• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Network distribution transformers serving grid and spot networks

Echo
Echo
Field: Transformer Analysis
China

Housed in Vaults
Network transformers, which are distribution transformers serving grid and spot networks, are large - sized three - phase units.

According to ANSI C57.12.40 - 1982, network units are typically categorized as vault - type or subway - type:

  • Vault - type transformers: Suitable for occasional submerged operation.

  • Subway - type transformers: Suitable for frequent or continuous submerged operation.

Network transformers are also employed in buildings, typically in the basement. In such cases, vault - type transformers can be utilized, provided that the room is properly constructed and safeguarded for this purpose.Utilities may also opt for dry - type units and units with less - flammable insulating oils.

Technical Characteristics

A network transformer is equipped with a three - phase primary - side switch, which is capable of opening, closing, or short - circuiting the primary - side connection to ground. Its standard secondary - side voltages are 216Y/125 V and 480Y/277 V. Table 1 below lists the standard specifications.

Transformers with a rated capacity of 1000 kVA or less have an impedance of 5%; for those with a rated capacity exceeding 1000 kVA, the standard impedance is 7%.
The reactance - to - resistance ratio (X/R) generally ranges from 3 to 12. Transformers with lower impedance (such as those with a 4% impedance) exhibit lower voltage drops and higher secondary - side fault currents. (Higher secondary - side fault currents are beneficial for clearing faults in the network.) However, lower impedance comes at a cost – it results in higher circulating currents and poorer load balancing among transformers.

Transformers with a rated capacity of 1000 kVA or less have an impedance of 5%; for those with a rated capacity exceeding 1000 kVA, the standard impedance is 7%.The reactance - to - resistance ratio (X/R) generally ranges from 3 to 12. Transformers with lower impedance (such as those with a 4% impedance) exhibit lower voltage drops and higher secondary - side fault currents. (Higher secondary - side fault currents are beneficial for clearing faults in the network.) However, lower impedance comes at a cost – it results in higher circulating currents and poorer load balancing among transformers.

Grounding connections 
Most network transformers are connected delta – grounded wye.By blocking the zero - sequence current, this connection keeps the grounding current on the primary cables at a low level. Consequently, a highly - sensitive ground - fault relay can be employed on the substation circuit breaker. Blocking the zero - sequence current also reduces the current on the cable neutrals and cable sheaths, including zero - sequence harmonics, predominantly the third harmonic.In the event of a primary line - to - ground fault, the feeder circuit breaker trips, yet the network transformers will continue to backfeed the fault until all network protectors operate (and some may malfunction). At this point, the network transformers backfeed the primary feeder as an ungrounded circuit.
In an ungrounded circuit, a single - phase line - to - ground fault causes a neutral - point shift, which raises the phase - to - neutral voltage of the unfaulted phases to the phase - to - phase voltage level. Non - network loads connected phase - to - neutral will be exposed to this overvoltage.Some networks adopt the grounded wye - grounded wye connection method.

This connection is more suitable for combination feeders. In the event of a primary line - to - ground fault, the feeder circuit breaker trips. For the backfeed current to the primary through the network, the wye - wye connection still provides a grounding reference point, thus reducing the likelihood of overvoltage.The grounded wye - grounded wye connection also decreases the probability of ferroresonance when the transformer undergoes single - pole switching.
Most network transformers are of the core type, with the core structure being either three - legged (three - phase, three - column) or five - legged (three - phase, five - column). The three - legged core, whether it is a stacked core or a wound core, is suitable for a delta - grounded wye connection (but not for a grounded wye - grounded wye connection due to tank heating issues). A five - legged core transformer is suitable for both of the above - mentioned connection types.

Give a tip and encourage the author!
Recommended
3D Wound-Core Transformer: Future of Power Distribution
3D Wound-Core Transformer: Future of Power Distribution
Technical Requirements and Development Trends for Distribution Transformers Low losses, especially low no-load losses; highlighting energy-saving performance. Low noise, particularly during no-load operation, to meet environmental protection standards. Fully sealed designto prevent transformer oil from contacting external air, enabling maintenance-free operation. Integrated protection devices within the tank, achieving miniaturization; reducing transformer size for easier on-site installation. C
Echo
10/20/2025
Reduce Downtime with Digital MV Circuit Breakers
Reduce Downtime with Digital MV Circuit Breakers
Reduce Downtime with Digitized Medium-Voltage Switchgear and Circuit Breakers"Downtime" — it’s a word no facility manager wants to hear, especially when it’s unplanned. Now, thanks to next-generation medium-voltage (MV) circuit breakers and switchgear, you can leverage digital solutions to maximize uptime and system reliability.Modern MV switchgear and circuit breakers are equipped with embedded digital sensors that enable product-level equipment monitoring, providing real-time insights into the
Echo
10/18/2025
One Article to Understand the Contact Separation Stages of a Vacuum Circuit Breaker
One Article to Understand the Contact Separation Stages of a Vacuum Circuit Breaker
Vacuum Circuit Breaker Contact Separation Stages: Arc Initiation, Arc Extinction, and OscillationStage 1: Initial Opening (Arc Initiation Phase, 0–3 mm)Modern theory confirms that the initial contact separation phase (0–3 mm) is critical to the interrupting performance of vacuum circuit breakers. At the beginning of contact separation, the arc current always transitions from a constricted mode to a diffused mode—the faster this transition, the better the interruption performance.Three measures c
Echo
10/16/2025
Advantages & Applications of Low-Voltage Vacuum Circuit Breakers
Advantages & Applications of Low-Voltage Vacuum Circuit Breakers
Low-Voltage Vacuum Circuit Breakers: Advantages, Application, and Technical ChallengesDue to their lower voltage rating, low-voltage vacuum circuit breakers have a smaller contact gap compared to medium-voltage types. Under such small gaps, transverse magnetic field (TMF) technology is superior to axial magnetic field (AMF) for interrupting high short-circuit currents. When interrupting large currents, the vacuum arc tends to concentrate into a constricted arc mode, where localized erosion zones
Echo
10/16/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.