• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Generator circuit breaker (GCB) important special requirements

Edwiin
Field: Power switch
China

High Continuous Current Levels

Generator Circuit Breakers (GCBs) are required to handle high continuous current levels over extended periods. To meet this demand, they necessitate a continuous cooling system for the conductors. This cooling mechanism ensures that the conductors can operate within a safe temperature range, preventing overheating and potential damage, thereby maintaining the reliability and efficiency of the GCBs during long - term high - current operations.

Unique Fault Current Conditions

There are two main types of fault current conditions associated with GCBs:

  • System - source (transformer - fed faults): These faults can be extremely severe because the full energy of the power system is involved in feeding the fault. To effectively clear such faults, GCBs must not only be tested but also be capable of interrupting high symmetrical fault currents. The magnitude of these faults can put significant stress on the GCBs, requiring them to have robust interruption capabilities.

  • Generator - source (generator - fed) faults: Although generally lower in magnitude compared to system - source faults, generator - source faults are characterized by a much higher degree of asymmetry. This high asymmetry can sometimes lead to a particularly challenging condition known as “Delayed Current Zeroes”. GCBs need to be designed to handle these unique characteristics to ensure reliable fault interruption.

Unique Voltage Conditions

There are also two notable voltage - related aspects for GCBs:

  • Very fast RRRV (Rate of Rise of Recovery Voltage): The resistance and stray capacitance in a generator circuit are typically much lower than those in a normal distribution circuit. As a result, the circuit has very high natural frequencies, which in turn lead to extreme Transient Recovery Voltage (TRV) with a high RRRV. GCBs must be able to withstand and operate effectively under these high - speed voltage recovery conditions.

  • Out - of - phase switching: This situation can occur during normal startup procedures. Initially, the GCB is in the open position, and the generator is disconnected while the power system is operating at its normal voltage. Out - of - phase switching can pose challenges to the GCBs, and they need to be designed to handle such scenarios safely and efficiently.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.