Rockwill RDK sectionalizer integrates intelligent control with dropout mechanism—zero standby power, maintenance-free lifetime, and precise MV network fault isolation.
A sectionalizer works in coordination with an upstream recloser (or circuit breaker) to isolate faults. Its core logic is count-then-trip on dead-line: it counts fault-current occurrences and opens only during a de-energized window — never under load, since it has no arc-interrupting capability.

| Parameter | Typical Value | Description |
|---|---|---|
| Count set value | 2 or 3 | Number of fault-current counts before arming to trip; must be less than the recloser's total reclose attempts |
| Counter reset time | 60 – 90 s | Time after voltage restoration before the count resets to zero on a healthy line |
| Voltage-loss confirmation delay | ≤ 0.5 s | Delay before confirming a de-energized condition, preventing false detection |
| Minimum operating current | 10 – 20 % of rated | Fault-current threshold below which the counter does not increment |
Sectionalisers must not be tripped manually or automatically under load (they have no arc-extinguishing capability). If manual operation is required, the upstream power supply must be disconnected first.
The preset tripping count must be strictly less than the reclosing count of the upstream recloser; otherwise, the recloser will lock out before the sectionaliser can complete fault isolation.
After a dropout trip, on-site inspection is required to identify and clear the fault before manual reclosing can be performed to restore service.
Rockwill Sectionalisers RDK Series are engineered around this core logic. Featuring an integrated design that combines a built-in microcomputer control unit with a highly reliable dropout operating mechanism, the RDK series ensures precise synchronization between fault current memory and trip triggering, while maintaining zero power consumption during standby. With maintenance-free stability throughout its entire service life, the RDK series fully meets the stringent requirements of medium-voltage distribution networks for autonomous fault isolation.