• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Unsa ang GIS (Gas-Insulated Switchgear)? Kalihukan, Mga Tipo, ug Paggamit

Garca
Larangan: Diseño ug Pagsulay
Congo

Unsa ang GIS Equipment?

Ang GIS mao ang English abbreviation sa Gas Insulated Switchgear, nga gipasabot sa Chinese isip Gas-Insulated Metal-Enclosed Switchgear. Kasagaran kini nagamit og sulfur hexafluoride (SF6) gas isip insulating ug arc-quenching medium. Ang GIS giintegro, pinaagi sa optimized design, ang primary equipment sa substation—wala na ang transformer— sama sa circuit breakers (CB), disconnectors (DS), earthing switches (ES/FES), busbars (BUS), current transformers (CT), voltage transformers (VT), surge arresters (LA), cable terminations, ug incoming/outgoing line bushings—isip usa ka sealed metallic enclosure, nahimong usa ka integrated unit.

Karon, ang range sa voltage rating sa GIS equipment maoy extensive, gikan sa 72.5 kV hangtod sa 1200 kV.

Characteristics of GIS Equipment

Ang SF6 gas adunay excellent dielectric strength, arc-quenching capability, ug chemical stability. Taliwala niini, ang GIS equipment adunay compact size, minimal footprint, high operational reliability, long maintenance intervals, ug strong electromagnetic interference resistance. Bisan pa, tungod sa iyang fully enclosed structure, ang mga internal components protektado gikan sa external environmental factors ( sama sa dust, moisture, ug salt fog), sigurado ang stable operation, low electromagnetic noise, ug reduced maintenance workload.

Pero, ang dielectric performance sa SF6 gas dako kaayo ang sensitiveness sa electric field uniformity. Ang mga internal defects sama sa conductor burrs, metallic particles, o assembly flaws mahimo kasagaran mog resulta og partial discharge o even insulation breakdown. Giyahan, ang sealed structure sa GIS komplikado ang internal fault diagnosis ug maintenance, limitado ang diagnostic tools. Ang poor sealing mahimo usab mag resulta og water ingress o gas leakage, kompromiso ang equipment safety.

Types of Electrical Contacts in GIS Conduction Circuits

Ang conduction circuit sa GIS gisangpot sa daghang components ug makaklasiha ngadto sa tulo ka types batasan sa contact method:

  • Fixed Contact: Electrical connections secured by bolts or other fasteners, with no relative movement during operation, such as the connection between a busbar and a basin-type insulator.

  • Separable Contact: Electrical contacts that can be opened or closed during operation, such as the contacts in circuit breakers and disconnectors.

  • Sliding or Rolling Contact: Contacts that allow relative sliding or rolling between contact surfaces but cannot be separated, such as intermediate contacts in switchgear.

Introduction to HGIS

Aside from GIS, there is another type called HGIS (Hybrid Gas-Insulated Switchgear), a hybrid gas-insulated switchgear. HGIS does not include components such as busbars, busbar voltage transformers, or busbar surge arresters, resulting in a simpler structure. It is suitable for harsh environments or locations with space constraints and offers greater flexibility in layout.

Classification of GIS Equipment

  • By Installation Location: Indoor and outdoor types.

  • By Structure: Single-phase single-enclosure and three-phase common-enclosure. Generally, busbars at voltage levels of 110 kV and below can adopt the three-phase common-enclosure design, while voltage levels of 220 kV and above typically use the single-phase single-enclosure design to reduce the risk of phase-to-phase faults.

Basic Operating Principles

  • Under normal conditions, GIS circuit breakers and disconnectors are primarily operated remotely. The "Remote/Local" selector switch should be set to the "Remote" position.

  • Earthing switches can only be operated locally. During operation, the "Disconnector/Earthing Switch" selector switch must be switched to the "Local" position.

  • All operations must follow programmed procedures. The "Interlock Release Switch" on the control cabinet must remain in the "Interlock" position. The unlocking key, along with the microcomputer anti-misoperation unlocking key, must be sealed and managed strictly according to regulations.

