• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Location of Shunt Capacitors

Encyclopedia
Field: Encyclopedia
0
China

Shunt Capacitors Definition


Shunt capacitors are devices installed in electrical systems to improve power factor by compensating for reactive power.


Distribution System Capacitor Bank


In distribution feeder capacitor bank are installed on pole to compensate reactive power of that particular feeder. These banks are normally mounted on one of the poles on which the distribution feeders run. The mounted capacitor banks are normally interconnected with over head feeder conductors by means of insulated power cable. 


The size of the cable depends upon the voltage rating of the system. The voltage range of the system for which pole mounted capacitor bank can be install, may be from 440 V to 33 KV. The rating of capacitor bank may be from 300 KVAR to MVAR. The pole mounted capacitor bank can be either fixed unit or switched unit depending upon varying load condition.


EHV Shunt Capacitor


In extra high voltage system, the generated electrical power may have to be transmitted a long distance via transmission line. During journey of power, sufficient voltage may be dropped due to inductive effect of the line conductors. This voltage drop may be compensated by providing ∑ HV capacitor bank at ∑ HV sub-station. This drop of voltage is maximum at peak load condition, hence, the capacitor bank installed for in this case should have switching control to make it off and on as when required.


Substation Capacitor Bank


When high inductive load has to be delivered from a high voltage or medium voltage substation, one or more capacitor bank of suitable size should be installed at substation to compensate inductive VAR of the entire load. These capacitors banks are controlled by circuit breaker and provided with lightening arrestors. Typical protection scheme along with protection relays are also provided.


Metal Encoder Capacitor Bank


For small and industrial subtraction indoor type capacitor banks may also be used. These capacitor bank are installed in metal cabinet. This design is compact and bank requires less maintenance. The uses of these banks are more compared to outdoor bank, as these are not exposed to external environment.


Distribution Capacitor Bank


Distribution capacitor banks are normally pole mounted capacitor bank installed nearer to load point or installed at distribution subtraction.


These banks do not help to improve power factor of primary system. These capacitors bank are cheaper than other power capacitors bank. All types of protection schemes for capacitor bank cannot be provided to a pole mounted capacitor bank. Although pole mounted cap bank is outdoor type but sometimes it is kept in metal enclosure to protect from outdoor environmental conditions.


Fixed Capacitor Bank


Some loads, especially industrial ones, need constant reactive power for power factor correction. Fixed capacitor banks, used in such cases, do not have control systems to switch on or off. They operate with the feeders, staying connected as long as the feeders are live.


Switched Capacitor Banks


In high voltage power system, compensation of reactive power is mainly required during peak load condition of system. There may be reverse effect if the bank is connected to the system at mean load condition. At low load condition, the capacitive effect of bank may increase the reactive power of the system instead of decreasing it.


In this situation capacitors bank must be switched ON during peak load poor power factor condition and must also be switched OFF during low load and high power factor condition. Here switched capacitor banks are used. When a capacitor bank is switched ON it provides more or less constant reactive power to the system. It helps to maintain desired power factor of the system even at peak load condition. It prevents, over voltage of system during low load condition as capacitor is disconnected from the system during low load condition. During operation of bank, it reduces losses both of the feeders and transformer of the system as it is directly installed at primary power system.

 

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.