Types & Characteristics of Surge Arresters

05/17/2025

Introduction
Atmospheric lightning strikes on overhead lines, bare conductors, or metallic structures in outdoor substations, as well as overvoltages caused by switching operations of equipment and networks (switching overvoltages), pose significant hazards to electrical equipment. To protect equipment and facilitate insulation coordination, surge arresters (also known as "lightning arresters") must be installed at the incoming/outgoing points of overhead lines and in close proximity to transformers, due to their limited spatial protection zone.
Types and Characteristics of Surge Arresters
The most common surge arresters are non-linear metal oxide (MO) resistor type, housed in porcelain or silicone rubber. These are connected in parallel with the protected equipment and grounded via the earth grid. Another construction type uses silicon carbide (SiC) resistors (valve-type arresters), though these are less prevalent today.
Key Electrical Characteristics:
  • Resealing Voltage: The voltage across the arrester at which the follow current is reliably interrupted after sparkover.
  • Maximum Continuous Operating Voltage (MCOV): The highest power-frequency voltage (50 Hz or 60 Hz) that the arrester can withstand indefinitely.
  • Rated Short-Circuit Current: The maximum short-circuit current the arrester can safely handle.
  • Nominal Discharge Current: Common values include 5 kA, 10 kA, and 20 kA, indicating the arrester’s capacity to dissipate surge energy.
Surge arresters are connected between live conductors and ground. In installations with voltages above 52 kV, they may include discharge operation counters to monitor performance. An example of surge arresters is shown in Figure 1.
Additional Methods

In overhead lines and outdoor substations with voltages above 52 kV, it is common practice to install a lightning protection system comprising "lightning rods," "lightning aerial protection wires," or a combination of both.

LV Overvoltage Protection
Low Voltage (LV, where ) equipment, particularly electronic and informatics systems, is highly susceptible to severe damage from lightning discharges that propagate through cables or building structures.
To mitigate such risks, power surge protectors (SPDs) are typically installed in LV switchboards. These devices feature standard nominal discharge currents of 5 kA, 10 kA, and 20 kA, with some advanced models capable of handling 30–70 kA.
Similar to surge arresters, SPDs are connected between live conductors and ground, as illustrated in Figure 4. This configuration diverts surge currents away from sensitive equipment, ensuring protection against overvoltage events.

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

What is the difference between a dielectric and an insulator?
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
08/30/2025
Transformer Connection Sections
Transformer Connection Sections
Transformer Connection DesignationsThe transformer connection designation indicates the winding connection method and the phase relationship between the line voltages of the primary and secondary windings. It consists of two parts: letters and a number. The letters on the left denote the connection configurations of the high-voltage and low-voltage windings, while the number on the right is an integer from 0 to 11.This number represents the phase shift of the low-voltage winding's line voltage r
08/15/2025
Automatic Reclosing Scheme in Transmission Systems
Automatic Reclosing Scheme in Transmission Systems
Automatic Reclosing Scheme for Transmission SystemsThe automatic reclosing system is a series-connected network designed to reduce operating costs and enhance network reliability. Extra-high voltage (EHV) transmission lines are used to transmit large amounts of power, on the order of thousands of megawatts (MW), and therefore should not be interrupted at all costs. Although faults on these overhead lines are common, the power transmitted through them should not be interrupted for long periods du
08/07/2025
Transformer operation and maintenance
Transformer operation and maintenance
Transformer Operating TemperatureDuring operation, transformers generate copper losses and iron losses, both of which are converted into heat, causing the transformer’s temperature to rise. Most transformers in China use Class A insulation. Due to heat transfer characteristics, significant temperature differences exist between different components during operation: winding temperature is the highest, followed by the core, and then the temperature of the insulating oil (with upper-layer oil being
07/31/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!