As the core component for regulating transformer voltage, the on-load tap-changer suffers a series of serious hazards from frequent operation, including contact wear, transition resistor burnout, insulating oil deterioration, and mechanical fatigue.
To ensure grid safety, tap-changing operations should strictly follow the frequency limits in the maintenance regulations (for example, a core inspection should be carried out 1–2 years after commissioning or after 5000 tap-changes, and overhaul should be carried out after reaching the prescribed maintenance-cycle limit), and the daily tap-changing frequency should be controlled according to the operator's regulations.
At the same time, tap-changing should be prohibited under abnormal conditions such as equipment overload, gas-relay alarm, or unqualified oil quality.