Brevis Discussio de Conversionis Problematis Reclosorum in Forinsecos Vacuum Disjunctores Usui Adhibendos

Noah
Campus: Design & Maintenance Constitutio & Conservatio
Australia

Transformatio rete electrica rurale iocum importantem agit in minuendo tariffis electricitatis ruralibus et accelerando developmentem economicam ruralem. Nuper, auctor participavit in designo quorundam parvorum projectorum transformationis rete electrica rurale sive substationes communes. In substationibus rete electrica rurale, systemata communa 10kV plerumque adhibent reclosers vacui circuiti auto exterioris 10kV.

Ut investitio salvaretur, schematam in transformatione adhibuimus quod removeret unitatem controlis recloser vacui circuiti auto exterioris 10kV et converteret eam in interrupper vacui externus. Haec quaestio suscitatur ut modus modificandi circuitos protectionis et controlis ad integrandum eos in systema monitorizationis integrale microcomputer-based. Hanc quaestionem et solutiones eius correspondentis elaborabimus infra.

1. Principia Basica Recloser Vacui Circuiti Auto Exterioris 10kV

Recloser vacui circuiti auto exterioris 10kV functiones commutationis, controlis, protectionis, et monitoriationis in unum corpus integra. Est dispositivum intelligentiale praeferendum pro automatione distributionis, capax operandi opening et reclosing operationes in lineis AC secundum sequentiam praescriptam, et postea resolvi automaticiter sive lock out. Habet functiones controlis et protectionis self-contained (necens nullam potentiam externam). Postquam introductus est in Sinam, propter suas unicas advantages, latissime usus est in urbano distributionibus retibus et substationibus ruralibus.

Recloser vacui circuiti auto exterioris 10kV constat ex duobus partibus: corpore recloser principali et unitate controller. Secundum methodum supplendi potentiam controlis, controller generaliter in tres configurationes venit:

  • Uti AC 220V directe tamquam potentia operationis et closing power pro controller;

  • Convertendi AC 220V in regulatum DC 220V pro potentia operationis et closing power;

  • Potentia controller cum batteria lithium interna.

Corpus recloser est instructum cum current transformers (CTs) bushing-typis ad detectandum currentem lineae. Valores mensurati ab unicuique phase separatim transmitteruntur ad controller. Post confirmantem currentem fault et post temporis delay praescriptum, recloser automaticiter operatur opening et reclosing operationes secundum sequentiam praedeterminatam. Quando fault transient occurrit in systema, functio automatica reclosing restituit supply potentiae automaticiter.

Si fault est permanentis, recloser operatur secundum sequentiam suam praescriptam. Post completum numerum reclosing attempts (typice tres), confirmat fault ut permanentis. Sectionalizer tunc isolat branch faulted, restituens supply potentiae ad sectiones non-faulted. Interventio manualis est necessaria ut fault clear et reset recloser’s status lockout ad revertendum ad normal operation. Uti cum sectionalizers et sectional circuit breakers, recloser efficaciter clears faults transientes et isolat loca fault permanentis, minimizando duration outages et area affected.

2. Methodi Modificationis Controller Recloser Vacui Circuiti Auto Exterioris 10kV

Ut reducatur costus investitionis, schematam in transformatione adhibuimus quod removeret unitatem controller recloser vacui circuiti auto exterioris 10kV et repurposet dispositivum ut interrupper vacui externus. Postquam substation adoptat systema automationis integrale, functiones protectionis et monitoriationis recloser debent disabilitari. Tamen, signales currentis a corpore recloser et trip/close circuits interruptoris debent connecti ad unitatem 10kV protectionis et monitoriationis systematis automationis integrale. Specifica modificationes sunt sequentes:

Disabilitare functiones protectionis et detectionis recloser disconnectendo supply potentiae controller et output circuits in terminal block.

Signales currentis a corpore recloser solent dirigi per terminal block controller ad unitatem 10kV protectionis et monitoriationis. Wiring a terminal block ad controller originalem debet disconnecti ut vitetur circuiti parasitic. Alternativiter, secondary side CTs in corpore recloser potest directe connecti ad unitatem 10kV protectionis et monitoriationis.

Supply potentiae pro 10kV unitate protectionis et monitoriationis integrale est typice DC 220V vel 110V. Pro tribus originalibus configurationibus supply potentiae, approaches modificationis sunt sequentes:

  • Configuratio originalis: AC 220V pro operatione et closing power
    → Replacer coil trip/close cum versione DC 220V vel 110V. Si mechanismus utitur motor charging spring qui non compatibilis est cum AC et DC, etiam repleri debet.

  • Configuratio originalis: AC 220V convertitur in regulatum DC 220V
    → Disconnectere supply potentiae a controller ad trip/close circuits et potentiari directe ab unitate 10kV protectionis et monitoriationis integrale. Supply potentiae substation debet setari ad DC 220V.

  • Configuratio originalis: Controller potentiatur a built-in battery lithium
    → In hoc casu, circuitus controlis solent uti DC 36V vel 12V, dum trip/close circuits utuntur AC 220V. Durante modificatione, coils trip/close repleri debent. Terminal coils debent connecti in series cum contactibus auxiliariis interruptoris et ducere directe ad terminal block. Omnis motor charging spring non rated pro AC et DC repleri debet.

Cum structura controller sit compacta, in selectendo replacement coils trip/close et motors charging, producta cum dimensionibus identicis originalibus preferenda sunt. Crucialiter, nova wiring non debet habere ullum connectionem cum circuitis originalibus controller ut preveniantur circuiti parasitic.

3. Conclusio

Durante transformatione rete electrica rurale, challenges possunt oriri quando refitting equipment existentium ad operandum cum novis systematis automationis. Tamen, quamdiu solutions appropriatae developentur pro his quaestionibus, saving cost potest attingi simulque objectiva projecti satisfieri.

Nota: Hoc methodus renovationis comparativus fuit in primis communi in primo melioramentis ruricolarum rete electricarum (p. ex. ante 2010) vel in tempore excludendi veteres instrumenta. In hodiernis retibus electricis ruricolis, novi instrumenta intelligentia vel specialis disjunctores vacuorum directe magis saepe collocantur.