1. Uri ng Circuit Breakers

1.1 Air Circuit Breaker (ACB)
Tinatawag din itong molded frame o universal circuit breaker, kung saan lahat ng komponente ay nakalakip sa isang insuladong metal na frame. Karaniwan ito ay open-type, na nagbibigay-daan sa madaling pagpalit ng mga contact at bahagi, at maaaring makapag-imbak ng iba't ibang accessories. Ang ACBs ay karaniwang ginagamit bilang pangunahing switch para sa power supply. Ang overcurrent trip units ay kasama ang electromagnetic, electronic, at intelligent types. Nagbibigay ito ng apat na yugto ng proteksyon: long-time delay, short-time delay, instantaneous, at ground fault, na bawat setting ng proteksyon ay maaaring i-adjust sa loob ng isang range batay sa laki ng frame.

Ang ACBs ay angkop para sa AC 50Hz networks na may rated voltages ng 380V o 660V at rated currents mula 200A hanggang 6300A. Ginagamit ito pangunahin para sa power distribution at proteksyon laban sa overloads, undervoltage, short circuits, at single-phase grounding. Ang mga breakers na ito ay nagbibigay ng maraming intelligent protection functions at selective protection. Sa normal na kondisyon, maaari itong gamitin para sa infrequent circuit switching. Ang ACBs na may rating hanggang 1250A ay maaari ring protektahan ang mga motors mula sa overload at short circuits sa 380V/50Hz systems.

Ang karaniwang aplikasyon nito ay kinabibilangan ng main outgoing switches sa 400V side ng mga transformers, bus tie switches, high-capacity feeder switches, at large motor control switches.

1.2 Molded Case Circuit Breaker (MCCB)
Tinatawag din itong plug-in circuit breaker, kung saan ang mga terminal, arc extinguishers, trip units, at operating mechanism ay nakalakip sa isang plastic enclosure. Ang auxiliary contacts, undervoltage trip units, at shunt trip units ay kadalasang modular, na nagreresulta sa compact na disenyo. Ang MCCBs ay hindi karaniwang disenyo para sa repair at karaniwang ginagamit bilang branch circuit protection.

Karamihan sa MCCBs ay may thermal-magnetic trip units. Ang mas malalaking modelo ay maaaring may solid-state trip sensors. Ang overcurrent trip units maaaring electromagnetic o electronic. Ang electromagnetic MCCBs ay kadalasang non-selective, na nagbibigay lamang ng long-time at instantaneous protection. Ang electronic MCCBs ay nagbibigay ng apat na function ng proteksyon: long-time, short-time, instantaneous, at ground fault. Ang ilang bagong modelo ay kasama ang zone-selective interlocking.

Ang MCCBs ay karaniwang ginagamit para sa feeder circuit control at proteksyon, main outgoing switches sa small distribution transformers, motor control terminals, at bilang power switches para sa iba't ibang machinery.

1.3 Miniature Circuit Breaker (MCB)
Ang MCBs ay ang pinaka-widely used na terminal protection devices sa building electrical systems. Protektado nito ang single-phase at three-phase circuits hanggang 125A laban sa short circuits, overloads, at overvoltage. Magkakaroon ito ng 1P, 2P, 3P, at 4P configurations.

Ang MCB ay binubuo ng operating mechanism, contacts, protective devices (iba't ibang trip units), at arc extinguishing system. Ang mga contact ay isinasara manwal o elektrikal at inilalagay sa lugar ng free-tripping mechanism. Ang coil ng overcurrent trip unit at ang heating element ng thermal trip unit ay konektado sa serye sa main circuit, habang ang undervoltage trip coil ay konektado sa parallel sa power supply.

Sa building electrical design, ang MCBs ay ginagamit para sa overload, short-circuit, overcurrent, undervoltage, ground fault, leakage protection, automatic transfer ng dual power sources, at infrequent motor starting at proteksyon.

2. Pangunahing Teknikal na Parameters ng Circuit Breakers

  • Rated Operating Voltage (Ue)
    Ang nominal voltage kung saan ang circuit breaker ay disenyo para mag-operate continuously sa ilalim ng tinukoy na kondisyon. Sa China, para sa mga sistema hanggang 220kV, ang maximum operating voltage ay 1.15 times ang system rated voltage; para sa 330kV at pataas, ito ay 1.1 times. Ang breaker ay dapat panatilihin ang insulation at gumawa ng switching operations sa maximum operating voltage ng sistema.

  • Rated Current (In)
    Ang current na ang trip unit ay maaaring carry continuously sa ambient temperatures hanggang 40°C. Para sa adjustable trip units, ito ang maximum adjustable current. Sa temperature na higit sa 40°C (hanggang 60°C), pinapayagan ang derating.

