transmission. For example, industrial facilities typically receive power at 10 kV, which is then stepped down to low voltage via transformers for on-site use. Today, let’s learn about several common transformer inspection methods.1
Oliver Watts
10/20/2025
How to Inspect 10kV Vacuum Circuit Breakers Properly
How to Inspect 10kV Vacuum Circuit Breakers Properly
I. Inspection of Vacuum Circuit Breakers During Normal Operation1. Inspection in Closed (ON) Position The operating mechanism should be in the closed position; The main shaft roller should be disengaged from the oil damper; The opening spring should be in a charged (stretched) energy-stored state; The length of the moving contact rod of the vacuum interrupter protruding below the guide plate should be approximately 4–5 mm; The bellows inside the vacuum interrupter should be visible (this does no
Felix Spark
10/18/2025
How to Choose Vacuum Circuit Breakers Correctly?
How to Choose Vacuum Circuit Breakers Correctly?
01 PrefaceIn medium-voltage systems, circuit breakers are indispensable primary components. Vacuum circuit breakers dominate the domestic market. Therefore, correct electrical design is inseparable from the proper selection of vacuum circuit breakers. In this section, we will discuss how to correctly select vacuum circuit breakers and common misconceptions in their selection.02 Interrupting Capacity for Short-Circuit Current Need Not Be Excessively HighThe short-circuit interrupting capacity of
James
10/18/2025
Mga Produkto na May Kaugnayan
Inquiry
I-download
Kumuha ng IEE-Business Application
Gamit ang app na IEE-Business upang makahanap ng kagamitan makuha ang mga solusyon makipag-ugnayan sa mga eksperto at sumama sa industriyal na pakikipagtulungan kahit kailan at saanman buong pagsuporta sa pag-unlad ng iyong mga proyekto at negosyo sa enerhiya