Circuit Breaker Ratings

Encyclopedia
09/09/2024

Circuit Breaker Definition


A circuit breaker is defined as a device designed to protect an electrical circuit from damage caused by overcurrent or short circuits by interrupting the flow of electricity.

 


Short Circuit Breaking Current of Circuit Breaker


This is the maximum short circuit current which a circuit breaker (CB) can withstand before it, finally cleared by opening its contacts.


When a short circuit flows through a circuit breaker, it causes thermal and mechanical stresses in the breaker’s current-carrying parts. If the contact area and conducting parts are too small, this can lead to permanent damage to the insulation and conducting parts of the circuit breaker.


According to Joule’s law of heating, the temperature rise is directly proportional to the square of the short circuit current, contact resistance, and duration of the short circuit. The short circuit current continues to flow through the circuit breaker until the fault is cleared by opening the breaker.


As the thermal stress in the circuit breaker is proportional to the period of short circuit, the breaking capacity of electrical circuit breaker, depends upon the operating time. At 160oC aluminum becomes soft and losses its mechanical strength, this temperature may be taken as limit of temperature rise of breaker contacts during short circuit.


Hence, the short circuit breaking capacity or breaking current of a circuit breaker is defined as the maximum current that can flow through the breaker from the time a short circuit occurs until it is cleared, without causing permanent damage to the circuit breaker.The value of short circuit breaking current is expressed in RMS.


During short circuit, the CB is not only subjected to thermal stress, it also suffers seriously from mechanical stresses. So during determining short circuit capacity, the mechanical strength of the CB is also considered.


So for choosing suitable circuit breaker it is obvious to determine the fault level at that point of the system where CB to be installed. Once the fault level of any part of electrical transmission is determined it is easy to choose the correct rated circuit breaker for this part of network.


Rated Short Circuit Making Capacity


The short circuit making capacity of a circuit breaker is expressed in peak value, unlike the breaking capacity, which is in RMS value. Theoretically, at the instant a fault occurs, the fault current can rise to twice its symmetrical fault level.


At the instant of switching on a circuit breaker in faulty condition, of system, the short circuit portion of the system connected to the source. The first cycle of the current during a circuit is closed by circuit breaker, has maximum amplitude. This is about twice of the amplitude of symmetrical fault current waveform.


The breaker’s contacts have to withstand this highest value of current during the first cycle of waveform when breaker is closed under fault. On the basis of this above mentioned phenomenon, a selected breaker should be rated with short circuit making capacity.


As the rated short circuit making current of circuit breaker is expressed in maximum peak value, it is always more than rated short circuit breaking current of circuit breaker. The normal value of short circuit making current is 2.5 times more than short circuit breaking current. This holds true for both standard and remote control circuit breaker.


Rated Operating Sequence


This is mechanical duty requirement of circuit breaker operating mechanism. The sequence of rated operating duty of a circuit breaker has been specified as:


437afca022c5811b9d3d1737f85f50de.jpeg

 

 

Where, O indicates opening operation of CB.CO represents closing operation time which is immediately followed by an opening operation without any intentional time delay.t’ is time between two operations which is necessary to restore the initial conditions and/or to prevent undue heating of conducting parts of circuit breaker. t = 0.3 sec for circuit breaker intended for first auto re closing duty, if not otherwise specified.

 

Suppose rated duty circle of a circuit breaker is:


f361c17cc1f57ab5c3f28a41a248faa3.jpeg


This means, an opening operation of circuit breaker is followed by a closing operation after a time interval of 0.3 sec, and then the circuit breaker again opens without any intentional time delay. After this opening operation the CB is again closed after 3 minutes and then instantly trips without any intentional time delay.


Rated Short Time Current


This is the current limit which a circuit breaker can carry safely for certain specific time without any damage in it. The circuit breakers do not clear the short circuit current as soon as any fault occurs in the system. There always some intentional and an intentional time delays present between the instant of occurrence of fault and instant of clearing the fault by CB.


This delay is because of time of operation of protection relays, time of operation of circuit breaker and also there may be some intentional time delay imposed in relay for proper coordination of power system protection. Even a circuit breaker fails to trip, the fault will be cleared by next higher positioned circuit breaker.


In this case the fault clearing time is longer. Hence, after fault, a circuit breaker has to carry the short circuit for certain time. The summation of all time delays should not be more than 3 seconds; hence a circuit breaker should be capable of carrying a maximum faulty current for at least this short period of time.

 

The short circuit current may have two major affects inside a circuit breaker.Because of the high electric current, there may be high thermal stress in the insulation and conducting parts of CB.The high short circuit current, produces significant mechanical stresses in different current carrying parts of the circuit breaker.


A circuit breaker is designed to withstand these stresses. However, no circuit breaker should carry a short circuit current for longer than the specified short period. The rated short time current of a circuit breaker is at least equal to its rated short circuit breaking current.


Rated Voltage of Circuit Breaker


Rated voltage of circuit breaker depends upon its insulation system. For below 400 KV systems, the circuit breaker is designed to withstand 10% above the normal system voltage. For above or equal 400 KV system the insulation of circuit breaker should be capable of withstanding 5% above the normal system voltage.


That means, rated voltage of circuit breaker corresponds to the highest system voltage. This is because during no load or small load condition the voltage level of power system is allowed rise up to highest voltage rating of the system.


cfaf76bfd9bf88b7157bad9e7641483a.jpeg


Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

Analysis of the Technical Characteristics of Online Monitoring for Medium-Voltage Switchgear Status
Analysis of the Technical Characteristics of Online Monitoring for Medium-Voltage Switchgear Status
With the increasing complexity of power system operation environment and the deepening of power system reform, traditional power grids are accelerating the transformation to smart grids. The goal of equipment condition-based maintenance is achieved through real-time perception of equipment status by new sensors, reliable communication via modern network technology, and effective monitoring by background expert systems.I. Analysis of Condition-based Maintenance StrategyCondition-based Maintenance
Oliver Watts
06/11/2025
What is the current application status and development trend of medium-voltage switchgear?
What is the current application status and development trend of medium-voltage switchgear?
With the accelerated automation of power equipment, various medium-voltage switchgear have emerged in the market. Classified by insulation media, they are mainly divided into air-insulated, SF₆ gas-insulated and solid-insulated types, each with its own advantages and disadvantages: solid insulation offers good performance but poor environmental friendliness, SF₆ features excellent arc extinguishing capability but is a greenhouse gas, and air insulation has high cost-performance but larger volume
Echo
06/11/2025
What components make up the design of medium-voltage ring network distribution switchgear?
What components make up the design of medium-voltage ring network distribution switchgear?
As an expert who has been deeply engaged in the field of power system design for many years, I have always paid attention to the technological evolution and application practice of medium-voltage ring main distribution equipment. As a core electrical device in the secondary distribution link of the power system, the design and performance of such equipment are directly related to the safe and stable operation of the power supply network. The following is a professional analysis of the key design
Dyson
06/11/2025
What aspects should be paid attention to when installing medium-voltage switch cabinets during the initial stage of subway operation?
What aspects should be paid attention to when installing medium-voltage switch cabinets during the initial stage of subway operation?
1. Statistics on Common Faults of Medium-Voltage Switchgear in the Early Operation StageAs project participants, we found during the early operation of a new metro line: 21 sets of power supply equipment were put into use, with a total of 266 accident phenomena in the first year. Among them, 77 faults occurred in medium-voltage switchgear, accounting for 28.9%—significantly higher than faults in other equipment. Statistical analysis shows that major fault types include: protection device s
Felix Spark
06/11/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!