What is Sag in Overhead Conductor ?

Encyclopedia
Field: Encyclopedia
0
China


What is Sag in Overhead Conductor ?


Sag Definition


Sag in a transmission line is defined as the vertical distance between the highest points of support and the lowest point of the conductor.

 

c353157cb6702e963779577f66e7b8fe.jpeg

 

 

Purpose of Sag


Including appropriate sag protects transmission lines from excessive tension and potential damage, especially under adverse conditions.Sag is mandatory in transmission line conductor suspension. The conductors are attached between two supports with the perfect value of sag.Sag is critical as it prevents the conductor from being overstretched and experiencing unsafe tension levels, thereby enhancing durability.

 


If the conductor is stretched fully during installation, wind exerts pressure on the conductor, hence the conductor gets a chance to be broken or detached from its end support. Thus sag is allowed to have during conductor suspension.

 


Some important points to note

 


  • When the same leveled two supports hold the conductor, a bent shape arises in the conductor. Sag is very small with respect to the span of the conductor.



  • The Sag span curve is parabolic.



  • At each point along the conductor, the tension is always tangential, maintaining balance across the span.



  • Again the horizontal component of the tension of the conductor is constant throughout conductor length.


  • The tension at supports is nearly equal to the tension at any point in the conductor.



6b0cb473e4f908ef829881494c2e203c.jpeg

 

 


Calculation Methodology


When calculating sag in a transmission line, two different conditions need to be considered:

 


  • When supports are at equal levels

  • When supports are not at equal levels


The formula to calculate sag changes based on whether the support levels (i.e. the transmission towers holding up the overhead conductor) are at the same level.

 


Sag calculation for supports are at equal levels

 


Suppose, AOB is the conductor. A and B are points of supports. Point O is the lowest point and the midpoint.Let, L = length of the span, i.e. ABw is the weight per unit length of the conductorT is the tension in the conductor.We have chosen any point on the conductor, say point P.The distance of point P from the Lowest point O is x.y is the height from point O to point P.

 


af9a8a6e7219b2a477832061f794c8bd.jpeg

 


Equating two moments of two forces about point O as per the figure above we get,

 


 

Sag calculation for supports are at unequal levels

 


Suppose AOB is the conductor that has point O as the lowest point.L is the Span of the conductor.h is the difference in height level between two supports.X 1 is the distance of support at the lower level point A from O.x2 is the distance of support at the upper-level point B from O.T is the tension of the conductor.w is the weight per unit length of the conductor.

 


9c3aeefba54a078a21d2ddf9193d132f.jpeg

 


So, having calculated the value of x 1 and x2, we can easily find out the value of sag S1 and sag S2. This formula calculates sag under conditions of still air and normal temperature, where only the conductor’s own weight affects it.

 


Environmental Impact


Some of the effects of ice and wind on sag include:

 

The weight per unit length of the conductor is changed when the wind blows at a certain force on the conductor and ice accumulate around the conductor.


Wind force acts on the conductor to change the conductor self-weight per unit length horizontally in the direction of the airflow.Ice loading acts on the conductor to change the conductor self-weight per unit length vertically downward.Considering wind force and ice loading both at a time, the conductor will have a resultant weight per unit length.


The resultant weight will create an angle with the ice loading down ward direction.Let us assume, w is the weight of the conductor per unit length.wi is the weight of ice per unit lengthwi= density of ice × volume of ice per unit length w is the force of wind per unit length.ww = wind pressure per unit area × projected area per unit length

 


435aff9eddbe96a301a2768baced631a.jpeg

 

 


So, the total weight of the conductor per unit length is

 

 


The sag in the conductor is given by

 


So the vertical sag

 


dba7cd98a6ab172c272ca12f0c134291.jpeg

 


Safety Considerations


Proper sag calculation is vital for maintaining the structural integrity and operational reliability of transmission lines.

 

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.