Conductor Resistance Test of Electrical Power Cables

Ensure cable performance with resistance testing—measure using Wheatstone or Kelvin bridge to detect material defects and ensure low power loss.

Electrical4u
Field: Generation
Electrical Engineer
10Year<
China
Add us on Google

What Is Conductor Resistance Test

This test is used to determine the DC resistance of copper or aluminum conductors. Resistance of a conductor tells us how easily a conductor allows the flow of current through it. Higher the resistance, lesser the current will flow though the conductor. Resistance of a conductor is influenced by conductor dimension and construction, conditions like, temperature and resistivity. It is normally expressed as ohms per km.
This test will make use of either
Kelvin Double Bridge with accuracy of 0.2 percent or Wheatstone Bridge with accuracy of 0.5 percent.
Test specimen is selected as indicated below.

  • All solid circular conductor Drum length of 1 m

  • All stranded or sector shaped solid conductors up to and including 25 mm2 size Drum length of 5 m

  • All stranded or sector shaped solid conductors greater than 25 mm2 size Drum length of 10 m

Note – The length of the test specimen is the length which lies between the potential terminals.

Procedure of Conductor Resistance Test

Connect the specimen to the resistance measuring bridge and make sure that proper considerations are taken into account about the contact resistance.
Measure the resistance and note down the temperature.
Measured resistance is converted to the standard temperature and length.

Observation and Report

Sample no

Nominal conductor size in mm2

Length (m)

Material Al/Cu

Class of conductor

Temperature oC

Observed Resistance

Specified Resistance

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

Calculation

Observed Resistance at a particular temperature,
Conductor Resistance Test of Electrical Power CablesWhere,
Rt = Observed Resistance
K = Temperature correction factor
L = Length of specimen in m.
Conclusion – The sample meets/does not meet the requirements of the specification.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Comments

Share your question or perspective
WhatsApp
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Login
or continue with
New here?
Register