Specificationes vel Aestimatio Banci Condensatorum Electricorum

Electrical4u
Campus: Electrica Elementaria
0
China

Quae sunt Specificationes vel Rating Potentiae Capacitor Bank

Capacitor bank per totam suam vitam diversis conditionibus systematis abnormalibus subire debet. Ut haec abnormia ad optimam costum manufacturam sustineat, capacitor banks rating cum sequentibus parametris permittitis. Capacitor bank in his limitibus servitium suum continuare debet.

  1. 110 % normalis systematis peak voltage.

  2. 120 % normalis systematis rms voltage.

  3. 135 % rated KVAR.

  4. 180 % normalis rated rms current.

Voltage Rating Capacitor Bank

Capacitor unit normaliter pro una phase designatur. Capacitor debet operari liceat usque ad 110% rated peak phase voltage systematis et etiam operari 120% rated rms phase voltage, id est, 120%times peak phase voltage.

KVAR Rating Capacitor Unit

Capacitor unit normaliter rating suo KVAR habet. Standard capacitor unit in mercato disponibilis, saepe rating KVAR sequentibus habet.
50 KVAR, 100 KVAR, 150 KVAR, 200 KVAR, 300 KVAR et 400 KVAR.
KVAR ad
systema potentiae dependet a systematis voltage secundum hanc formulam.

Temperature Rating Capacitor Bank

Hae sunt duae causae principales caloris in capacitor bank.

  1. Capacitor bank outdoor type saepe in spatio aperto instauratur ubi soles directe in capacitor unit cadunt. Capacitor potest etiam calorem a fornace proxima absorbere pro qua instaurata est.

  2. Productio caloris in capacitor unit initium sumit a VAR quod unit tradit.

Propter raditionem huius caloris, sufficientia dispositiva esse debent. Maxima temperatura ambientalis in qua capacitor bank operari debet tabulariter sequitur,

Maxima Temperatura Ambientalis


Pro meliori ventilatione, satis spatii inter capacitor units esse debet. Interdum aer fluxus coactus uti potest ad accelerandum radiationem caloris a banco.

Capacitor Bank Unit vel Capacitor Unit

Capacitor bank units vel simpliciter capacitors units fabricantur in configuratione unius phase vel trium phasium.

Single Phase Capacitor Unit

Capacitor units unius phase designantur aut double bushing aut single bushing.

Double Bushing Capacitor Unit

Hic, termini utriusque extremi capacitor assembly ex metallic casing unit per duas bushings egrediuntur. Tota capacitor assembly, hoc est series parallel combination requiriti numeri capacitivorum elementorum, immersa est in insulante fluido casing. Ergo, erit insulata separatio inter conductivam partem capacitor element assembly per bushings, non erit connexio inter conductor et casing. Hoc est cur double bushing capacitor unit cognoscitur ut dead tank capacitor unit.

Single Bushing Capacitor Unit

In hoc casu, casing unit ut secundum terminus assembly capacitor elementi usatur. Hic, unus bushing utitur ad terminandum unum extremum assembly et alter terminus internus connectitur ad metallic casing. Hoc possibile est quia praeter terminum, omnis alia pars conductiva capacitor assembly a casing insulatur.

Three Bushing Capacitor Unit

Capacitor unit trium phasium tres bushings habet ad terminandum tres phases respective. Non est terminalis neutralis in capacitor unit trium phasium.

BIL vel Basic Insulation Level Capacitor Unit

Sicut alia instrumenta electrica, capacitor bank etiam diversas voltage conditiones, ut power frequency over voltages et lightening et switching over voltages, sustinere debet.
Itaque
Basic Insulation Level in omni capacitor unit rating plate specificandus est.

Internal Discharge Device

Capacitor units normaliter cum internal discharge device providentur quod celerem dismissionem residuae voltage ad suum tuto level, id est, 50 V vel minus, intra specificum tempus periodum assecurat. Capacitor unit etiam rating suo discharge period habet.

