• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What is Arcing Ground ?

Encyclopedia
Field: Encyclopedia
0
China

What is Arcing Ground ?

Definition: Arcing ground refers to a surge that arises when the neutral is not earthed. This phenomenon occurs in ungrounded three - phase systems due to the flow of capacitive current. Capacitive current is the current that flows between conductors when a voltage is applied. The voltage across the capacitances is called the phase voltage. During a fault, the voltage across the capacitance in the faulted phase drops to zero, while in the other phases, the voltage increases by a factor of √3.

Arcing Ground Phenomena

In a three - phase line, each phase has capacitance to earth. When a fault occurs in any one of the phases, capacitive fault current flows to the ground. If the fault current exceeds 4 - 5 amperes, it becomes sufficient to sustain an arc in the ionized fault path, even after the fault has self - cleared.

插图.jpg

When the capacitive current exceeds 4 - 5 amperes and flows through the fault, it generates an arc in the ionized fault path. Once the arc is formed, the voltage across it drops to zero, causing the arc to extinguish. Subsequently, the potential of the fault current is restored, leading to the formation of a second arc. This intermittent arcing phenomenon is known as arcing grounding.

The alternating extinction and reignition of the charging current flowing through the arc build up the potential of the other two healthy conductors as a result of high - frequency oscillations being set up. These high - frequency oscillations are superimposed on the network and can produce surge voltages as high as six times the normal value. Such overvoltages can damage the healthy conductors at other points in the system.

How to Eliminate Arcing Ground?

The surge voltage caused by arcing ground can be eliminated by using an arc suppression coil, also known as a Peterson coil. The arc suppression coil is an iron - cored tapped reactor connected between the neutral and the ground.

插图1.jpg

The reactor within the arc suppression coil extinguishes arcing ground by counterbalancing the capacitive current. Specifically, the Peterson coil functions to isolate the system. In this way, the healthy phases can continue to supply power. This allows the system to avoid a complete shutdown until the fault is accurately located and isolated.

Give a tip and encourage the author!
Recommended
Strange Devices on Transmission Lines: 5 Little-Known Practical Functions(1)
1 Aviation Warning SpheresAviation warning spheres, also known as reflective safety spheres, are used on overhead transmission lines near airports, especially on extra-high-voltage (above 220kV) lines and river-crossing transmission lines. Highly visible aviation marker spheres (aviation warning spheres) must be installed along the lines to provide warning signals.The aviation marker sphere (aviation warning sphere) has a diameter of ф=600mm. The sphere can be manufactured in various bright colo
Leon
09/04/2025
Transmission Line
In transmission lines, a "π" connection involves breaking the original line from Substation A to Substation B and inserting Substation C, forming a "π" configuration. After the "π" connection, the original single line is divided into two independent transmission lines. Following the "π" connection, Substations B and C may both be powered by Substation A (in this case, Substation C receives power via a feeder from Substation B's busbar, or possibly from another voltage point within Substation B);
Encyclopedia
09/04/2025
What are the principles of forced re-energization of transmission lines?
Principles of Forced Re-energization of Transmission LinesRegulations for Forced Re-energization of Transmission Lines Correctly select the forced re-energization end of the line. If necessary, change the connection configuration before forced re-energization, taking into account the reduction of short-circuit capacity and its impact on grid stability. There must be a transformer with its neutral point directly grounded on the busbar at the forced re-energization end. Pay attention to the impact
Edwiin
09/04/2025
Analysis of Accident Handling in Transmission Lines
Analysis of Transmission Line Fault HandlingAs a fundamental component of the power grid, transmission lines are widely distributed and numerous, often exposed to diverse geographical and climatic conditions, making them highly susceptible to faults. Common causes include overvoltage, pollution flashover, insulation damage, tree encroachment, and external damage. Line tripping is one of the most frequent faults in power plant and substation operations, with fault types including single-phase-to-
Leon
09/04/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.