• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Unsa ang GIS (Gas-Insulated Switchgear)? Kalihukan, Mga Tipo, ug Paggamit

Garca
Garca
Larangan: Diseño ug Pagsulay
Congo

Unsa ang GIS Equipment?

Ang GIS mao ang English abbreviation sa Gas Insulated Switchgear, nga gipasabot sa Chinese isip Gas-Insulated Metal-Enclosed Switchgear. Kasagaran kini nagamit og sulfur hexafluoride (SF6) gas isip insulating ug arc-quenching medium. Ang GIS giintegro, pinaagi sa optimized design, ang primary equipment sa substation—wala na ang transformer— sama sa circuit breakers (CB), disconnectors (DS), earthing switches (ES/FES), busbars (BUS), current transformers (CT), voltage transformers (VT), surge arresters (LA), cable terminations, ug incoming/outgoing line bushings—isip usa ka sealed metallic enclosure, nahimong usa ka integrated unit.

Karon, ang range sa voltage rating sa GIS equipment maoy extensive, gikan sa 72.5 kV hangtod sa 1200 kV.

Characteristics of GIS Equipment

Ang SF6 gas adunay excellent dielectric strength, arc-quenching capability, ug chemical stability. Taliwala niini, ang GIS equipment adunay compact size, minimal footprint, high operational reliability, long maintenance intervals, ug strong electromagnetic interference resistance. Bisan pa, tungod sa iyang fully enclosed structure, ang mga internal components protektado gikan sa external environmental factors ( sama sa dust, moisture, ug salt fog), sigurado ang stable operation, low electromagnetic noise, ug reduced maintenance workload.

Pero, ang dielectric performance sa SF6 gas dako kaayo ang sensitiveness sa electric field uniformity. Ang mga internal defects sama sa conductor burrs, metallic particles, o assembly flaws mahimo kasagaran mog resulta og partial discharge o even insulation breakdown. Giyahan, ang sealed structure sa GIS komplikado ang internal fault diagnosis ug maintenance, limitado ang diagnostic tools. Ang poor sealing mahimo usab mag resulta og water ingress o gas leakage, kompromiso ang equipment safety.

Types of Electrical Contacts in GIS Conduction Circuits

Ang conduction circuit sa GIS gisangpot sa daghang components ug makaklasiha ngadto sa tulo ka types batasan sa contact method:

  • Fixed Contact: Electrical connections secured by bolts or other fasteners, with no relative movement during operation, such as the connection between a busbar and a basin-type insulator.

  • Separable Contact: Electrical contacts that can be opened or closed during operation, such as the contacts in circuit breakers and disconnectors.

  • Sliding or Rolling Contact: Contacts that allow relative sliding or rolling between contact surfaces but cannot be separated, such as intermediate contacts in switchgear.

Introduction to HGIS

Aside from GIS, there is another type called HGIS (Hybrid Gas-Insulated Switchgear), a hybrid gas-insulated switchgear. HGIS does not include components such as busbars, busbar voltage transformers, or busbar surge arresters, resulting in a simpler structure. It is suitable for harsh environments or locations with space constraints and offers greater flexibility in layout.

Classification of GIS Equipment

  • By Installation Location: Indoor and outdoor types.

  • By Structure: Single-phase single-enclosure and three-phase common-enclosure. Generally, busbars at voltage levels of 110 kV and below can adopt the three-phase common-enclosure design, while voltage levels of 220 kV and above typically use the single-phase single-enclosure design to reduce the risk of phase-to-phase faults.

Basic Operating Principles

  • Under normal conditions, GIS circuit breakers and disconnectors are primarily operated remotely. The "Remote/Local" selector switch should be set to the "Remote" position.

  • Earthing switches can only be operated locally. During operation, the "Disconnector/Earthing Switch" selector switch must be switched to the "Local" position.

  • All operations must follow programmed procedures. The "Interlock Release Switch" on the control cabinet must remain in the "Interlock" position. The unlocking key, along with the microcomputer anti-misoperation unlocking key, must be sealed and managed strictly according to regulations.

Basic Operational Requirements

  • For indoor SF6 equipment rooms frequently accessed by personnel, ventilation should be performed at least once per shift for no less than 15 minutes, with air exchange volume exceeding 3–5 times the room volume. Air exhaust outlets should be located at the lower part of the room. For areas not frequently entered, ventilation for 15 minutes is required before entry.

