For a sectionalizer-what are the specific operating steps for automatic dropout tripping?

Rockwill RDK sectionalizer integrates intelligent control with dropout mechanism—zero standby power, maintenance-free lifetime, and precise MV network fault isolation.

Rockwill
Field: Manufacturing
10Year<
China
Add us on Google

A sectionalizer works in coordination with an upstream recloser (or circuit breaker) to isolate faults. Its core logic is count-then-trip on dead-line: it counts fault-current occurrences and opens only during a de-energized window — never under load, since it has no arc-interrupting capability.

Automatic Drop-Out Tripping Sequence

iee-business

Key Setting Parameters

Parameter Typical Value Description
Count set value 2 or 3 Number of fault-current counts before arming to trip; must be less than the recloser's total reclose attempts
Counter reset time 60 – 90 s Time after voltage restoration before the count resets to zero on a healthy line
Voltage-loss confirmation delay ≤ 0.5 s Delay before confirming a de-energized condition, preventing false detection
Minimum operating current 10 – 20 % of rated Fault-current threshold below which the counter does not increment

Important Notes

  • Sectionalisers must not be tripped manually or automatically under load (they have no arc-extinguishing capability). If manual operation is required, the upstream power supply must be disconnected first.

  • The preset tripping count must be strictly less than the reclosing count of the upstream recloser; otherwise, the recloser will lock out before the sectionaliser can complete fault isolation.

  • After a dropout trip, on-site inspection is required to identify and clear the fault before manual reclosing can be performed to restore service.

Rockwill Sectionalisers RDK Series are engineered around this core logic. Featuring an integrated design that combines a built-in microcomputer control unit with a highly reliable dropout operating mechanism, the RDK series ensures precise synchronization between fault current memory and trip triggering, while maintaining zero power consumption during standby. With maintenance-free stability throughout its entire service life, the RDK series fully meets the stringent requirements of medium-voltage distribution networks for autonomous fault isolation.

Edited From:Garca

 
Give a tip and encourage the author!

Comments

Share your question or perspective
WhatsApp
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Login
or continue with
New here?
Register