• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What are the methods for switching operations of station transformers?

Vziman
Vziman
Field: Manufacturing
China

Let's take an auxiliary power system with two station transformers as an example. When one station transformer needs to be out of service, there are two operation methods: non-interruptive power supply and instantaneous power interruption. Generally, the method of instantaneous power interruption on the low-voltage side is preferred.

The operation method for instantaneous power interruption on the low-voltage side is as follows:

  • Open the 380V power incoming circuit breaker of the corresponding section of the auxiliary power for the station transformer to be out of service.

  • Open the 380V incoming isolating switch of the station transformer to be out of service.

  • Close the auxiliary power section circuit breaker.

  • Open the bus isolating switch of the station transformer to be out of service.

  • Open the high-voltage fuse of the station transformer to be out of service.

The operation method for non-interruptive power supply on the low-voltage side is as follows:

  • Apply to the dispatching for paralleling the high-voltage side of the station transformers (for example, close the 35kV bus tie circuit breaker).

  • Measure that the voltage difference between the busbars of section Ⅰ and section Ⅱ of the auxiliary power is qualified, then close the auxiliary power section circuit breaker to make section Ⅰ and section Ⅱ of the auxiliary power operate in parallel.

  • Open the 380V power incoming circuit breaker of the corresponding section of the auxiliary power for the station transformer to be out of service.

  • Open the 380V incoming isolating switch of the station transformer to be out of service.

  • Open the bus isolating switch of the station transformer to be out of service.

  • Open the high-voltage fuse of the station transformer to be out of service.

electrical transformer.jpg

Give a tip and encourage the author!
Recommended
Toroidal vs Square Transformers: Key Differences
Toroidal vs Square Transformers: Key Differences
What Is a Toroidal Transformer?A toroidal transformer is a major type of electronic transformer that has been widely used in household appliances and other electronic equipment with higher technical requirements. Its primary applications are as a power transformer and an isolation transformer. Abroad, toroidal transformers are already available in complete series and are extensively used in computers, medical equipment, telecommunications, instruments, and lighting applications.In China, toroida
Dyson
11/06/2025
What causes a transformer to be noisier under no-load conditions?
What causes a transformer to be noisier under no-load conditions?
When a transformer is operating under no-load conditions, it often produces louder noise than under full load. The primary reason is that, with no load on the secondary winding, the primary voltage tends to be slightly higher than nominal. For example, while the rated voltage is typically 10 kV, the actual no-load voltage may reach around 10.5 kV.This elevated voltage increases the magnetic flux density (B) in the core. According to the formula:B = 45 × Et / S(where Et is the designed volts-per-
Noah
11/05/2025
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
When installing an arc suppression coil, it is important to identify the conditions under which the coil should be taken out of service. The arc suppression coil should be disconnected under the following circumstances: When a transformer is being de-energized, the neutral-point disconnector must be opened first before performing any switching operations on the transformer. The energizing sequence is the reverse: the neutral-point disconnector should be closed only after the transformer is energ
Echo
11/05/2025
What fire prevention measures are available for power transformer failures?
What fire prevention measures are available for power transformer failures?
Failures in power transformers are commonly caused by severe overload operation, short circuits due to winding insulation degradation, aging of transformer oil, excessive contact resistance at connections or tap changers, failure of high- or low-voltage fuses to operate during external short circuits, core damage, internal arcing in oil, and lightning strikes.Since transformers are filled with insulating oil, fires can have severe consequences—ranging from oil spraying and ignition to, in extrem
Noah
11/05/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.