Quid est GIS (Gas-Insulated Switchgear)? Characteristica, Species, et Applicationes

Garca
Campus: Design & Manutentio
Congo

Quid est GIS apparatus?

GIS est sigla Latina pro Gas Insulated Switchgear, quae in lingua Sinica integre vertitur ut Gas-Insulated Metal-Enclosed Switchgear. Haec saepe adhibet sulfur hexafluoride (SF6) gas ut medium insulantem et arc-quenching. GIS per optimam designacionem integrat principia primaria substationis - praeter transformator - sicut circuit breakers (CB), disconnectors (DS), earthing switches (ES/FES), busbars (BUS), current transformers (CT), voltage transformers (VT), surge arresters (LA), cable terminations, et incoming/outgoing line bushings in unum clausum metallicum corpus, formans unitatem integratam.

Nunc, scala tensionis GIS apparatorum ampla est, ab 72.5 kV usque ad 1200 kV.

Characteres GIS Apparatorum

Gas SF6 habet excellentem dielectricam potentiam, arc-quenching capacitate, et chemica stabilitate. Propter haec, GIS apparatus characterizatur parvo volumine, minima superficie, alta operationis fide, longis intervallis maintenance, et fortis resistencia ad electromagneticam interpellationem. Praeterea, propter eius clausam structuram, interna componentia sunt tuta ab externis factoribus (sicut pulvis, umiditas, et salina nebula), assecurantes stabiliter operationem, parvam electromagneticam sonitum, et minorem onus maintenance.

Tamen, dielectrica performantia gas SF6 valde sensibilis est ad uniformitatem electrici campi. Interna defecta sicut burrs conductorum, metallicorum particula, vel deficiens constructio facile ducunt ad partial discharge vel etiam insulation breakdown. Praeterea, clausa structura GIS facit internam diagnosticationem et maintenance complexam, cum limitatis diagnosticis instrumentis. Mala clausura potest etiam ducere ad aquae ingressum vel gas effluvium, compromittendo securitatem apparatorum.

Species Contactuum Electricorum in GIS Conduction Circuits

Conduction circuit in GIS constat ex multis componentibus et potest classificari in tres species secundum contactum methodum:

  • Contactus Fixus: Electrica conexiones securatae per bolts vel alia fastigia, sine relativa motione durante operationem, sicut conexus inter busbar et basin-type insulator.

  • Contactus Separabilis: Contactus electrici qui possunt aperiri vel claudere durante operationem, sicut contactus in circuit breakers et disconnectors.

  • Contactus Glissans vel Rotans: Contactus qui permittunt relativam glissationem vel rotationem inter contactum superficies sed non possunt separari, sicut intermedii contactus in switchgear.

Introductio ad HGIS

Praeter GIS, est alia species appellata HGIS (Hybrid Gas-Insulated Switchgear), hibrida gas-insulated switchgear. HGIS non includit componentia sicut busbars, busbar voltage transformers, vel busbar surge arresters, resultans in simpliciore structura. Id aptum est pro asperis ambientibus vel locis cum spatii restrictionibus et offert maiorem flexibilitatem in dispositione.

Classificatio GIS Apparatorum

  • Per Locum Installationis: Species interior et exterior.

  • Per Structuram: Uniphasis unius clausi et triphasica communis clausi. Generaliter, busbars ad tensionis niveles 110 kV et infra possunt adoptare designatum triphasica communis clausi, dum tensionis niveles 220 kV et supra saepe adhibent uniphasis unius clausi designatum ad reducendum periculum interphase faults.

Principia Operativi Basi

  • Sub normalibus conditionibus, GIS circuit breakers et disconnectors principaliter operantur remote. Selector switch "Remote/Local" debet esse positus in "Remote" positione.

  • Earthing switches possunt operari tantum localiter. Durante operatione, selector switch "Disconnector/Earthing Switch" debet commutari in "Local" positionem.

  • Omnes operationes debent sequi programmata procedura. Interlock release switch in control cabinet debet permanere in "Interlock" positione. Unlocking key, simul cum microcomputer anti-misoperation unlocking key, debet esse sigillata et strictim administrata secundum regulas.