  • Overload Trip Current Setting (Ir)
    Ang breaker trips na may time delay kapag lumampas ang current sa Ir, na kumakatawan sa maximum current na ang breaker ay maaaring carry nang walang tripping. Ang Ir ay dapat mas malaki sa maximum load current (Ib) ngunit mas maliit sa cable’s permissible current (Iz). Para sa thermal-magnetic breakers, ang Ir ay tipikal na adjustable mula 0.7 hanggang 1.0In; ang electronic trip units ay nagbibigay ng mas wide range, karaniwang 0.4 hanggang 1.0In. Para sa fixed trip units, Ir = In.

  • Short-Circuit Trip Current Setting (Im)
    Ang threshold kung saan ang instantaneous o short-time trip unit ay aktibo upang mabilis na disconnect ang circuit sa high fault currents.

  • Rated Short-Time Withstand Current (Icw)
    Ang current na ang breaker ay maaaring tiisin sa isang specified duration nang walang thermal damage.

  • Breaking Capacity
    Ang maximum fault current na ang breaker ay maaaring safely interrupt, independent ng rated current. Common values include 36kA at 50kA. Ito ay categorized into ultimate breaking capacity (Icu) at service breaking capacity (Ics).

3. General Principles for Circuit Breaker Selection

  • Rated operating voltage ≥ circuit rated voltage.

  • Rated short-circuit making/breaking capacity ≥ calculated load current.

  • Rated short-circuit making/breaking capacity ≥ maximum possible short-circuit current sa circuit.

  • Single-phase-to-ground short-circuit current sa circuit end ≥ 1.25 × instantaneous (o short-time) trip setting.

  • Undervoltage trip unit rated voltage = circuit rated voltage.

  • Shunt trip unit rated voltage = control power supply voltage.

  • Electric operating mechanism rated voltage = control power supply voltage.

  • Para sa lighting circuits, set instantaneous electromagnetic trip current sa 6 times ang load current.

  • Para sa single motor short-circuit protection: 1.35× motor starting current (DW series) o 1.7× (DZ series).

  • Para sa multiple motors: 1.3× largest motor starting current + sum of other motors’ running currents.

  • As main transformer low-voltage side switch: breaking capacity > transformer’s low-voltage short-circuit current; trip rated current ≥ transformer rated current; short-circuit setting = 6–10× transformer rated current; overload setting = transformer rated current.

  • After preliminary selection, coordinate with upstream and downstream breakers to prevent cascading trips and minimize outage scope.

4. Selectivity of Circuit Breakers
Ang circuit breakers ay classified bilang selective o non-selective. Ang selective breakers ay nagbibigay ng two- o three-stage protection: instantaneous at short-time para sa short circuits, long-time para sa overload. Ang non-selective breakers ay tipikal na instantaneous (short-circuit only) o long-time (overload only). Ang selectivity ay nakuha gamit ang short-time delay trip units na may iba't ibang time settings. Key considerations:

  • Upstream instantaneous trip setting ≥ 1.1 × maximum 3-phase short-circuit current sa downstream breaker’s output.

  • If downstream is non-selective, upstream short-time trip setting ≥ 1.2 × downstream instantaneous trip setting to maintain selectivity.

  • If downstream is also selective, upstream short-time delay time ≥ downstream short-time delay time + 0.1s.
    Generally, Iop.1 ≥ 1.2 × Iop.2.

5. Cascading Protection
Sa system design, ang coordination sa pagitan ng upstream at downstream breakers ay nagbibigay ng selectivity, speed, at sensitivity. Ang proper coordination ay nagbibigay ng selective fault isolation, na nagsasala ng power sa healthy circuits. Ang cascading ay gumagamit ng current-limiting effect ng upstream breaker (QF1). Kapag nagkaroon ng short circuit sa downstream (sa QF2), ang QF1’s current-limiting action ay nagsasala ng actual fault current, na nagbibigay-daan sa QF2 na interrupt ang isang current na mas mataas sa rated capacity nito. Ito ay nagbibigay-daan sa paggamit ng lower-cost, lower-breaking-capacity downstream breakers. Ang conditions ay kasama ang walang critical loads sa adjacent circuits (dahil ang QF1 trip ay mag-blackout sa QF3), at proper matching ng instantaneous settings. Ang cascading data ay determined sa pamamagitan ng testing at provided ng manufacturers.

6. Sensitivity of Circuit Breakers
Upang matiyak ang reliable operation sa minimum fault conditions, ang sensitivity (Sp) ay dapat ≥1.3 per GB50054-95:
Sp = Ik.min / Iop ≥ 1.3
Kung saan ang Iop ay ang instantaneous o short-time trip setting, at ang Ik.min ay ang minimum short-circuit current sa protected line end sa ilalim ng minimum system operation. Para sa selective breakers na may both short-time at instantaneous trips, ang short-time trip sensitivity lang ang kailangan ng verification.

