The Application of Reclosers and Sectionalizers in Distribution Network Automation

06/03/2025

1. Selection of Reclosers and Sectionalizers
The selection of reclosers and sectionalizers is crucial for achieving distribution network automation. Sectionalizers cooperate with the upstream circuit breakers on the power supply side. They automatically trip when three conditions are simultaneously met: the fault current exceeds its set - value, the line undervoltage current is less than 300 mA, and the set number of counts is reached. Reclosers are applied in indoor substations or on outdoor poles. They enhance power supply reliability through multiple reclosing operations, identify fault areas, reduce the power - outage area, and miniaturize the information upload control system, thereby meeting the requirements of distribution network automation.
  • Install an outdoor high - voltage vacuum automatic recloser (with a permanent - magnet mechanism) at the substation outlet as the main line protection switch. This switch should be adjusted to perform two reclosing operations, one fast and two slow (it can also be adjusted according to specific needs).
  • Install sectionalizers with two - count functions at the entrances of large branches, and install sectionalizers with one - count functions at the entrances of small branches. This effectively isolates the terminal accident points, reduces the power - outage area, and optimizes their coordination.
  • Since the line protection adopts reclosing protection, it effectively ensures that the line can bypass transient faults, preventing more than 85% of transient faults from severely affecting the power supply quality.
  • When installing a recloser, calculate the short - circuit current and then adjust its activation value.
  • Reclosers are equipped with remote - operation interfaces, which provide sufficient room for future implementation of "four - remote" control (remote sensing, remote control, remote signaling, and remote metering).
  • For line grounding faults, reclosers have grounding - fault protection functions, but they can only protect the entire line. When a grounding fault occurs, the specific location of the fault cannot be determined. If a sectionalizer with grounding - fault protection function is selected, the cost is extremely high. It is recommended to use a grounding - fault receiver in the substation and grounding - fault indicators on the line. When a grounding fault occurs, the grounding - fault indicators on the line flip to indicate and send signals to determine the specific location, and the grounding - fault receiver in the substation receives the signals and gives an alarm.
  • To ensure good coordination between reclosers and sectionalizers, the originally installed pole - mounted vacuum circuit breakers on the line must be converted into load switches.
2. Example Illustration
Take the radial - structured power grid shown in Figure 1 as an example. Install sectionalizers with a count of 2 times at the entrances of large branches where the load is particularly heavy and the lines are relatively long, and install sectionalizers with a count of 1 time at the entrances of small branches. Set the recloser at the substation outlet to have an inverse - time characteristic with one fast and two slow operations. Install a sectionalizer F1 with a count of 2 times at the entrance of the L2 branch of line L1, and install a sectionalizer F2 with a count of 1 time at the L3 branch.
If a fault occurs in the L2 branch, the recloser at the substation outlet detects the fault current and acts quickly once. Since the sectionalizer F1 has not reached the set number of counts, it remains in the closed state. After a certain reclosing interval, the recloser at the substation outlet recloses. If it is a transient fault, the power supply to the line is restored after the recloser recloses. If it is a permanent fault, the outlet recloser trips again. The sectionalizer F1 reaches the set number of counts, drops, and trips, isolating the fault section. After the outlet recloser recloses again, the power supply to the other lines is restored.
This solution is applicable when the original pole - mounted circuit breakers cannot meet the requirements of distribution network automation. Adding reclosers and sectionalizers fully realizes the protection of 10 kV lines, is suitable for the construction and development of the power grid, and meets the requirements of distribution network automation.

As an expert in the application and trends of electrical equipment, I have a profound mastery of knowledge in circuits, power electronics, etc. I possess a comprehensive set of abilities including equipment design, fault diagnosis, and project management. I can precisely grasp the industry's pulse and lead the development of the electrical field.

A hybrid DC circuit breaker
A hybrid DC circuit breaker
Most DC molded-case circuit breakers use natural air arc extinction, and there are typically two arc extinguishing methods: one is conventional opening and closing, where the contacts axially stretch the arc, while the conductive circuit generates a magnetic field that bends and elongates the arc, pulling it lengthwise perpendicular to the arc axis. This not only increases the arc length but also induces lateral motion, enabling air cooling to achieve arc extinction.The other method involves the
09/02/2025
 Can AC and DC circuit breakers be used interchangeably?
Can AC and DC circuit breakers be used interchangeably?
First of all, it must be clarified: AC circuit breakers must not be used to replace DC circuit breakers in DC circuits!Due to differences in arc generation and extinction processes between AC and DC, AC and DC circuit breakers with the same rated values do not have identical capabilities when interrupting DC power. Using AC circuit breakers in place of DC ones, or mixing AC and DC breakers, is one of the main causes of protection miscoordination and unintended upstream tripping.Circuit breakers
09/02/2025
ABB Solid-State DC Circuit Breaker Advantages!
ABB Solid-State DC Circuit Breaker Advantages!
Fully electric commercial vessels are becoming increasingly popular, with DC power systems being the preferred choice for onboard power distribution due to their ability to handle high power flows within limited space at higher system efficiency and lower lifecycle costs.Commercial vessels equipped with onboard DC grids have proven capable of operating at peak energy efficiency while minimizing emissions. This results in significant power savings and reduced operating costs across maritime appli
09/02/2025
Research and Application of Communication Security Strategies for Smart Meters
Research and Application of Communication Security Strategies for Smart Meters
1. Security Threats Facing Smart Meter Communications1.1 Physical Layer Security ThreatsPhysical layer security threats refer to factors that damage or interfere with the hardware devices and physical connections of smart meters, directly affecting their normal operation and data transmission. From the perspective of equipment damage, harsh natural environments such as lightning strikes, floods, and earthquakes can directly destroy the hardware circuits and structures of smart meters, rendering
09/01/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!