  • During operation, the induced voltage on accessible parts of the GIS enclosure and structure should not exceed 36 V under normal conditions.

  • Temperature Rise Limits:

    • Easily accessible parts: no more than 30 K;

    • Parts easily touched but not contacted during operation: no more than 40 K;

    • Rarely accessible individual parts: no more than 65 K.

  • SF6 switchgear should be inspected at least once daily. For unattended substations, inspections should be conducted according to established procedures. Inspections should focus on visual checks for abnormalities such as unusual sounds, leaks, or abnormal indications, with records maintained accordingly.

Maghatag og tip ug pagsalig sa author
Gipareserbado
Unsaon nimo nga ang 2-in 4-out 10 kV solid-insulated ring main unit adunay duha ka incoming feeder cabinets?
Unsaon nimo nga ang 2-in 4-out 10 kV solid-insulated ring main unit adunay duha ka incoming feeder cabinets?
Ang "2-in 4-out 10 kV solid-insulated ring main unit" nagrefer sa isang partikular nga tipo sa ring main unit (RMU). Ang termino nga "2-in 4-out" nagpakita nga ang RMU kini adunay duha ka incoming feeders ug upat ka outgoing feeders.Ang 10 kV solid-insulated ring main unit mao ang mga equipment nga gigamit sa medium-voltage power distribution systems, kasagaran gitakda sa mga substations, distribution stations, ug transformer stations aron mopadistribute og high-voltage power sa low-voltage dist
Garca
12/10/2025
Mga Low-Voltage Distribution Lines ug Mga Requisitos sa Power Distribution Alang sa mga Construction Sites
Mga Low-Voltage Distribution Lines ug Mga Requisitos sa Power Distribution Alang sa mga Construction Sites
Ang mga low-voltage distribution lines nagrefer sa mga circuit nga pamaagi han distribution transformer, gipabag-o ang taas nga voltage han 10 kV ngadto sa 380/220 V level—i.e., ang mga low-voltage lines nga nagmula gikan sa substation hangtod sa end-use equipment.Ang mga low-voltage distribution lines dapat mokonsidera ha panahon han design phase han substation wiring configurations. Ha factories, para han mga workshop nga may relatyibong mataas nga demand sa power, kasagaran gigamit an mga ded
James
12/09/2025
GIS Dual Grounding & Direct Grounding: State Grid 2018 Anti-Accident Measures
GIS Dual na Grounding ug Direct na Grounding: Mga Pamaagi sa Pag-uli sa mga Aksidente sa State Grid 2018
GIS Dual Grounding & Direct Grounding: State Grid 2018 Anti-Accident Measures GIS Dual na Grounding ug Direct na Grounding: Mga Pamaagi sa Pag-uli sa mga Aksidente sa State Grid 2018
1. Mahitungod sa GIS, unsa ang pagkatuod sa gipangutana sa Clause 14.1.1.4 sa "Eighteen Anti-Accident Measures" (2018 Edition) sa State Grid?14.1.1.4: Ang neutral point sa transformer kailangan i-connection ngadto sa duha ka uban-uban nga bahin sa main mesh sa grounding grid pinaagi sa duha ka grounding down conductors, ug ang bawg konduktor kailangan mobati sa thermal stability verification requirements. Ang main equipment ug equipment structures kailangan adunay duha ka grounding down conducto
Echo
12/05/2025
Tres Fase SPD: Mga Tipo, Wiring ug Guide sa Pagsulay
Tres Fase SPD: Mga Tipo, Wiring ug Guide sa Pagsulay
1. Ano ang Tres-Phase Power Surge Protective Device (SPD)?Ang tres-phase power surge protective device (SPD), nga gitawag usab og tres-phase lightning arrester, gihimo sa espesyal alang sa tres-phase AC power systems. Ang iyang primary function mao ang pag-limitar sa transient overvoltages gikan sa lightning strikes o switching operations sa power grid, aron maprotektahan ang downstream electrical equipment gikan sa damage. Ang SPD operasyon basehan sa energy absorption ug dissipation: kon maoy
James
12/02/2025
Inquiry
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo