Relay Protection Basics: Types of Transmission Line Faults and Fundamental Protection Schemes

Leon
Leon
Field: Fault Diagnosis
China

1. Types of Faults on Power Lines

Phase-to-Phase Faults:

  • Three-phase short circuit

  • Two-phase short circuit

Ground Faults:

  • Single-phase to ground fault

  • Two-phase to ground fault

  • Three-phase to ground fault

2. Definition of Relay Protection Devices
When an abnormality or fault occurs in a component of a power system, relay protection devices are those that can quickly and selectively isolate the faulty or abnormal component from the system, ensuring the continued normal operation of the remaining healthy equipment.

Examples include: overcurrent protection, distance protection, zero-sequence protection, and high-frequency protection.

  • Main Protection: Protection that meets the basic requirements for system stability and equipment safety during a short-circuit fault. It operates first to trip the circuit breaker and selectively clears faults on the protected equipment or entire line.

  • Backup Protection: Protection that removes the fault if the main protection or circuit breaker fails to operate.

  • Auxiliary Protection: Simple protection added to compensate for limitations in main and backup protection.

3. Role of Relay Protection in Transmission Lines
During operation, transmission lines may experience faults due to strong winds, ice and snow, lightning strikes, external damage, insulation failure, or pollution flashover. In such cases, the relay protection device can act quickly and selectively, tripping the line circuit breaker (switch).

If the fault is transient, the switch successfully recloses after the fault disappears, restoring safe power supply. If the fault is permanent, the reclosing fails, and the faulty line is rapidly isolated, ensuring uninterrupted power supply to the healthy lines.

4. Overcurrent Protection Devices
Overcurrent protection devices are designed based on the significant increase in current during a line fault. When the fault current reaches the protection setting (pickup current), the device initiates operation. Once the time delay setting is reached, the line circuit breaker trips.

Common types include:

  • Instantaneous Overcurrent Protection: Simple, reliable, and fast-acting, but only protects a portion (typically 80–85%) of the same line.

  • Time-Delayed Overcurrent Protection: Operates with a short time delay, protecting the full length of the line and coordinating with the instantaneous protection of the next downstream line.

  • Overcurrent Protection: Set to avoid maximum load current. It protects the entire length of the line and the full length of the next line, serving as backup protection.

  • Directional Overcurrent Protection: Adds a power direction element to overcurrent protection. It operates only when the fault power flows from the bus to the line, preventing misoperation during reverse-direction faults.

5. Distance Protection Devices
Distance protection responds to the impedance (or distance) between the fault point and the protection installation point. It has excellent directional characteristics and is widely used on high-voltage ring networks. Three-stage distance protection is commonly employed:

  • Zone I: Instantaneous operation, protecting 80%–85% of the line length.

  • Zone II: Protects the entire length of the line and extends into part of the next line (typically Zone I of the adjacent line).

  • Zone III: Protects the full length of this line and the next line, serving as backup for Zones I and II.

6. Zero-Sequence Current Protection Devices
In directly grounded neutral systems (also known as high-earth-fault-current systems), a single-phase-to-ground fault produces a significant zero-sequence current. Protection devices that use this current are called zero-sequence current protection devices. A three-stage configuration is commonly used:

  • Stage I: Instantaneous zero-sequence current protection, covering 70%–80% of the line length.

  • Stage II: Time-delayed zero-sequence current protection, covering the full line length and part of the next line.

  • Stage III: Zero-sequence overcurrent protection, covering the full line and serving as backup for the next line.

7. High-Frequency Protection Devices
High-frequency protection converts the phase angle (or power direction) of currents at both ends of a line into high-frequency signals, which are transmitted via a high-frequency channel to the opposite end. The system compares the current phase or power direction at both ends.

This protection only responds to faults within the protected line section and does not require coordination with downstream lines. It operates without time delay, enabling rapid clearance of any fault along the protected line.

Based on operating principles, high-frequency protection is classified into:

  • Blocking Type (Directional Comparison): Compares power direction at both ends.

  • Phase Comparison Type: Compares current phase angles at both ends.

8. Automatic Reclosing Devices
An automatic reclosing device is one that automatically re-closes the circuit breaker after it has tripped.

Function:

  • For transient faults, after the fault clears, the device quickly re-closes the breaker, restoring normal power supply.

  • For permanent faults, the reclosing fails, the breaker trips again, and the faulty line is isolated, ensuring continued power supply to healthy lines.

9. Line Fault Recorder
A device that automatically records the waveforms of current and voltage before and during a line fault, along with the timing and circuit breaker operation status.

By analyzing the recorded waveforms, the fault type can be accurately determined, and the approximate fault location can be calculated. This provides critical data for fault analysis, troubleshooting, and restoration of normal power supply.

Give a tip and encourage the author!
Recommended
Grounding Causes of Cable Lines and the Principles of Incident Handling
Grounding Causes of Cable Lines and the Principles of Incident Handling
Our 220 kV substation is located far from the urban center in a remote area, surrounded primarily by industrial zones such as Lanshan, Hebin, and Tasha Industrial Parks. Major high-load consumers in these zones—including silicon carbide, ferroalloy, and calcium carbide plants—account for approximately 83.87% of our bureau’s total load. The substation operates at voltage levels of 220 kV, 110 kV, and 35 kV.The 35 kV low-voltage side mainly supplies feeders to ferroalloy and silicon carbide plants
Felix Spark
10/21/2025
 Latest Standards for Surge Arresters in Cable Auxiliary Equipment (2025)
Latest Standards for Surge Arresters in Cable Auxiliary Equipment (2025)
Standards for Surge Arresters Used in Cable Auxiliary Equipment GB/T 2900.12-2008 Electrotechnical Terminology – Surge Arresters, Low-Voltage Surge Protective Devices, and ComponentsThis standard defines specialized terminology for surge arresters, low-voltage surge protective devices, and their functional components. It is primarily intended for use in drafting standards, writing technical documents, translating professional manuals, textbooks, journals, and publications. GB/T 11032-2020 Metal-
Edwiin
10/21/2025
 What Are the Types and Common Faults of HV Switchgear?
What Are the Types and Common Faults of HV Switchgear?
High-voltage switchgear is a critical electrical device in power systems. Deterioration in switchgear operating conditions is one of the main causes of power system failures. So, what are the common faults in high-voltage switchgear?I.Classification of High-Voltage Switchgear(1) Outdoor and Indoor TypesBased on installation location, high-voltage switchgear can be classified as outdoor or indoor types. Indoor switchgear is commonly used for systems at 10 kV and below. According to primary circui
Noah
10/10/2025
What Causes Boiling or Popping in Transformers
What Causes Boiling or Popping in Transformers
Normal operating sound of a transformer. Although a transformer is static equipment, a slight, continuous "humming" sound can be heard during operation. This sound is an inherent characteristic of operating electrical equipment, commonly known as "noise." A uniform and continuous sound is considered normal; an uneven or intermittent noise is abnormal. Tools such as a stethoscope rod can assist in determining whether the transformer's sound is normal. The causes of this noise are as follows: Vibr