• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What are the methods for switching operations of station transformers?

Vziman
Field: Manufacturing
China

Let's take an auxiliary power system with two station transformers as an example. When one station transformer needs to be out of service, there are two operation methods: non-interruptive power supply and instantaneous power interruption. Generally, the method of instantaneous power interruption on the low-voltage side is preferred.

The operation method for instantaneous power interruption on the low-voltage side is as follows:

  • Open the 380V power incoming circuit breaker of the corresponding section of the auxiliary power for the station transformer to be out of service.

  • Open the 380V incoming isolating switch of the station transformer to be out of service.

  • Close the auxiliary power section circuit breaker.

  • Open the bus isolating switch of the station transformer to be out of service.

  • Open the high-voltage fuse of the station transformer to be out of service.

The operation method for non-interruptive power supply on the low-voltage side is as follows:

  • Apply to the dispatching for paralleling the high-voltage side of the station transformers (for example, close the 35kV bus tie circuit breaker).

  • Measure that the voltage difference between the busbars of section Ⅰ and section Ⅱ of the auxiliary power is qualified, then close the auxiliary power section circuit breaker to make section Ⅰ and section Ⅱ of the auxiliary power operate in parallel.

  • Open the 380V power incoming circuit breaker of the corresponding section of the auxiliary power for the station transformer to be out of service.

  • Open the 380V incoming isolating switch of the station transformer to be out of service.

  • Open the bus isolating switch of the station transformer to be out of service.

  • Open the high-voltage fuse of the station transformer to be out of service.

electrical transformer.jpg

Give a tip and encourage the author!

Recommended

How to Judge, Detect and Troubleshoot Transformer Core Faults
1. Hazards, Causes, and Types of Multi-Point Grounding Faults in Transformer Cores1.1 Hazards of Multi-Point Grounding Faults in the CoreUnder normal operation, a transformer core must be grounded at only one point. During operation, alternating magnetic fields surround the windings. Due to electromagnetic induction, parasitic capacitances exist between the high-voltage and low-voltage windings, between the low-voltage winding and the core, and between the core and the tank. The energized windin
01/27/2026
A Brief Discussion on the Selection of Grounding Transformers in Boost Stations
A Brief Discussion on the Selection of Grounding Transformers in Boost StationsThe grounding transformer, commonly referred to as "grounding transformer," operates under the condition of being no-load during normal grid operation and overloaded during short-circuit faults. According to the difference in filling medium, common types can be divided into oil-immersed and dry-type; according to phase number, they can be classified into three-phase and single-phase grounding transformers. The groundi
01/27/2026
Impact of DC Bias in Transformers at Renewable Energy Stations Near UHVDC Grounding Electrodes
Impact of DC Bias in Transformers at Renewable Energy Stations Near UHVDC Grounding ElectrodesWhen the grounding electrode of an Ultra-High-Voltage Direct Current (UHVDC) transmission system is located close to a renewable energy power station, the return current flowing through the earth can cause a rise in ground potential around the electrode area. This ground potential rise leads to a shift in the neutral-point potential of nearby power transformers, inducing DC bias (or DC offset) in their
01/15/2026
Distribution Equipment Transformer Testing, Inspection, and Maintenance
1.Transformer Maintenance and Inspection Open the low-voltage (LV) circuit breaker of the transformer under maintenance, remove the control power fuse, and hang a “Do Not Close” warning sign on the switch handle. Open the high-voltage (HV) circuit breaker of the transformer under maintenance, close the grounding switch, fully discharge the transformer, lock the HV switchgear, and hang a “Do Not Close” warning sign on the switch handle. For dry-type transformer maintenance: first clean the porcel
12/25/2025
Related Products
Send inquiry
+86
Click to upload file

IEE Business will not sell or share your personal information.

Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.