Search


Tuning Method for Measuring Ground Parameters of Arc Suppression Coil Grounded Systems

This article explains the tuning method's principle for measuring system ground parameters its application scope and advantage of using resonant frequency to calculate grid parameters.

Leon
Field: Fault Diagnosis
10Year<
China
Add us on Google

The tuning method is suitable for measuring the ground parameters of systems where the neutral point is grounded via an arc suppression coil, but not applicable to ungrounded neutral point systems. Its measurement principle involves injecting a current signal with continuously varying frequency from the secondary side of the Potential Transformer (PT), measuring the returned voltage signal, and identifying the system's resonant frequency.

During the frequency sweeping process, each injected heterodyne current signal corresponds to a returned voltage value, based on which insulation parameters of the distribution network such as ground capacitance, ground conductance, detuning degree, and damping rate are calculated. When the frequency of the injected current signal matches the resonant frequency, parallel resonance occurs in the system, and the amplitude of the returned voltage on the secondary side reaches its maximum.

Once the resonant frequency is determined, the ground parameters of the distribution network system can be calculated accordingly. The specific principle is illustrated in Figure 1: a variable-frequency current signal is injected from the secondary side of the PT, and by varying the signal frequency, the relationship between the injected signal and the returned voltage signal is measured to find the resonant angular frequency &omega;₀ of the distribution network.

Tuning Method for Measuring Ground Parameters of Arc Suppression Coil Grounded Systems

The equivalent equivalent circuit of the injected signal at resonance is shown in Figure 2:

Tuning Method for Measuring Ground Parameters of Arc Suppression Coil Grounded Systems

Tuning Method for Measuring Ground Parameters of Arc Suppression Coil Grounded Systems

 

The advantage of the tuning method lies in that it does not require accurate measurement of the returned voltage value. It only needs to identify the resonant frequency injected when the returned voltage reaches its maximum, and then the grid parameters can be accurately calculated.