What are the causes of dry-type transformers burning out during operation?

Felix Spark
07/01/2025

1 Fault Phenomenon
I am engaged in front - line fault maintenance work, and recently encountered problems with dry - type transformers. Dry - type transformers have a simple structure, are convenient for transportation, and easy for maintenance. They are widely used in power distribution places with relatively high environmental protection requirements. Because of their good fire - resistance, they can be installed in load - center areas to reduce voltage loss and power loss.
The property management company I work for manages 11 residential communities, with a total of 56 transformers, with a voltage level of 6000/400V. Among them, there are 38 dry - type transformers, model SCB9, with a capacity of 160 - 630kVA, all installed in box - type closed high - voltage switch cabinets. The power distribution stations in these communities have been put into operation for less than 2 years, and 5 dry - type transformers in operation have been burned one after another, which has seriously affected the lives of residents. I deeply feel the great responsibility and must thoroughly investigate the reasons.
2 Cause Analysis
As a front - line maintenance worker, my colleagues and I inspected, tested, analyzed the burned dry - type transformers. During the 5 accidents, the weather was good, there was no water accumulation or moisture in the cable trench at the bottom of the transformer, and there was no over - voltage in the system before and after the accidents. Checking the recent high - voltage test reports, the insulation was good, and the DC resistance difference met the standards.
To find out the reasons, the company invited relevant experts for consultation. I participated in the on - site investigation and found that the heat dissipation air ducts of the burned dry - type transformers were blocked. After dissection, it was seen that the insulation of the residual coils was brittle and uniformly cracked, indicating that the coils had been operating at high temperatures for a long time.
It was learned that the accidents all occurred between July and September, with hot weather and peak electricity load. The dry - type transformers had been operating at full load in the closed cabinets for a long time. Further inspection revealed that the heat dissipation air ducts were blocked by the slot plates of the control cables, causing the temperature of the transformers to continue to rise. Moreover, the only temperature alarm device was installed in the transformer room, unable to timely transmit over - temperature alarms.
Long - term high - temperature operation reduces the insulation resistance. Especially, the high - voltage coils have a high voltage level, and the decrease in insulation strength is prone to discharge, increasing the leakage current between the high - voltage layers, turns, and to the ground of the transformer, increasing the active power loss and the temperature continuously, forming a vicious cycle. Eventually, the insulating material loses its insulating performance, and inter - layer and inter - turn short - circuit insulation breakdown and burning occur . This is the main reason for the burning of dry - type transformers, and I also truly felt the impact of these factors on the equipment during on - site maintenance.
3 Treatment Measures
3.1 Cabinet Transformation and Device Installation
I participated in the transformation of the dry - type transformer cabinets by the company. We slotted the iron plates, set up air ducts around the transformer cabinets, and installed remote temperature alarm and high - temperature trip protection devices. This can monitor and respond to temperature abnormalities more timely, ensuring the operation of the equipment, and it is a specific measure I implemented in maintenance practice.
3.2 Cooling Fan Installation
For dry - type transformers of 400kVA and above, I assisted in installing cooling fans, which can automatically start and stop according to the set temperature, eliminating potential defects of operating transformers in advance and avoiding sudden accidents. In daily maintenance, I also pay attention to the operating status of these fans.
3.3 Remote Monitoring of Power Distribution Rooms
For the power distribution room of the 630kVA transformer, through remote information transmission, monitoring, and online monitoring of the operating temperature, insulation and other parameters of the transformer, as a front - line worker, I can timely grasp the operating health status of high - voltage equipment, ensuring the reliable operation of dry - type transformers, and it is also convenient for me to refer to these monitoring data during maintenance.
4 Preventive Measures
4.1 Daily Inspection Requirements
The company requires us operation and maintenance managers to conduct a patrol inspection of the high - voltage equipment in the power distribution room once a day, especially the operating status of dry - type transformers. I perform this task seriously every day, and report problems in a timely manner to ensure the safe operation of the equipment. This is an important part of my daily work.
4.2 Temperature Detection Specifications
An infrared thermometer is used to measure the temperature of the conductive connection parts of high - voltage equipment. The company stipulates that detection should be carried out once a week in spring, autumn and winter, and once a day in summer. I strictly operate according to this frequency to ensure that temperature abnormalities can be detected in a timely manner.
4.3 Comprehensive Inspection of Power Distribution Stations
For the power distribution stations without accidents, I participated in the comprehensive inspection and test, set up corresponding heat dissipation devices for dry - type transformers, ensuring good ventilation, eliminating potential equipment hazards, and taking measures for weak insulation points. I have accumulated experience in actual operations and also seen good results.
5 Conclusion
Because the armored switch cabinet has a small volume, compact structure, and poor heat dissipation effect, and the transformer is installed in a closed cabinet, a suitable cooling method must be adopted according to the capacity to avoid sudden accidents of dry - type transformers caused by unreasonable design.
It should be particularly noted that ordinary dry - type transformers must undergo a temperature rise test when put into operation in the cabinet, to understand the maximum temperature of long - term operation in advance, and eliminate potential hazards left to the power grid due to non - standard detection and construction.
After the implementation of preventive measures, no similar accidents have occurred to the operating dry - type transformers, effectively improving the reliability, and providing a guarantee for the safe operation of the power grid. As a front - line maintenance worker, I am more confident in dealing with the maintenance of such equipment.
Felix Spark

