• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Secondary System Grounding in Substations: IEC & GB/T Guide

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

1. What is Secondary Equipment Grounding?

Secondary equipment grounding refers to connecting the secondary equipment (such as relay protection and computer monitoring systems) in power plants and substations to the earth via dedicated conductors. Simply put, it establishes an equipotential bonding network, which is then connected to the station’s main grounding grid at multiple points.

2. Why Does Secondary Equipment Require Grounding?

Normal power-frequency currents and voltages during primary equipment operation, short-circuit fault currents and overvoltages, arc discharges from disconnector operations, and lightning disturbances during thunderstorms can all pose serious threats to the normal operation of secondary systems. These disturbances may lead to maloperation or failure to operate of protective relays, and in severe cases, even damage the protection devices. To ensure the safe and stable operation of the power system, secondary equipment must be properly grounded for protection.

grounding.jpg

3. Requirements for Secondary Equipment Grounding

According to the Code for Installation and Acceptance of Relay Protection and Secondary Circuits (GB/T 50976-2014), the equipotential grounding network shall meet the following requirements:

  • A copper grounding busbar with a cross-sectional area of not less than 100 mm² shall be installed at the bottom of each relay protection and control panel. This grounding busbar need not be insulated from the panel frame. The grounding terminals of devices mounted on the panel shall be connected to this busbar using multi-strand copper wire with a cross-sectional area of not less than 4 mm². The grounding busbar shall be connected to the main equipotential grounding network in the protection room via a copper cable with a cross-sectional area of not less than 50 mm².

  • In the cable compartment beneath the main control room and protection room, a dedicated copper bar (or cable) with a cross-sectional area of not less than 100 mm² shall be laid out along the direction of panel arrangement. The ends of this conductor shall be interconnected, and it shall be arranged in a "grid" or "mesh" pattern to form an equipotential grounding network within the protection room. This equipotential network shall be reliably connected at a single point to the main grounding grid using at least four copper bars (or cables), each with a cross-sectional area of not less than 50 mm².

  • The equipotential grounding network in the protection room shall be welded reliably to the outdoor equipotential network using a copper bar (or cable) with a cross-sectional area of not less than 100 mm².

  • A copper bar (or cable) with a cross-sectional area of not less than 100 mm² shall be laid along the trench for secondary cables, placed at the top of the cable tray, to form an outdoor equipotential bonding network. This copper conductor shall extend to the location of the line trap (wave trap) used for protection, and be reliably connected to the main grounding grid at a point 3 m to 5 m away from the primary grounding point of the line trap.

References

  • GB/T 50976-2014: Code for Installation and Acceptance of Relay Protection and Secondary Circuits

  • IEC 61000-5-2: Electromagnetic compatibility – Bonding and grounding

  • IEEE Std 80: Guide for Safety in AC Substation Grounding

Written by: Senior Protection Engineer | 12+ years in HV substation design (IEC/GB standards)

Give a tip and encourage the author!
Topics:
Recommended
Low-Voltage Distribution Lines and Power Distribution Requirements for Construction Sites
Low-Voltage Distribution Lines and Power Distribution Requirements for Construction Sites
Low-voltage distribution lines refer to the circuits that, through a distribution transformer, step down the high voltage of 10 kV to the 380/220 V level—i.e., the low-voltage lines running from the substation to the end-use equipment.Low-voltage distribution lines should be considered during the design phase of substation wiring configurations. In factories, for workshops with relatively high power demand, dedicated workshop substations are often installed, where transformers supply power direc
James
12/09/2025
Three-Phase SPD: Types, Wiring & Maintenance Guide
Three-Phase SPD: Types, Wiring & Maintenance Guide
1. What Is a Three-Phase Power Surge Protective Device (SPD)?A three-phase power surge protective device (SPD), also known as a three-phase lightning arrester, is specifically designed for three-phase AC power systems. Its primary function is to limit transient overvoltages caused by lightning strikes or switching operations in the power grid, thereby protecting downstream electrical equipment from damage. The SPD operates based on energy absorption and dissipation: when an overvoltage event occ
James
12/02/2025
Neutral Grounding Methods for Conventional-Speed Railway Power Systems
Neutral Grounding Methods for Conventional-Speed Railway Power Systems
Railway power systems primarily consist of automatic block signaling lines, through-feeder power lines, railway substations and distribution stations, and incoming power supply lines. They provide electricity to critical railway operations—including signaling, communications, rolling stock systems, station passenger handling, and maintenance facilities. As an integral part of the national power grid, railway power systems exhibit distinct characteristics of both electrical power engineering and
Echo
11/26/2025
What are the safety precautions and guidelines for using AC load banks?
What are the safety precautions and guidelines for using AC load banks?
AC load banks are electrical devices used to simulate real-world loads and are widely applied in power systems, communication systems, automation control systems, and other fields. To ensure personal and equipment safety during use, the following safety precautions and guidelines must be observed:Select an appropriate AC load bank: Choose an AC load bank that meets actual requirements, ensuring its capacity, voltage rating, and other parameters satisfy the intended application. Additionally, sel
Echo
11/06/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.