Requirimenta Operationis Basi

  • Pro interioribus SF6 equipment room frequentibus accessu personarum, ventilatio debet fieri saltem semel per shift non minus quam 15 minutis, cum aer exchange volume superante 3-5 times room volumen. Aer exhaust outlets debent esse locati in parte inferiori room. Pro areis non frequentibus intritu, ventilatio 15 minutis est requirita ante introitum.

  • Durante operatione, induxit voltage in accessibilibus partibus GIS enclosure et structure non debet superare 36 V sub normalibus conditionibus.

  • Limites Temperaturae Incrementi:

    • Faciliter accessibiles partes: non plus quam 30 K;

    • Partes faciliter tactiles sed non contactae durante operatione: non plus quam 40 K;

    • Raro accessibiles singulares partes: non plus quam 65 K.

  • SF6 switchgear debet inspectari saltem semel cotidie. Pro unmanned substationibus, inspectiones debent fieri secundum stabilitas proceduras. Inspectiones debent concentrari in visualibus inspectionibus pro abnormalitatibus sicut insolitus sonus, effluvia, vel abnormalis indicationes, cum recordis retinendis.

Donum da et auctorem hortare

Suggestus

HECI GCB for Generators – Cepus SF₆ Circuit Breaker
1. Definitio et Functio1.1 Munus Interruptoris Circuiti GeneratorisInterruptor Circuitus Generatoris (GCB) est punctum disiunctionis controllabile situatum inter generator et transformator incrementalis, servans ut interficium inter generator et rete electricitatis. Principales eius functiones includunt isolationem defectuum lateris generatoris et facilitationem controlis operationis durante synchronizatione generatoris et connectione ad rete. Principium operativum GCB non differt significanter
01/06/2026
Principia Design pro Transformeribus Distributionis in Columna Fixis
Principia Design Pro Distributionibus Transformerum in Polum Fixis(1) Principia Locorum et DispositionumPlataformae transformerum in polum fixarum debent collocari iuxta centrum oneris aut prope onera critica, secundum principium “parva capacitas, plura loca” ad facilitatem substitutionis et maintenance. Ad distributionem electricitatis domesticam, transformatores triphasici possunt instaurari iuxta necessitatem praesentem et projectiones futurorum incrementorum.(2) Selectio Capacitatis pro Tran
12/25/2025
Solutio Controlis Stridoris Transformatorum pro Diversis Installationibus
1. Mitigatio sonoris pro camera transformatoris independente in superficie terraeStrategia mitigationis:Primum, fac inspectionem et maintenance cum potestate interrupta, includens renovationem olei insulantis vetustatis, examinationem et consolidationem omnium fixorum, et mundationem pulvis a unitate.Deinde, reficere fundamentum transformatoris vel installare dispositiva isolationis vibrationis—ut gommae vel isolatores springalis—selecta secundum gravitatem vibrationis.Tandem, fortificare insula
12/25/2025
Rockwill Transitus Testum Defectus Terreni Unipolaris pro Terminale Sagaciter Distributivum
Rockwill Electric Co., Ltd. successerunt in experimento defectus uniphasis ad terram peracto ab ramo Wuhan Institutum Sinicum Investigativum Electricitatis pro terminale aliminatorio DA-F200-302 et interruptoribus circuiti montati in columna ZW20-12/T630-20 et ZW68-12/T630-20 integratis primario-secundo, obtinendo raportum experimenti qualificatum officiale. Hoc successus indicat Rockwill Electric ut ducem in technologia delectionis defectus uniphasis ad terram in rete distributionis.Terminale a
12/25/2025
Inquiry
+86
Click to upload file

IEE Business will not sell or share your personal information.

Descarica
Obtine Applicatio Commerciale IEE-Business
Utiliza app IEE-Business ad inveniendum apparatus obtinendumque solutiones coniungendum cum peritis et participandum in collaboratione industriale ubique et semper propter totam supportionem tuorum projectorum electricitatis et negotiorum