Hey there! I'm an electrical engineer specializing in Failure and Maintenance. I've dedicated my career to ensuring the seamless operation of electrical systems. I excel at diagnosing complex electrical failures, from malfunctioning industrial motors to glitchy power distribution networks. Using state - of - the - art diagnostic tools and my in - depth knowledge, I pinpoint issues quickly. On this platform, I'm eager to share my insights, exchange ideas, and collaborate with fellow experts. Let's work together to enhance the reliability of electrical setups.

What are the common faults of low-voltage voltage transformers?
What are the common faults of low-voltage voltage transformers?
1. Open - Circuit Fault on the Secondary SideOpen - circuit in the secondary side is a typical fault of low - voltage voltage transformers, showing abnormal voltmeter readings (zero/fluctuation), faulty power meters, buzzing noises, and core overheating. When open - circuited, the secondary voltage spikes (no secondary current to balance the primary EMF), causing core saturation, flux distortion, and potential overheating/damage.Causes include loose terminals, poor contact, or human error. In lo
Oliver Watts
07/16/2025
Fault Analysis of Single - Phase Grounding of Three - Phase 4PT Voltage Transformer
Fault Analysis of Single - Phase Grounding of Three - Phase 4PT Voltage Transformer
In 10 kV and 35 kV ungrounded systems, single - phase grounding faults cause minimal current, so protection rarely trips. Per regulations, operation is limited to 2 hours; prolonged undetected faults may worsen, even damaging switches. While the State Grid promotes small - current grounding line selection devices in 110 kV and 220 kV substations, their accuracy remains low, requiring monitoring/operation staff to analyze remote measurements. For ungrounded systems with three - phase 4PT voltage
Felix Spark
07/15/2025
What Are the Common Failures of AIS Voltage Transformers?
What Are the Common Failures of AIS Voltage Transformers?
Hey everyone! I’m Felix, a 10-year veteran in the power system industry. Today, we’re going to dive into an important topic — what are the common failures of Air Insulated Switchgear (AIS) voltage transformers? How do you identify these issues, and how can they be resolved? Let’s get started!1. Insulation DamageThe Problem You Might Encounter:One of the most frequent issues is insulation damage. This typically happens due to aging insulation materials, overvoltage surges,
Felix Spark
07/14/2025
Fault Analysis and Diagnosis on Current Transformer
Fault Analysis and Diagnosis on Current Transformer
Current transformers are numerous in substations and are key equipment to ensure the normal operation of the system. If a current transformer fails, it will cause the circuit breaker to trip and may even evolve into a power outage event, which will have an adverse impact on the safe and stable operation of the power grid. Taking an event of the main transformer differential protection operation caused by the failure of the current transformer on the low-voltage side of the main transformer in a
Felix Spark
07/14/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!