Learn if SF6 slight pressure drop allows long-term loaded operation – risks, thresholds, and safe actions before lockout value.
SF6 gas in high-voltage switchgear (circuit breakers, GIS, etc.) performs two critical functions:
Both functions are strongly correlated with gas density (pressure). Crucially, the SF6 compartment is a fixed volume — pressure varies significantly with temperature (rises when hot, drops when cold). Industry standard practice uses 20°C as the reference temperature for pressure conversion and comparison to avoid misjudgment from temperature fluctuations.
Equipment uses density relays (with temperature compensation) to set graded protection thresholds:
| Threshold | Definition |
|---|---|
| Rated Pressure | Standard operating pressure; arc-quenching and insulation performance at optimum. |
| Alarm Value (Warning) | Slightly below rated; arc-quenching and insulation still adequate but deviated from normal range — alerts O&M personnel for prompt action. |
| Lockout Value (Protection) | Further reduced pressure; arc-quenching and insulation insufficient — forces prohibition of open/close operations to prevent flashover or explosion. |
Relationship: Lockout Value < Alarm Value < Rated Value. As pressure drops, alarm triggers first; continued decline triggers lockout.

Although pressure has only dropped slightly and has not reached lockout — meaning the equipment can still operate safely temporarily — the real danger is not the low pressure itself, but the ongoing leakage trend.
Leakage is progressive: seal aging, flange seepage, welding defects — none self-heal. Drop by drop, month by month, pressure will eventually reach lockout, at which point the breaker is forcibly locked out and cannot operate.
Fault trip risk is extremely high: if a system fault occurs during pressure decline requiring a trip, insufficient arc-quenching may fail to extinguish the arc, leading to phase-to-phase short circuit or equipment explosion.
Insulation flashover risk: reduced pressure shrinks insulation margin; under overvoltage (lightning, switching) internal flashover may occur.
Core method: compare adjacent pressure readings under identical temperature conditions.
At the same temperature, if adjacent recorded pressure values differ by (0.1–0.3) × 10⁵ Pa, suspect leakage exists. Pressure readings are temperature-sensitive; comparison must be at same temperature, or use the density relay reading (already temperature-compensated). Specific leakage rate grading and handling strategies per equipment manufacturer procedures.
| Step | Action |
|---|---|
| 1. Confirm Alarm Level | Check density relay indication; verify current pressure is in alarm zone (above lockout, below rated). |
| 2. Enhance Monitoring | Record current pressure; increase patrol frequency; focus on pressure trend. |
| 3. Report to Dispatch & Request Outage | Standard practice. Equipment may remain loaded but must schedule outage for repair ASAP to prevent further decline to lockout. |
| 4. Implement Safety Pre-Control (Before Outage) | Execute in sequence: ① Remove operation fuse (prevents mis-trip if lockout circuit unreliable); ② Apply dedicated lockout tool to mechanically block mechanism (ensures no mis-operation under low pressure); ③ Re-install operation fuse (ensures fail-safe protection circuit remains active). |
| 5. Identify Root Cause | Use leak detector to locate leak points. Common locations: weld seams, flange sealing surfaces, arc chamber top covers, pipe joints. |
| 6. Replenish or Repair | If no leak found (normal long-term pressure drop): qualified technician performs live gas replenishment using SF6 purity ≥99.995%. Recharge slowly near rated pressure to avoid overpressure shock to seals. If leak found: immediately report to dispatch, transfer load, then outage for repair. |

Pure SF6 is non-toxic, odorless, and non-flammable. After arc decomposition, it produces toxic, corrosive byproducts:
Toxic Gases: Thionyl fluoride (SOF₂), sulfuryl fluoride (SO₂F₂), sulfur tetrafluoride (SF₄), sulfur dioxide (SO₂).
Toxic Solids: Metal fluoride powders (copper fluoride, aluminum fluoride, etc.) — white or gray-white powder.
SF6 is among the most potent greenhouse gases known. Per IPCC assessment reports:
Leakage means not only SF6 loss but potential moisture ingress. Moisture is a key driver of SF6 equipment insulation degradation:
Mechanism 1: Moisture + SF6 decomposition products → HF (hydrofluoric acid) & H₂SO₃ (sulfurous acid) → corrodes internal metal parts & insulation.
Mechanism 2: Moisture condenses at low temperature → reduces surface insulation strength → flashover risk.
SF6 pressure slightly below rated but above lockout = temporary loaded operation permissible, but long-term operation PROHIBITED.
Guiding Principle: Alarm doesn't always mean immediate trip; lockout means no operation. Check alarm first, then pressure, assess trend, confirm leak point.
Edited From:Garca