Secondary Gas-Insulated Switchgear & RMU (12–40.5kV) Engineering Guide

Engineering guide to secondary gas-insulated switchgear & RMU (12kV–40.5kV). Hermetic 3.0mm stainless steel, eco N2 zero-GWP panels. Certified IEC 62271-200.

Jaylen
Field: Relay protection
Energineer
10Year<
China
Add us on Google

1. Executive Summary & Architectural Overview

Secondary gas-insulated switchgear (Secondary GIS) and compact ring main units (RMU) represent the core infrastructure of modern urban, coastal, and industrial medium-voltage power distribution networks. Designed to operate across 12kV, 24kV, 36kV, and 40.5kV voltage classes, these assemblies house all primary medium-voltage busbars, rotary disconnectors, and vacuum circuit breakers inside a hermetically sealed gas envelope.

By isolating all high-voltage conductors from ambient atmospheric conditions, secondary GIS delivers an operational footprint up to 70% smaller than traditional air-insulated switchgear (AIS) while providing complete immunity against humidity, salt spray, airborne chemical pollution, and floodwater submersion.

2. Physical Construction: The 3.0mm Laser-Welded Hermetic Stainless Steel Tank

The cornerstone of secondary GIS reliability is the gas vessel. RW Energy manufactures its secondary GIS tanks from heavy-gauge 3.0mm corrosion-resistant stainless steel utilizing computer-controlled robotic laser welding.

Key engineering benchmarks of this construction include:

  • Ingress Protection Degree: Rated IP65, the gas tank can withstand temporary flood submersion in underground vaults without moisture ingress or dielectric tracking.
  • Vacuum Mass-Spectrometry Leak Detection: Every fabricated tank is tested in a vacuum chamber using helium tracer gas before gas filling, certifying an annual gas leakage rate below 0.1% across a 30-year sealed-for-life design duration.
  • Maintenance-Free High-Voltage Core: Because primary switching contacts and busbars operate in an inert, oxygen-free gas environment, internal contact oxidation and partial discharge inception are completely eliminated.

3. Decarbonization Roadmap: Eco-Friendly Nitrogen-Insulated Switchgear

In response to global greenhouse gas phase-out mandates and European F-gas regulations, RW Energy delivers eco-friendly nitrogen-insulated secondary switchgear (such as Product 3426).

Technical highlights of the clean-air alternative include:

  • Pure Nitrogen Gas Medium: Utilizing pure nitrogen (N2) with zero global warming potential (GWP = 0) and zero ozone depletion potential (ODP = 0).
  • Vacuum Circuit Breaker Core: Current interruption is executed entirely within hermetically sealed ceramic vacuum interrupters, ensuring safe load, fault, and transformer inrush breaking.
  • Zero Regulatory Reporting: Eliminates mandatory SF6 mass inventory logging, gas leakage emission taxation, and specialized decommissioning recovery contractor expenses.

4. Modular Functional Units & System Configuration (C, V, F Schemes)

Secondary GIS lineups can be delivered as compact monolithic multi-way tanks or modular expandable assemblies joined by shielded solid-insulated busbar extensions:

  • Code C (Cable Switch Unit): Features a 3-position rotary load break switch (Closed, Open, Earthed) with capacitive voltage indicators and integral earthing switch rated for full making capacity.
  • Code V (Vacuum Circuit Breaker Unit): Houses high-endurance vacuum circuit breakers rated up to 2500A and 31.5kA short-circuit breaking, equipped with CT-powered autonomous digital protection relays requiring zero external potential transformers.
  • Code F (Switch-Fuse Combination): Provides transformer feeder protection utilizing fast-acting current-limiting fuses with striker-pin mechanical trip linkages conforming to IEC 62271-105.

5. International Standards Compliance & Safety Interlocking

RW Energy secondary gas-insulated switchgear is type-tested and certified by accredited international testing authorities:

  • AC Metal-Enclosed Switchgear: Fully certified to IEC 62271-200.
  • Vacuum Circuit Breakers: Conforms to IEC 62271-100.
  • Disconnectors & Earthing Switches: Conforms to IEC 62271-102.
  • Internal Arc Classification: Certified IAC AFLR up to 31.5kA for 1.0 second, directing arc-flash pressure waves upward through rear blast channels.
  • Mechanical Five-Prevention Interlocking: Enforces strict operational sequencing, preventing operator access to energized cable rooms and disallowing switching between live and earthed states under load.

6. Substation Automation & Telemetry Integration

All secondary GIS units can be equipped with factory-fitted motorized operating mechanisms, auxiliary contacts, and feeder terminal units (FTUs). Supporting standardized industrial protocols including Modbus, DNP3.0, and IEC 61850, the switchgear enables real-time SCADA telemetry, automated fault detection, and rapid FLISR feeder reconfiguration across smart grid architectures.

Technical Inquiries & Global EPC Support

Give a tip and encourage the author!

Comments

Share your question or perspective
WhatsApp
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Login
or continue with
New here?
Register