• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What Are Combined Transformer Standards? Key Specs & Tests

Edwiin
Edwiin
Field: Power switch
China

Combined Instrument Transformers: Technical Requirements and Testing Standards Explained with Data

A combined instrument transformer integrates a voltage transformer (VT) and a current transformer (CT) into a single unit. Its design and performance are governed by comprehensive standards covering technical specifications, testing procedures, and operational reliability.

1. Technical Requirements

Rated Voltage:
The primary rated voltages include 3kV, 6kV, 10kV, and 35kV, among others. The secondary voltage is typically standardized at 100V or 100/√3 V. For example, in a 10kV system, the primary rated voltage of the combined transformer is 10kV, while the secondary output is 100V—meeting both measurement and protection requirements.

Rated Current Ratio:
The CT section offers various rated current ratios such as 50/5, 100/5, and 200/5. These ratios can be selected based on actual system current levels to accurately transform primary current to the secondary side (typically 5A), ensuring precise monitoring and relay protection operation.

2. Testing Standards

Insulation Tests:
These verify the dielectric strength of the transformer under normal and transient overvoltage conditions.

  • Power Frequency Withstand Test:
    For a 10kV combined transformer, the test voltage is typically 42kV RMS, applied for 1 minute. This ensures the insulation can withstand sustained power-frequency overvoltages during service.

  • Impulse Withstand Test:
    The peak impulse voltage is generally 75kV, simulating lightning surge conditions. This test evaluates the transformer’s ability to endure transient overvoltages without breakdown.

Accuracy (Error) Tests:
Strict error limits are defined based on accuracy classes.

CT VT.jpg

  • Voltage Transformer (0.2 Class):
    At rated voltage, the ratio error must not exceed ±0.2%, and the phase angle error must be within ±10 minutes (′).

  • Current Transformer (0.2S Class):
    Over a wide range from 1% to 120% of rated current, the ratio error remains within approximately ±0.2%, with tightly controlled phase angle error. This high accuracy is essential for metering applications, especially under low-load conditions.

Temperature Rise Test:
This test ensures safe long-term operation under full load.

  • Conducted at rated load and specified ambient temperature (usually 40°C), the average winding temperature rise must not exceed 65K. This limit prevents insulation degradation and ensures reliable performance over the transformer’s service life.

Summary

Combined instrument transformers are engineered to meet rigorous international standards (such as IEC 61869 series and GB/T 20840). Their technical parameters—like 10kV primary voltage, 100V secondary output, and 100/5 current ratio—are selected based on system requirements. Compliance with tests including 42kV power frequency, 75kV impulse withstand, ±0.2% accuracy, and 65K temperature rise guarantees safety, precision, and durability in power systems.

Give a tip and encourage the author!
Recommended
How Altitude Affects HV Equipment Insulation & Temperature Rise?
How Altitude Affects HV Equipment Insulation & Temperature Rise?
As altitude increases, air density, temperature, and atmospheric pressure decrease accordingly, leading to reduced dielectric strength of air gaps and external insulation performance of porcelain components. This results in degraded external insulation performance for high-voltage electrical equipment. Since most high-voltage equipment is designed for installation at altitudes below 1,000 meters, using such equipment at elevations exceeding 1,000 meters may compromise reliable insulation perform
James
10/23/2025
What Causes CT20 Mechanism to Fail to Close? Insufficient Closing Solenoid Stroke Is Key
What Causes CT20 Mechanism to Fail to Close? Insufficient Closing Solenoid Stroke Is Key
The CT20 series operating mechanism is a classic design. One common cause of failure to close is an improperly adjusted, overly short stroke of the closing solenoid. The rated stroke is approximately 5mm. However, due to vibration or incorrect adjustment after maintenance, the stroke may decrease to around 3mm, potentially causing the mechanism to fail to operate. If the control system continuously issues a closing command under such conditions, the solenoid remains energized, which can lead to
Felix Spark
10/23/2025
Are PM Actuators Reliable? Compare Types & Benefits
Are PM Actuators Reliable? Compare Types & Benefits
The performance of circuit breaker operating mechanisms is decisive for reliable and safe power supply. While various mechanisms each have their advantages, the emergence of a new type does not completely replace traditional ones. For example, despite the rise of eco-friendly gas insulation, solid insulation ring main units still hold about 8% of the market, showing new technologies rarely fully displace existing solutions.The permanent magnet actuator (PMA) consists of permanent magnets, a clos
Edwiin
10/23/2025
What Are the Types of Reactors? Key Roles in Power Systems
What Are the Types of Reactors? Key Roles in Power Systems
Reactor (Inductor): Definition and TypesA reactor, also known as an inductor, generates a magnetic field within the surrounding space when current flows through a conductor. Therefore, any current-carrying conductor inherently possesses inductance. However, the inductance of a straight conductor is small and produces a weak magnetic field. Practical reactors are constructed by winding the conductor into a solenoid shape, known as an air-core reactor. To further increase inductance, a ferromagnet
James
10/23/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.