Transformers Fire Protection System – Causes, Types & Requirements

05/17/2025

Causes of Transformer Fires
Transformers can catch fire due to several critical issues, including excessive overheating, severe short circuits, faults in the insulating oil, and lightning strikes. While transformer fires are relatively uncommon, their consequences can be devastating. As depicted in the figure below, a transformer engulfed in fire is often irreparably damaged within minutes. However, it is crucial to address the potential impact of such fires on adjacent equipment and structures, as proper mitigation measures can limit collateral damage.
Fire Risks and Protection for Transformers
An uncontained transformer fire can cause extensive damage and lead to prolonged, unscheduled power outages. For high-rated power transformers with voltages exceeding 123 kV, it is standard practice to install dedicated fire protection systems. One common solution is fixed water spray systems, often referred to as transformer "deluge" or "fire water" systems, as illustrated in Figure 1.
These systems are designed to rapidly suppress fires by dousing the transformer with a controlled, high-volume water spray, mitigating the risk of fire spreading to adjacent equipment or structures and minimizing downtime.
Transformer Fire Protection Systems
This system is activated by flame detectors if the transformer is installed outdoors, or by smoke detectors if indoors.
Types of Transformer Fire Protection Systems
Transformer fire protection systems can be categorized into:
Water-Based and Mist Systems
  • Components: Fire pumps, fixed water spray systems/nozzles, valves, valve components, and piping.
  • Function: Rapidly suppress fires by dousing the transformer with water, leveraging high-pressure sprays or fine mists to cool surfaces and smother flames.

Fire Detection Systems

  • Components: Fire detectors (thermal, smoke, or flame sensors), control panels, and cabling.
  • Function: Detect fire hazards early and trigger suppression systems or alarms to minimize response time.
Mitigation Considerations
Fire suppression may be less critical if:
  • The transformer is remotely located from structures and other equipment.
  • Burning oil can be contained effectively (e.g., via fire-resistant barriers or drainage systems).
However, in most cases, protecting plant structures, adjacent equipment, and personnel necessitates fire suppression measures.
Alternative Solutions
Using less-flammable insulating fluids (e.g., high flashpoint oils or synthetic esters) can reduce fire risks and may eliminate the need for active suppression systems, making them a viable alternative in some installations.
Requirements for Transformer Fire Protection
The following are the fundamental principles for transformer fire protection:
New Facilities with Mineral-Oil-Filled Transformers
  • New installations featuring large mineral-oil-filled transformers located near plant structures or other equipment must incorporate active fire suppression systems to safeguard the structure, adjacent equipment, and the environment.
  • Additionally, they require properly designed containment systems (e.g., oil retention dikes) to prevent environmental contamination from spilled oil.
  • For new facilities—and where practical in existing plants—mineral-oil-filled transformers should be sited away from buildings, other equipment, and waterways to minimize fire and environmental risks. In such cases, active fire suppression may be unnecessary if separation distances and other risk mitigation measures are sufficient.

Existing Facilities

  • Functional fire suppression systems in operation should continue to protect plant structures and equipment but must be periodically reviewed for adequacy and compliance with current codes and standards.
  • Inactive or non-functional fire suppression systems must be assessed for compliance with modern standards and restored to operational status where required.
  • Existing facilities without fire suppression systems must install them where necessary to protect critical structures or equipment, as determined by risk assessments.

Transformer Maintenance and Assessment

  • Transformers require periodic condition assessments in addition to routine inspections, testing, and maintenance. Units with low condition indices should be prioritized for rehabilitation or replacement to reduce failure risks.

Fire Containment Structures

  • Fire walls or barriers should be installed between adjacent transformers, between transformers and plant structures, between single-phase units, or between transformers and other equipment where feasible. These barriers limit fire and explosion spread, minimizing collateral damage.

System Operation and Compliance

  • Fire suppression systems must be regularly operated, maintained, and tested to ensure reliability during emergencies.
  • Oil containment and oil-water separation structures (e.g., spill berms, interceptor tanks) must comply with all relevant environmental laws, regulations, and industry standards to prevent pollution.

Access and Public Safety

  • Access to transformer areas must be restricted to authorized personnel only. Measures should be taken to physically limit public proximity to transformers, reducing the risk of injury or unauthorized interference.
  • All fire protection and containment measures must align with applicable environmental laws to prevent regulatory non-compliance and ecological harm.
By adhering to these principles, facilities can effectively mitigate fire risks, protect infrastructure, safeguard personnel, and minimize environmental impact from transformer incidents.

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

What is the difference between a dielectric and an insulator?
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
08/30/2025
Transformer Connection Sections
Transformer Connection Sections
Transformer Connection DesignationsThe transformer connection designation indicates the winding connection method and the phase relationship between the line voltages of the primary and secondary windings. It consists of two parts: letters and a number. The letters on the left denote the connection configurations of the high-voltage and low-voltage windings, while the number on the right is an integer from 0 to 11.This number represents the phase shift of the low-voltage winding's line voltage r
08/15/2025
Automatic Reclosing Scheme in Transmission Systems
Automatic Reclosing Scheme in Transmission Systems
Automatic Reclosing Scheme for Transmission SystemsThe automatic reclosing system is a series-connected network designed to reduce operating costs and enhance network reliability. Extra-high voltage (EHV) transmission lines are used to transmit large amounts of power, on the order of thousands of megawatts (MW), and therefore should not be interrupted at all costs. Although faults on these overhead lines are common, the power transmitted through them should not be interrupted for long periods du
08/07/2025
Transformer operation and maintenance
Transformer operation and maintenance
Transformer Operating TemperatureDuring operation, transformers generate copper losses and iron losses, both of which are converted into heat, causing the transformer’s temperature to rise. Most transformers in China use Class A insulation. Due to heat transfer characteristics, significant temperature differences exist between different components during operation: winding temperature is the highest, followed by the core, and then the temperature of the insulating oil (with upper-layer oil being
07/31/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!