Transient Over Current Rating

Power capacitor transiens current situatione durante operationis switching subire potest. Itaque capacitor unit rating habere debet pro permisso short circuit current pro specifico tempore.
Itaque,
capacitor unit rating habere debet cum omnibus supra mentionatis parametris.
Exemplum rating typicalis capacitor unit sequitur-
Itaque, power capacitor unit rating fieri potest ut sequitur,

  1. Nominalis systematis voltage in KV.

  2. Systematis power frequency in Hz.

  3. Temperatura classis cum maxima et minima temperatura permissa in oC.

  4. Rated voltage per unit in KV.

  5. Rated output in KVAR.

  6. Rated capacitance in µF.

  7. Rated current in Amp.

  8. Rated insulation level (Nominal voltage/Impulse voltage).

  9. Discharge time/voltage in second/voltage.

  10. Fusing arrangement sive interne fusus sive externe fusus sive fuseless.

  11. Numerus bushing, double/single/triple bushing.

  12. Numerus phasium. Unus phase vel tres phases.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Donum da et auctorem hortare

Suggestus

Accidentia Transformatoris Principalis et Questiones Operationis Gas Luminis
1. Registri accidentis (XIX Martii, MMXIX)Hora XVI:XIIX die XIX Martii, MMXIX, monitorium background reportavit actionem gas levis transformatoris principis numeri III. Conformiter Codex Operationis Transformatorum Electricitatis (DL/T572-2010), personale operationis et maintenance (O&M) inspectavit statum in situ transformatoris principis numeri III.Confirmatio in situ: Panel non-electricus protectionis WBH transformatoris principis numeri III reportavit actionem gas levis phase B corpus tr
02/05/2026
Culpae et Tractatio Terrae Unipolaris in Lineis Distributionis 10kV
Characteristica et Instrumenta Detegendi Defectus Terrae Monofasiales1. Characteristica Defectuum Terrae MonofasialiumSigna Centralia Admonitionis:Campanula admonitionis sonat, et lucerna indicativa inscripta „Defectus Terrae in Sectione Omnibus [X] kV [Y]“ accenditur. In systematibus ubi punctum neutrum per bobinam Petersen (bobinam suppressionis arcus) ad terram connectitur, lucerna indicativa „Bobina Petersen Operatur“ etiam accenditur.Indicationes Voltmetri Monitoris Isolationis:Tensio phase
01/30/2026
Modus operationis terre iunctae puncti neutralis pro transformatoribus retis electricitatis 110kV~220kV
Dispositio modi operis terrae puncti neutralis pro transformatoribus rete electricitatis 110kV~220kV debet exigentias tolerationis insulationis puncti neutralis transformatorum complere, et simul conari ut impedimentum sequentiae nullae stationum transformationis fere immutatum maneat, dum certatur ne impedimentum sequentiae nullae compositum in quocumque puncto raptus circuiti systematis ultra ter impedimentum sequentiae positivae compositum excedat.Pro transformatoribus 220kV et 110kV in novis
01/29/2026
Cur Quare Substationes Lapidem Gravem Calculos et Rupem Fractam Utuntur
Cur Quare Substationes Utuntur Lapidibus, Gravibus, Piscinis et Saxis Tritis?In stationibus transformationis, instrumenta ut transformatores electricitatis et distributionis, lineae transmissionis, transformatores tensionis, transformatores currentis et commutatores disiunctionis omnia terram exigunt. Praeter terram, nunc profundius explorabimus cur gravia et saxa trita in stationibus transformationis saepe utuntur. Quamquam videantur ordinaria, isti lapides partem criticam iuxtaque functionalem
01/29/2026
Inquiry
+86
Click to upload file
Descarica
Obtine Applicatio Commerciale IEE-Business
Utiliza app IEE-Business ad inveniendum apparatus obtinendumque solutiones coniungendum cum peritis et participandum in collaboratione industriale ubique et semper propter totam supportionem tuorum projectorum electricitatis et negotiorum