• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Unsa ang GIS (Gas-Insulated Switchgear)? Kalihukan, Mga Tipo, ug Paggamit

Garca
Larangan: Diseño ug Pagsulay
Congo

Unsa ang GIS Equipment?

Ang GIS mao ang English abbreviation sa Gas Insulated Switchgear, nga gipasabot sa Chinese isip Gas-Insulated Metal-Enclosed Switchgear. Kasagaran kini nagamit og sulfur hexafluoride (SF6) gas isip insulating ug arc-quenching medium. Ang GIS giintegro, pinaagi sa optimized design, ang primary equipment sa substation—wala na ang transformer— sama sa circuit breakers (CB), disconnectors (DS), earthing switches (ES/FES), busbars (BUS), current transformers (CT), voltage transformers (VT), surge arresters (LA), cable terminations, ug incoming/outgoing line bushings—isip usa ka sealed metallic enclosure, nahimong usa ka integrated unit.

Karon, ang range sa voltage rating sa GIS equipment maoy extensive, gikan sa 72.5 kV hangtod sa 1200 kV.

Characteristics of GIS Equipment

Ang SF6 gas adunay excellent dielectric strength, arc-quenching capability, ug chemical stability. Taliwala niini, ang GIS equipment adunay compact size, minimal footprint, high operational reliability, long maintenance intervals, ug strong electromagnetic interference resistance. Bisan pa, tungod sa iyang fully enclosed structure, ang mga internal components protektado gikan sa external environmental factors ( sama sa dust, moisture, ug salt fog), sigurado ang stable operation, low electromagnetic noise, ug reduced maintenance workload.

Pero, ang dielectric performance sa SF6 gas dako kaayo ang sensitiveness sa electric field uniformity. Ang mga internal defects sama sa conductor burrs, metallic particles, o assembly flaws mahimo kasagaran mog resulta og partial discharge o even insulation breakdown. Giyahan, ang sealed structure sa GIS komplikado ang internal fault diagnosis ug maintenance, limitado ang diagnostic tools. Ang poor sealing mahimo usab mag resulta og water ingress o gas leakage, kompromiso ang equipment safety.

Types of Electrical Contacts in GIS Conduction Circuits

Ang conduction circuit sa GIS gisangpot sa daghang components ug makaklasiha ngadto sa tulo ka types batasan sa contact method:

  • Fixed Contact: Electrical connections secured by bolts or other fasteners, with no relative movement during operation, such as the connection between a busbar and a basin-type insulator.

  • Separable Contact: Electrical contacts that can be opened or closed during operation, such as the contacts in circuit breakers and disconnectors.

  • Sliding or Rolling Contact: Contacts that allow relative sliding or rolling between contact surfaces but cannot be separated, such as intermediate contacts in switchgear.

Introduction to HGIS

Aside from GIS, there is another type called HGIS (Hybrid Gas-Insulated Switchgear), a hybrid gas-insulated switchgear. HGIS does not include components such as busbars, busbar voltage transformers, or busbar surge arresters, resulting in a simpler structure. It is suitable for harsh environments or locations with space constraints and offers greater flexibility in layout.

Classification of GIS Equipment

  • By Installation Location: Indoor and outdoor types.

  • By Structure: Single-phase single-enclosure and three-phase common-enclosure. Generally, busbars at voltage levels of 110 kV and below can adopt the three-phase common-enclosure design, while voltage levels of 220 kV and above typically use the single-phase single-enclosure design to reduce the risk of phase-to-phase faults.

Basic Operating Principles

  • Under normal conditions, GIS circuit breakers and disconnectors are primarily operated remotely. The "Remote/Local" selector switch should be set to the "Remote" position.

  • Earthing switches can only be operated locally. During operation, the "Disconnector/Earthing Switch" selector switch must be switched to the "Local" position.

  • All operations must follow programmed procedures. The "Interlock Release Switch" on the control cabinet must remain in the "Interlock" position. The unlocking key, along with the microcomputer anti-misoperation unlocking key, must be sealed and managed strictly according to regulations.

