• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Unsa ang mga Modo sa Automatic Reclosing ug Ilahang mga Katangian

Echo
Larangan: Pagsusi sa Transformer
China

Ang pag-reclose mahimong isulat sa tulo ka kategoriya: single-phase reclosing, three-phase reclosing, ug comprehensive reclosing.

Single-phase reclosing: Human sa pag-occur og single-phase fault sa line, gigamit ang single-phase reclosing. Kon ang reclosing naa sa permanenteng fault, gitripped ang tanang tulo ka phase ug walay uban pang attempt sa reclosing. Alang sa interphase faults, gitripped ang tanang tulo ka phase walay reclosing.

Three-phase reclosing: Bisag unsa ang klase sa fault, gitripped ang tanang tulo ka phase sumala sa three-phase reclosing. Kon ang reclosing naa sa permanenteng fault, gitripped ang tanang tulo ka phase usab.

Comprehensive reclosing: Alang sa single-phase faults, gigamit ang single-phase reclosing; alang sa interphase faults, gitripped ang tanang tulo ka phase sumala sa three-phase reclosing. Pagkahuman sa reclosing sa bisan unsang permanenteng fault, gitripped ang tanang tulo ka phase.

Single-Sided Power Source Three-Phase Single-Shot Reclosing

Karakteristik sa three-phase single-shot reclosing sa single-sided power source lines: 

  • Walay lisod nga consideron sa power source synchronization check.

  • Walay lisod nga distinguish sa klase sa fault o select sa faulted phases.

Operasyon proseso sa three-phase single-shot reclosing sa single-sided power source lines: 

  • Reclosing initiation: Ang reclosing magsugod human sa circuit breaker tripping (non-manual). 

  • Reclosing time delay: Human sa initiation, nag-delay ang timing elements bago mag-issue og closing pulse command. 

  • Single closing pulse: Human sa pag-issue og closing pulse, nagsugod ang timing para sa complete reclosing group reset (15-25 seconds), preventing multiple reclosing attempts. 

  • Blocking after manual tripping. 

  • Post-reclosing accelerated protection tripping: Alang sa permanenteng faults, coordinated sa protection systems.

Prinsipyo sa setting sa minimum reclosing time: 

  • Time required for feedback current from load motors to fault point after breaker tripping; time needed for fault arc extinction and insulation strength recovery of surrounding medium. 

  • Time required for insulation strength recovery around breaker contacts after arc extinction, refilling of oil/gas in arc-quenching chamber, and operating mechanism recovery. 

  • For reclosing via protective relay trip output, add circuit breaker tripping time. 

  • (Note: This appears to be a duplicate of 3.3 in the original text)

Baton sa operational experience sa China's power systems, ang minimum reclosing time mao ang 0.3-0.4 seconds.

Dual-Sided Power Source Three-Phase Single-Shot Reclosing

Karakteristik sa three-phase single-shot reclosing sa dual-sided power source lines:

  • Human sa fault tripping, adunay mga issues bahin sa whether ang duha ka power sources molabay pa o allowed ba ang non-synchronous reclosing. 

  • Kinahanglan siguraduhon nga ang circuit breakers sa duha ka gilid mi-tripped bago ang reclosing.

Pangutana reclosing methods alang sa dual-sided power source transmission lines: 

  • Fast reclosing: 

    • Circuit breakers capable of fast reclosing installed on both sides of the line. 

    • Full-line instantaneous protection installed on both sides, such as pilot protection. 

    • Inrush currents must remain within allowable limits for equipment and system impacts.

  • Non-synchronous reclosing: Closing under out-of-step conditions. All power system components will experience inrush current impacts.

  • Synchronism-check automatic reclosing: Closing only permitted after synchronism conditions are satisfied.

Requirements for synchronism-check reclosing:

  • System structure must ensure no loss of synchronism.

  • For double-circuit lines, check current flow on the other circuit.

  • Must verify actual synchronism between both power sources before reclosing.

Optimal reclosing time for dual-sided power source three-phase reclosing:

The optimal reclosing time is calculated and set based on fault conditions most severely affecting system stability. This ensures minimal additional impact on the system when reclosing onto severe permanent faults. While not optimal for other fault types, it provides sub-optimal but acceptable performance, avoiding worst-case scenarios.

Maghatag og tip ug pagsalig sa author

Gipareserbado

Mga Sayop ug Paghunahuna Sa Pag-atas Sa Iisa Ka Fasa Sa 10kV Distribution Lines
Mga Kinaiya ug mga Kaugalingong Detektor sa Single-Phase Ground Fault1. Mga Kinaiya sa Single-Phase Ground FaultMga Signal sa Central Alarm:Nagring ang warning bell, ug naglitaw ang indicator lamp nga gilabel “Ground Fault on [X] kV Bus Section [Y]”. Sa mga sistema nga may Petersen coil (arc suppression coil) nga naka-ground sa neutral point, ang “Petersen Coil Operated” nga indicator usab motindog.Mga Indikasyon sa Insulation Monitoring Voltmeter:Ang voltage sa nahisalaan nga phase mokubos (kon
01/30/2026
Neutral nga punto sa grounding operation mode alang sa 110kV~220kV power grid transformers
Ang pag-arrange sa mga modo ng operasyon ng grounding ng neutral point para sa 110kV~220kV power grid transformers dapat matugunan ang mga requirement ng insulation withstand sa mga neutral points ng transformer, ug usahay mao usab ang pagpanalipod sa zero-sequence impedance sa mga substation nga walay dako nga kausaban, samtang sigurado nga ang zero-sequence comprehensive impedance sa anumang punto sa short-circuit sa sistema dili mogawas sa tulo ka beses sa positive-sequence comprehensive impe
01/29/2026
Unsa ang Katuyohan sa Paggamit og Bato Gravel Pebbles ug Crushed Rock sa mga Substation?
Asa Kini ang mga Substation Usa ka Bato, Gravel, Pebbles, ug Crushed Rock?Sa mga substation, ang mga equipment sama sa power ug distribution transformers, transmission lines, voltage transformers, current transformers, ug disconnect switches nimo kinahanglan og grounding. Padulong sa grounding, karon atong ibutangan ang kahibawo bahin kon asa kini nga gravel ug crushed stone gamiton sa mga substation. Bisag ordinaryohan ra sila, importante kaayo ang papel nila sa seguridad ug pagkabana-bana.Sa d
01/29/2026
HECI GCB para sa Mga Generator – Fast SF₆ Circuit Breaker
1.Pagtulun-an ug Funcion1.1 Papeles sa Generator Circuit BreakerAng Generator Circuit Breaker (GCB) mao ang ma-kontrol nga punto sa pagkonektar nga nahimutang tali sa generator ug step-up transformer, nagserbi isip interface tali sa generator ug power grid. Ang iyang primary nga mga funcion kinahanglan ng adunay pag-isolate sa mga fault sa gilid sa generator ug pag-enable sa operasyonal nga kontrol sa panahon sa synchronization sa generator ug koneksyon sa grid. Ang operasyonal nga prinsipyong G
01/06/2026
Inquiry
+86
I-klik aron i-upload ang file
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo