Relay Protection Basics: Types of Transmission Line Faults and Fundamental Protection Schemes

Leon
Field: Fault Diagnosis
China

1. Types of Faults on Power Lines

Phase-to-Phase Faults:

  • Three-phase short circuit

  • Two-phase short circuit

Ground Faults:

  • Single-phase to ground fault

  • Two-phase to ground fault

  • Three-phase to ground fault

2. Definition of Relay Protection Devices
When an abnormality or fault occurs in a component of a power system, relay protection devices are those that can quickly and selectively isolate the faulty or abnormal component from the system, ensuring the continued normal operation of the remaining healthy equipment.

Examples include: overcurrent protection, distance protection, zero-sequence protection, and high-frequency protection.

  • Main Protection: Protection that meets the basic requirements for system stability and equipment safety during a short-circuit fault. It operates first to trip the circuit breaker and selectively clears faults on the protected equipment or entire line.

  • Backup Protection: Protection that removes the fault if the main protection or circuit breaker fails to operate.

  • Auxiliary Protection: Simple protection added to compensate for limitations in main and backup protection.

3. Role of Relay Protection in Transmission Lines
During operation, transmission lines may experience faults due to strong winds, ice and snow, lightning strikes, external damage, insulation failure, or pollution flashover. In such cases, the relay protection device can act quickly and selectively, tripping the line circuit breaker (switch).

If the fault is transient, the switch successfully recloses after the fault disappears, restoring safe power supply. If the fault is permanent, the reclosing fails, and the faulty line is rapidly isolated, ensuring uninterrupted power supply to the healthy lines.

4. Overcurrent Protection Devices
Overcurrent protection devices are designed based on the significant increase in current during a line fault. When the fault current reaches the protection setting (pickup current), the device initiates operation. Once the time delay setting is reached, the line circuit breaker trips.

Common types include:

  • Instantaneous Overcurrent Protection: Simple, reliable, and fast-acting, but only protects a portion (typically 80–85%) of the same line.

  • Time-Delayed Overcurrent Protection: Operates with a short time delay, protecting the full length of the line and coordinating with the instantaneous protection of the next downstream line.

  • Overcurrent Protection: Set to avoid maximum load current. It protects the entire length of the line and the full length of the next line, serving as backup protection.

  • Directional Overcurrent Protection: Adds a power direction element to overcurrent protection. It operates only when the fault power flows from the bus to the line, preventing misoperation during reverse-direction faults.

5. Distance Protection Devices
Distance protection responds to the impedance (or distance) between the fault point and the protection installation point. It has excellent directional characteristics and is widely used on high-voltage ring networks. Three-stage distance protection is commonly employed:

  • Zone I: Instantaneous operation, protecting 80%–85% of the line length.

  • Zone II: Protects the entire length of the line and extends into part of the next line (typically Zone I of the adjacent line).

  • Zone III: Protects the full length of this line and the next line, serving as backup for Zones I and II.

6. Zero-Sequence Current Protection Devices
In directly grounded neutral systems (also known as high-earth-fault-current systems), a single-phase-to-ground fault produces a significant zero-sequence current. Protection devices that use this current are called zero-sequence current protection devices. A three-stage configuration is commonly used:

  • Stage I: Instantaneous zero-sequence current protection, covering 70%–80% of the line length.

  • Stage II: Time-delayed zero-sequence current protection, covering the full line length and part of the next line.

  • Stage III: Zero-sequence overcurrent protection, covering the full line and serving as backup for the next line.

7. High-Frequency Protection Devices
High-frequency protection converts the phase angle (or power direction) of currents at both ends of a line into high-frequency signals, which are transmitted via a high-frequency channel to the opposite end. The system compares the current phase or power direction at both ends.

This protection only responds to faults within the protected line section and does not require coordination with downstream lines. It operates without time delay, enabling rapid clearance of any fault along the protected line.

Based on operating principles, high-frequency protection is classified into:

  • Blocking Type (Directional Comparison): Compares power direction at both ends.

  • Phase Comparison Type: Compares current phase angles at both ends.

8. Automatic Reclosing Devices
An automatic reclosing device is one that automatically re-closes the circuit breaker after it has tripped.

Function:

  • For transient faults, after the fault clears, the device quickly re-closes the breaker, restoring normal power supply.

  • For permanent faults, the reclosing fails, the breaker trips again, and the faulty line is isolated, ensuring continued power supply to healthy lines.

9. Line Fault Recorder
A device that automatically records the waveforms of current and voltage before and during a line fault, along with the timing and circuit breaker operation status.

By analyzing the recorded waveforms, the fault type can be accurately determined, and the approximate fault location can be calculated. This provides critical data for fault analysis, troubleshooting, and restoration of normal power supply.

Give a tip and encourage the author!
Recommended
5 Common Transmission Line Faults and Effective Prevention Methods
1. OverviewA transmission line fault is a sudden power interruption caused by various factors. To restore supply and prevent recurrence, operators must first locate the fault point, identify the type, determine the cause, and implement repairs.The most common faults include: Lightning strikes Ice buildup (icing) Wind deviation (wind sway) Bird-related issues Pollution flashover External damageUnderstanding these faults and their prevention is critical for grid reliability.2. Lightning Strike Fau
Edwiin
09/05/2025
Analysis of Accident Handling in Transmission Lines
Analysis of Transmission Line Fault HandlingAs a fundamental component of the power grid, transmission lines are widely distributed and numerous, often exposed to diverse geographical and climatic conditions, making them highly susceptible to faults. Common causes include overvoltage, pollution flashover, insulation damage, tree encroachment, and external damage. Line tripping is one of the most frequent faults in power plant and substation operations, with fault types including single-phase-to-
Leon
09/04/2025
Fault Analysis and Treatment of Oil-Immersed Transformers
Oil Leakage at Welded JointsOil leakage at welded joints primarily stems from poor welding quality, such as incomplete or detached welds, and defects like pinholes and gas pores. Although oil-immersed transformers are initially coated with solder and paint during manufacturing, potentially masking these issues temporarily, the defects tend to surface during operation. Additionally, electromagnetic vibration can cause weld cracks, leading to oil leakage.To resolve such leaks, the first critical s
Edwiin
08/29/2025
Cable Fault Detection, Testing, Location and Repair
I. Methods for Cable Testing and Inspection:Insulation Resistance Test: Use an insulation resistance tester to measure the insulation resistance value of the cable. A high insulation resistance value indicates good insulation, while a low value may suggest insulation problems requiring further investigation.Voltage Withstand Test: Apply a high-voltage test using a high-voltage tester to verify whether the cable can withstand high voltage under its rated operating conditions. Under normal circums
Leon
08/29/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.