Basic Operational Requirements

  • For indoor SF6 equipment rooms frequently accessed by personnel, ventilation should be performed at least once per shift for no less than 15 minutes, with air exchange volume exceeding 3–5 times the room volume. Air exhaust outlets should be located at the lower part of the room. For areas not frequently entered, ventilation for 15 minutes is required before entry.

  • During operation, the induced voltage on accessible parts of the GIS enclosure and structure should not exceed 36 V under normal conditions.

  • Temperature Rise Limits:

    • Easily accessible parts: no more than 30 K;

    • Parts easily touched but not contacted during operation: no more than 40 K;

    • Rarely accessible individual parts: no more than 65 K.

  • SF6 switchgear should be inspected at least once daily. For unattended substations, inspections should be conducted according to established procedures. Inspections should focus on visual checks for abnormalities such as unusual sounds, leaks, or abnormal indications, with records maintained accordingly.

Maghatag og tip ug pagsalig sa author

Gipareserbado

HECI GCB para sa Mga Generator – Fast SF₆ Circuit Breaker
1.Pagtulun-an ug Funcion1.1 Papeles sa Generator Circuit BreakerAng Generator Circuit Breaker (GCB) mao ang ma-kontrol nga punto sa pagkonektar nga nahimutang tali sa generator ug step-up transformer, nagserbi isip interface tali sa generator ug power grid. Ang iyang primary nga mga funcion kinahanglan ng adunay pag-isolate sa mga fault sa gilid sa generator ug pag-enable sa operasyonal nga kontrol sa panahon sa synchronization sa generator ug koneksyon sa grid. Ang operasyonal nga prinsipyong G
01/06/2026
Mga Prinsipyo sa Pagdisenyo alang sa Pole-Mounted Distribution Transformers
Mga Prinsipyo sa Disenyo alang sa Mga Transformer sa Distribusyon nga Gitindog sa Poste(1) Mga Prinsipyo sa Lokasyon ug LayoutAng mga plataporma sa transformer nga gitindog sa poste kinahanglan ibutang duol sa sentro sa karga o duol sa mga importante nga karga, sumala sa prinsipyo sa “gamay nga kapasidad, daghang lokasyon” aron mapadali ang pag-ilis ug pagmintinar sa ekipo. Alang sa suplay sa kuryente sa panimalay, ang mga three-phase nga transformer mahimong i-instalar sa duol base sa kasamtang
12/25/2025
Solusyon sa Pagkontrol sa Ingong sa Transformer para sa Mga Dili Parehas nga Pagsulay
1.Pag- kontrol sa Bulakbo para sa mga Ground-Level Independent Transformer RoomsStratehiya sa Pag- kontrol:Una, gihahayag ang pag-inspekta ug pag-maintain sa transformer nga walay kuryente, kasama ang pag-bagong insulating oil nga lumad, pag-suri ug pag-pigsa sa tanang fasteners, ug pag-limpyo sa dust mula sa unit.Pangalawa, palig-onon ang foundation sa transformer o i-install ang mga vibration isolation devices—tulad ng rubber pads o spring isolators—na pinili batas sa grabe sa vibration.Finalm
12/25/2025
Rockwill Nagsalang sa Test sa Single-Phase Ground Fault Alang sa Smart Feeder Terminal
Ang Rockwill Electric Co., Ltd. naka-approve na sa aktwal nga scenario sa single-phase-to-ground fault test gisagol sa Wuhan Branch sa China Electric Power Research Institute alang sa ilang DA-F200-302 hood-type feeder terminal ug integrated primary-secondary pole-mounted circuit breakers—ZW20-12/T630-20 ug ZW68-12/T630-20—nagpadala og opisyal nga qualified test report. Kini nga achievement marka ang Rockwill Electric isip usa ka lider sa teknolohiya sa pagpili sa single-phase ground fault detec
12/25/2025
Inquiry
+86
I-klik aron i-upload ang file

IEE Business will not sell or share your personal information.

Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo