• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Automatic Reclosing Modes: Single, Three-Phase & Composite

Edwiin
Edwiin
Field: Power switch
China

General Overview of Automatic Reclosing Modes

Typically, automatic reclosing devices are categorized into four modes: single-phase reclosing, three-phase reclosing, composite reclosing, and disabled reclosing. The appropriate mode can be selected based on load requirements and system conditions.

1. Single-Phase Reclosing

Most 110kV and higher transmission lines employ three-phase single-shot reclosing. According to operational experience, over 70% of short-circuit faults in high-voltage overhead lines within solidly grounded systems (110kV and above) are single-phase-to-ground faults. For 220kV and higher lines, due to larger phase spacing, single-phase ground faults can account for up to 90% of all faults. In such cases, disconnecting only the faulty phase and performing single-phase reclosing—while keeping the two healthy phases energized during the reclosing cycle—significantly improves power supply reliability and enhances the stability of parallel system operation. Therefore, single-phase reclosing is widely used in solidly grounded systems of 220kV and above.

It is generally applied to:

  • 220kV and below single-circuit tie lines;

  • Lines with weak interconnection between two power sources (including electromagnetic loop networks weakly connected via lower-voltage lines);

  • High-voltage outgoing lines from large steam turbine generator units.

2. Composite Reclosing

Composite reclosing applies single-phase reclosing for single-phase-to-ground faults and three-phase reclosing for phase-to-phase faults.

It is typically used on lines where three-phase reclosing is permitted, but single-phase reclosing offers better performance in maintaining system stability or restoring power supply.

3. Three-Phase Reclosing

Three-phase reclosing refers to a method where, regardless of whether a single-phase or phase-to-phase fault occurs on transmission or distribution lines, the protective relay trips all three phases of the circuit breaker simultaneously, followed by the automatic reclosing device re-closing all three phases at once.

This mode is generally used on lines with strong interconnection between a power source and a load, or between two robust power systems.

There are two main methods to initiate automatic reclosing:

I. Non-Correspondence Initiation (Position Mismatch Start)

Non-correspondence initiation occurs when the control status of the circuit breaker does not match its actual position.

The protection device uses a breaker position input (typically the "trip position" contact) to determine the breaker's status. If this input is closed, it indicates the breaker is open. If the control switch is in the "closed" position at this time, it implies the breaker was previously closed. This mismatch between control and actual position triggers the reclosing function—known as "position mismatch initiation."

This method can initiate reclosing both for protective relay trips and for unintended breaker tripping ("stealth tripping").

Advantages: Simple and reliable.
Disadvantages: May fail to operate if position relay contacts are faulty or auxiliary breaker contacts are defective.

II. Protection-Based Initiation

Protection-based initiation refers to starting the reclosing process after the protective relay issues a trip command.

After a protective trip, the device detects loss of line current and initiates reclosing. Typically, the protection device also includes a digital input labeled "external trip to initiate reclosing," allowing the second protection set in a dual-redundant configuration to trigger reclosing in the first set.

This method simplifies reclosing configuration, as the protection software determines a fixed reclosing mode, making it simple and reliable.

It can effectively correct false trips caused by protection maloperation, but cannot correct unintended "stealth tripping" caused by the circuit breaker itself.

III. Summary

Protection-based initiation and non-correspondence initiation serve as complementary methods. Modern microprocessor-based protection relays typically incorporate both methods. Some advanced designs omit external mismatch contacts and instead initiate reclosing directly when, in the absence of an external trip command (e.g., manual or remote trip), the device detects a change from "closed" to "open" position.

Give a tip and encourage the author!
Recommended
Why does a 2-in 4-out 10 kV solid-insulated ring main unit have two incoming feeder cabinets?
Why does a 2-in 4-out 10 kV solid-insulated ring main unit have two incoming feeder cabinets?
A "2-in 4-out 10 kVsolid-insulated ring main unit" refers to a specific type of ring main unit (RMU). The term "2-in 4-out" indicates that this RMU has two incoming feeders and four outgoing feeders.10 kVsolid-insulated ring main unit are equipment used in medium-voltage power distribution systems, primarily installed in substations, distribution stations, and transformer stations to distribute high-voltage power to low-voltage distribution networks. They generally consist of high-voltage incomi
Garca
12/10/2025
Low-Voltage Distribution Lines and Power Distribution Requirements for Construction Sites
Low-Voltage Distribution Lines and Power Distribution Requirements for Construction Sites
Low-voltage distribution lines refer to the circuits that, through a distribution transformer, step down the high voltage of 10 kV to the 380/220 V level—i.e., the low-voltage lines running from the substation to the end-use equipment.Low-voltage distribution lines should be considered during the design phase of substation wiring configurations. In factories, for workshops with relatively high power demand, dedicated workshop substations are often installed, where transformers supply power direc
James
12/09/2025
What lightning protection measures are used for H61 distribution transformers?
What lightning protection measures are used for H61 distribution transformers?
What lightning protection measures are used for H61 distribution transformers?A surge arrester should be installed on the high-voltage side of the H61 distribution transformer. According to SDJ7–79 "Technical Code for Design of Overvoltage Protection of Electric Power Equipment," the high-voltage side of an H61 distribution transformer should generally be protected by a surge arrester. The grounding conductor of the arrester, the neutral point on the low-voltage side of the transformer, and the
Felix Spark
12/08/2025
How to Implement Transformer Gap Protection & Standard Shutdown Steps
How to Implement Transformer Gap Protection & Standard Shutdown Steps
How to Implement Transformer Neutral Grounding Gap Protection Measures?In a certain power grid, when a single-phase ground fault occurs on a power supply line, both the transformer neutral grounding gap protection and the power supply line protection operate simultaneously, causing an outage of an otherwise healthy transformer. The main reason is that during a system single-phase ground fault, the zero-sequence overvoltage causes the transformer neutral grounding gap to break down. The resulting
Noah
12/05/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.