7. Selection and Setting of Trip Units

(1) Instantaneous Overcurrent Trip Setting.Must exceed the circuit’s peak current (Ipk) during motor startup:
Iop(0) ≥ Krel × Ipk
(Krel = reliability factor)

(2) Short-Time Overcurrent Trip Setting and Time
Iop(s) ≥ Krel × Ipk. Time delays are typically 0.2s, 0.4s, or 0.6s, set to ensure upstream operation time exceeds downstream by one time step.

(3) Long-Time Overcurrent Trip Setting and Time
Protects against overload: Iop(l) ≥ Krel × I30 (maximum load current). Time setting must exceed allowable short-term overload duration.

(4) Coordination Between Trip Settings and Cable Capacity.To prevent cable overheating or fire without tripping:

Iop ≤ Kol × Ial
Where Ial = cable’s allowable current-carrying capacity, Kol = short-term overload factor (4.5 for instantaneous/short-time trips; 1.1 for long-time trip as short-circuit protection; 1.0 for overload protection only). If not satisfied, adjust trip setting or increase cable size.

Magbigay ng tip at hikayatin ang may-akda!
Inirerekomenda
Ano ang Discharge Load para sa Energy Absorption sa mga Power Systems?
Ano ang Discharge Load para sa Energy Absorption sa mga Power Systems?
Pag-load ng Discharge para sa Pag-absorb ng Enerhiya: Isang Mahalagang Teknolohiya para sa Paggamit ng Sistemang Paggamit ng KapangyarihanAng pag-load ng discharge para sa pag-absorb ng enerhiya ay isang teknolohiya ng operasyon at kontrol ng sistema ng kapangyarihan na pangunahing ginagamit upang tugunan ang labis na enerhiyang elektriko dahil sa pag-ugit ng load, mga kaso ng sorseng kapangyarihan, o iba pang mga pagkakaiba sa grid. Ang pagpapatupad nito ay kinabibilangan ng mga sumusunod na ma
Echo
10/30/2025
Kung Bakit Mahalaga ang Katumpakan ng Paghahabi sa mga Sistema ng Kalidad ng Kapangyarihan
Kung Bakit Mahalaga ang Katumpakan ng Paghahabi sa mga Sistema ng Kalidad ng Kapangyarihan
Ang Mahalagang Tungkulin ng Pagmomonito sa Katumpakan sa mga Online na Device para sa Kalidad ng KapangyarihanAng katumpakan ng pagsukat ng mga online na device para sa pagmomonito ng kalidad ng kapangyarihan ay ang pundamental na bahagi ng "kakayahan ng pagkaalam" ng sistema ng kapangyarihan, na direktang nagpapasya sa kaligtasan, ekonomiya, estabilidad, at katiwalaan ng pagbibigay ng kapangyarihan sa mga gumagamit. Ang hindi sapat na katumpakan ay nagdudulot ng maling paghuhusga, maling pagkon
Oliver Watts
10/30/2025
Paano Sinisiguro ng Power Dispatching ang Estabilidad at Epektividad ng Grid?
Paano Sinisiguro ng Power Dispatching ang Estabilidad at Epektividad ng Grid?
Pamamahala ng Elektrikong Pwersa sa Modernong mga Sistemang PwersaAng sistema ng pwersa ay isang kritikal na imprastraktura ng modernong lipunan, nagbibigay ng mahalagang elektrikong enerhiya para sa industriyal, komersyal, at residential na paggamit. Bilang core ng operasyon at pamamahala ng sistema ng pwersa, ang pamamahala ng elektrikong pwersa ay may layuning tugunan ang pangangailangan sa kuryente habang sinisigurado ang estabilidad ng grid at ekonomiko na epektibidad.1. Pundamental na mga
Echo
10/30/2025
Paano Pabutiin ang Katumpakan ng Pagkakatuklas ng Harmonics sa mga Sistemang Paggamit ng Kapangyarihan
Paano Pabutiin ang Katumpakan ng Pagkakatuklas ng Harmonics sa mga Sistemang Paggamit ng Kapangyarihan
Ang papel ng Harmonic Detection sa Pagtaguyod ng Estabilidad ng Sistema ng Paggamit ng Kuryente1. Kahalagahan ng Harmonic DetectionAng harmonic detection ay isang kritikal na pamamaraan para masukat ang antas ng polusyon ng harmonics sa mga sistema ng kuryente, matukoy ang mga pinagmulan ng harmonics, at maging hula ng potensyal na epekto ng harmonics sa grid at konektadong mga aparato. Dahil sa malawakang paggamit ng power electronics at lumalaking bilang ng mga nonlinear load, ang polusyon ng
Oliver Watts
10/30/2025
Inquiry
I-download
Kumuha ng IEE-Business Application
Gamit ang app na IEE-Business upang makahanap ng kagamitan makuha ang mga solusyon makipag-ugnayan sa mga eksperto at sumama sa industriyal na pakikipagtulungan kahit kailan at saanman buong pagsuporta sa pag-unlad ng iyong mga proyekto at negosyo sa enerhiya