Network distribution transformers serving grid and spot networks

Echo
04/12/2025

Housed in Vaults
Network transformers, which are distribution transformers serving grid and spot networks, are large - sized three - phase units.

According to ANSI C57.12.40 - 1982, network units are typically categorized as vault - type or subway - type:
  • Vault - type transformers: Suitable for occasional submerged operation.
  • Subway - type transformers: Suitable for frequent or continuous submerged operation.
Network transformers are also employed in buildings, typically in the basement. In such cases, vault - type transformers can be utilized, provided that the room is properly constructed and safeguarded for this purpose.Utilities may also opt for dry - type units and units with less - flammable insulating oils.
Technical Characteristics
A network transformer is equipped with a three - phase primary - side switch, which is capable of opening, closing, or short - circuiting the primary - side connection to ground. Its standard secondary - side voltages are 216Y/125 V and 480Y/277 V. Table 1 below lists the standard specifications.
Transformers with a rated capacity of 1000 kVA or less have an impedance of 5%; for those with a rated capacity exceeding 1000 kVA, the standard impedance is 7%.
The reactance - to - resistance ratio (X/R) generally ranges from 3 to 12. Transformers with lower impedance (such as those with a 4% impedance) exhibit lower voltage drops and higher secondary - side fault currents. (Higher secondary - side fault currents are beneficial for clearing faults in the network.) However, lower impedance comes at a cost – it results in higher circulating currents and poorer load balancing among transformers.
Transformers with a rated capacity of 1000 kVA or less have an impedance of 5%; for those with a rated capacity exceeding 1000 kVA, the standard impedance is 7%.The reactance - to - resistance ratio (X/R) generally ranges from 3 to 12. Transformers with lower impedance (such as those with a 4% impedance) exhibit lower voltage drops and higher secondary - side fault currents. (Higher secondary - side fault currents are beneficial for clearing faults in the network.) However, lower impedance comes at a cost – it results in higher circulating currents and poorer load balancing among transformers.
Grounding connections 
Most network transformers are connected delta – grounded wye.By blocking the zero - sequence current, this connection keeps the grounding current on the primary cables at a low level. Consequently, a highly - sensitive ground - fault relay can be employed on the substation circuit breaker. Blocking the zero - sequence current also reduces the current on the cable neutrals and cable sheaths, including zero - sequence harmonics, predominantly the third harmonic.In the event of a primary line - to - ground fault, the feeder circuit breaker trips, yet the network transformers will continue to backfeed the fault until all network protectors operate (and some may malfunction). At this point, the network transformers backfeed the primary feeder as an ungrounded circuit.
In an ungrounded circuit, a single - phase line - to - ground fault causes a neutral - point shift, which raises the phase - to - neutral voltage of the unfaulted phases to the phase - to - phase voltage level. Non - network loads connected phase - to - neutral will be exposed to this overvoltage.Some networks adopt the grounded wye - grounded wye connection method.
This connection is more suitable for combination feeders. In the event of a primary line - to - ground fault, the feeder circuit breaker trips. For the backfeed current to the primary through the network, the wye - wye connection still provides a grounding reference point, thus reducing the likelihood of overvoltage.The grounded wye - grounded wye connection also decreases the probability of ferroresonance when the transformer undergoes single - pole switching.
Most network transformers are of the core type, with the core structure being either three - legged (three - phase, three - column) or five - legged (three - phase, five - column). The three - legged core, whether it is a stacked core or a wound core, is suitable for a delta - grounded wye connection (but not for a grounded wye - grounded wye connection due to tank heating issues). A five - legged core transformer is suitable for both of the above - mentioned connection types.

 

Echo

As an expert in the application and trends of electrical equipment, I have a profound mastery of knowledge in circuits, power electronics, etc. I possess a comprehensive set of abilities including equipment design, fault diagnosis, and project management. I can precisely grasp the industry's pulse and lead the development of the electrical field.

What are the monitoring methods and future development trends of low-voltage voltage transformers?
What are the monitoring methods and future development trends of low-voltage voltage transformers?
With the continuous advancement of smart grid technology, intelligent monitoring systems are playing an increasingly important role in preventing and addressing faults in voltage transformers. These modern intelligent monitoring systems can collect key parameters from voltage transformers in real time—such as partial discharge levels, temperature, and oil quality—and use data analysis algorithms to assess the health status of the equipment, enabling early fault warnings and precise l
Echo
07/16/2025
What are the impacts of temperature on AIS voltage transformers?
What are the impacts of temperature on AIS voltage transformers?
Impact on Insulation PerformanceChanges in Insulating Material Properties: AIS voltage transformers rely on air as the insulating medium, and they also contain some solid insulating materials, such as insulating paper and insulating bushings. When the temperature rises, the migration and evaporation of moisture in solid insulating materials like insulating paper will accelerate, resulting in a decrease in the electrical strength of the insulating materials and an increased risk of insulation bre
Echo
07/15/2025
How is the application and development of AIS voltage transformers in 66kV outdoor substations?
How is the application and development of AIS voltage transformers in 66kV outdoor substations?
Hey everyone! I’m Echo, and today we’re diving into the application and development of Air Insulated Switchgear (AIS) voltage transformers in 66kV outdoor substations. These devices play a crucial role in power systems, not just for measurement but also for protection and control. As technology advances, they continue to evolve to meet higher performance demands and stricter environmental standards. Let’s take a closer look!ApplicationsVoltage MeasurementOne of the primary task
Echo
07/15/2025
What Is the Development Trend of AIS Current Transformers?
What Is the Development Trend of AIS Current Transformers?
Hey everyone, I'm Echo, a 10-year veteran in the power system industry. Today we’re going to talk about an important topic — the future development trends of current transformers (CTs) used in Air Insulated Switchgear (AIS).As technology advances and market demands evolve, these critical components are also undergoing continuous innovation. In this article, I’ll walk you through the key directions of future development based on my hands-on experience and industry observations.1
Echo
07/12/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!