Basic Operational Requirements

  • For indoor SF6 equipment rooms frequently accessed by personnel, ventilation should be performed at least once per shift for no less than 15 minutes, with air exchange volume exceeding 3–5 times the room volume. Air exhaust outlets should be located at the lower part of the room. For areas not frequently entered, ventilation for 15 minutes is required before entry.

  • During operation, the induced voltage on accessible parts of the GIS enclosure and structure should not exceed 36 V under normal conditions.

  • Temperature Rise Limits:

    • Easily accessible parts: no more than 30 K;

    • Parts easily touched but not contacted during operation: no more than 40 K;

    • Rarely accessible individual parts: no more than 65 K.

  • SF6 switchgear should be inspected at least once daily. For unattended substations, inspections should be conducted according to established procedures. Inspections should focus on visual checks for abnormalities such as unusual sounds, leaks, or abnormal indications, with records maintained accordingly.

Maghatag og tip ug pagsalig sa author

Gipareserbado

Pangunahon nga Transformer Accidents ug Light Gas Operation Issues
1. Talaan sa Pagkamalasakit (Marso 19, 2019)Sa 16:13 sa Marso 19, 2019, ang background monitoring nagreport og light gas action sa No. 3 main transformer. Sumala sa Code for Operation of Power Transformers (DL/T572-2010), ang mga tawo sa operation and maintenance (O&M) nagsagol sa kondisyon sa No. 3 main transformer sa dapit.Konfirmasyon sa dapit: Ang WBH non-electrical protection panel sa No. 3 main transformer nagreport og Phase B light gas action sa transformer body, ug ang reset wala mae
02/05/2026
Mga Sayop ug Paghunahuna Sa Pag-atas Sa Iisa Ka Fasa Sa 10kV Distribution Lines
Mga Kinaiya ug mga Kaugalingong Detektor sa Single-Phase Ground Fault1. Mga Kinaiya sa Single-Phase Ground FaultMga Signal sa Central Alarm:Nagring ang warning bell, ug naglitaw ang indicator lamp nga gilabel “Ground Fault on [X] kV Bus Section [Y]”. Sa mga sistema nga may Petersen coil (arc suppression coil) nga naka-ground sa neutral point, ang “Petersen Coil Operated” nga indicator usab motindog.Mga Indikasyon sa Insulation Monitoring Voltmeter:Ang voltage sa nahisalaan nga phase mokubos (kon
01/30/2026
Neutral nga punto sa grounding operation mode alang sa 110kV~220kV power grid transformers
Ang pag-arrange sa mga modo ng operasyon ng grounding ng neutral point para sa 110kV~220kV power grid transformers dapat matugunan ang mga requirement ng insulation withstand sa mga neutral points ng transformer, ug usahay mao usab ang pagpanalipod sa zero-sequence impedance sa mga substation nga walay dako nga kausaban, samtang sigurado nga ang zero-sequence comprehensive impedance sa anumang punto sa short-circuit sa sistema dili mogawas sa tulo ka beses sa positive-sequence comprehensive impe
01/29/2026
Unsa ang Katuyohan sa Paggamit og Bato Gravel Pebbles ug Crushed Rock sa mga Substation?
Asa Kini ang mga Substation Usa ka Bato, Gravel, Pebbles, ug Crushed Rock?Sa mga substation, ang mga equipment sama sa power ug distribution transformers, transmission lines, voltage transformers, current transformers, ug disconnect switches nimo kinahanglan og grounding. Padulong sa grounding, karon atong ibutangan ang kahibawo bahin kon asa kini nga gravel ug crushed stone gamiton sa mga substation. Bisag ordinaryohan ra sila, importante kaayo ang papel nila sa seguridad ug pagkabana-bana.Sa d
01/29/2026
Inquiry
+86
I-klik aron i-upload ang file
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo