• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What should be noted when selecting and installing current transformers for air-insulated switchgear?

James
James
Field: Electrical Operations
China

The selection and installation of current transformers for air-insulated switchgear (AIS CT) directly affect the measurement accuracy, protection reliability, and operational safety of power systems. It is necessary to comprehensively consider equipment characteristics, system requirements, and environmental conditions. The specific precautions are as follows:

1. Precautions for Selection
1.1 Matching of Electrical Parameters

  • Rated primary current: Determine based on the maximum continuous operating current of the circuit where it is located. Generally, it is selected as 1.2-1.5 times the rated current of the circuit to ensure no overheating or overload during long-term operation. For example, if the rated current of a 10kV line is 400A, a CT with 500A/5A can be selected.

  • Rated secondary current: It needs to match secondary equipment (instruments, relays, etc.), with common values being 5A or 1A (1A is suitable for long-distance transmission with smaller losses).

  • Accuracy class and accuracy limit factor (ALF):

    • Measurement-purpose CTs must meet the accuracy class (such as 0.2, 0.5) to ensure metering precision.

    • Protection-purpose CTs should focus on the accuracy limit factor (such as 5P20, 10P30) to ensure that the secondary current error is within the allowable range during short circuits (5P20 means that when the short-circuit current is 20 times the rated primary current, the error is ≤5%).

  • Rated voltage: It must be consistent with the rated voltage of the AIS equipment (such as 10kV, 35kV, 110kV) and meet the insulation level requirements (such as lightning impulse withstand voltage, power frequency withstand voltage).

1.2 Adaptability of Structural Form

  • Installation method: Select post-type, through-wall type, or busbar type according to the layout of AIS equipment. Post-type is suitable for outdoor open layout; through-wall type is used for passing through walls or switchgear partitions; busbar type is directly sleeved on the busbar, with a compact structure.

  • Number of windings: Choose single-winding (only for measurement or only for protection) or multi-winding (to meet functions such as measurement, protection, and metering simultaneously, with different windings corresponding to different accuracy classes) according to secondary needs.

  • Shell material: For outdoor use, materials with strong weather resistance (such as silicone rubber, porcelain) should be selected; for indoor use, epoxy glass fiber, etc., can be used to avoid rust or aging affecting insulation.

1.3 Environmental Adaptability

  • Climatic conditions: For outdoor installation, factors such as temperature range (-40℃~60℃), humidity, altitude (insulation needs to be strengthened in high-altitude areas, e.g., insulation strength needs to be increased by 20% at an altitude of 3000m), and pollution level (products with large creepage distance should be selected in heavily polluted areas, with creepage distance ≥25mm/kV) must be considered.

  • Mechanical strength: It must withstand mechanical stresses such as earthquakes and wind forces, especially for post-type CTs installed outdoors at high heights, which must meet anti-overturning and anti-seismic grade requirements.

2. Installation Precautions
2.1 Inspection Before Installation

  • Appearance and insulation: Check that the porcelain sleeve/shell is free of damage and cracks, and the insulation surface is clean; measure the insulation resistance with a 2500V megohmmeter, which should be ≥1000MΩ (at room temperature).

  • Parameter verification: Confirm that the CT's model, rated current, accuracy class, and other parameters are consistent with the design drawings, and the nameplate is clear and complete.

  • Test report: A factory test report (such as transformation ratio test, volt-ampere characteristic test, polarity test) must be provided to ensure qualified performance.

2.2 Installation Specifications

  • Correct polarity: The primary side "L1" (incoming end) and the secondary side "K1" (outgoing end) of the CT must maintain consistent polarity (subtractive polarity) to avoid misoperation of the protection device or reverse measurement. Polarity can be confirmed by the DC method or instrument testing.

  • Grounding requirements:

    • The shell must be reliably grounded (single-point grounding) with a grounding resistance ≤4Ω to prevent electric shock hazards from live shells.

    • The "K2" end of the secondary winding must be reliably grounded to avoid high voltage generated by an open secondary side (the secondary side of the CT is strictly prohibited from being open; the secondary winding must be short-circuited first during installation).

  • Installation position:

    • It should be as close as possible to the circuit breaker or disconnector to shorten the length of the connecting wire and reduce measurement errors.

    • Avoid arranging it in close proximity to strong magnetic field equipment (such as reactors) to prevent electromagnetic interference from affecting accuracy.

  • Connection tightness: The primary side terminal must be tightened (meeting torque requirements) to prevent heating; the cross-sectional area of the secondary side wire should be ≥2.5mm², and the wiring should be firm to avoid poor contact due to looseness.

2.3 Safety Protection

  • Anti-open circuit measures: During installation or maintenance, the secondary winding must be short-circuited first (with a special shorting piece). It is strictly prohibited to disconnect the secondary circuit in a live state (an open secondary side will generate thousands of volts of high voltage, endangering equipment and personal safety).

  • Clear identification: Mark the polarity, transformation ratio, and winding purpose on the CT body and the secondary circuit end cover to avoid wrong wiring.

2.4 Calibration After Installation

  • Transformation ratio review: Confirm that the primary and secondary current transformation ratios are consistent with the design through tests.

  • Insulation test: Measure the insulation resistance again after installation to ensure that the insulation is not damaged during the installation process.

  • Overall debugging: Conduct linkage tests with AIS equipment and secondary protection devices to verify the correctness of protection actions (such as overcurrent protection, differential protection).

3. Subsequent Maintenance Points

  • Regularly clean the insulation surface (especially for outdoor equipment) to remove dirt, bird droppings, etc., to prevent flashover.

  • Check whether the grounding connection is loose and whether the shell is rusted or leaking oil (oil-immersed CT).

  • Conduct preventive tests (such as dielectric loss test, partial discharge test) every 3-5 years to evaluate the degree of insulation aging.

By strictly following the selection standards and installation specifications, AIS CT can achieve accurate measurement and reliable protection in the power system, and extend the service life of the equipment.

Give a tip and encourage the author!
Recommended
How to Design 10kV Overhead Line Poles
How to Design 10kV Overhead Line Poles
This article combines practical examples to refine the selection logic for 10kV steel tubular poles, discussing clear general rules, design procedures, and specific requirements for use in 10kV overhead line design and construction.Special conditions (such as long spans or heavy ice zones) require additional specialized verifications based on this foundation to ensure safe and reliable tower operation.General Rules for Overhead Transmission Line Tower SelectionThe rational selection of overhead
James
10/20/2025
How to select a dry-type transformer?
How to select a dry-type transformer?
1. Temperature Control SystemOne of the main causes of transformer failure is insulation damage, and the greatest threat to insulation comes from exceeding the allowable temperature limit of the windings. Therefore, monitoring temperature and implementing alarm systems for transformers in operation are essential. The following introduces the temperature control system using the TTC-300 as an example.1.1 Automatic Cooling FansA thermistor is pre-embedded at the hottest spot of the low-voltage win
James
10/18/2025
How to Choose the Right Transformer?
How to Choose the Right Transformer?
Transformer Selection and Configuration Standards1. Importance of Transformer Selection and ConfigurationTransformers play a critical role in power systems. They adjust voltage levels to suit different requirements, enabling electricity generated at power plants to be efficiently transmitted and distributed. Improper transformer selection or configuration can lead to serious issues. For example, if the capacity is too small, the transformer may not support the connected load, causing voltage dro
James
10/18/2025
How to Choose Vacuum Circuit Breakers Correctly?
How to Choose Vacuum Circuit Breakers Correctly?
01 PrefaceIn medium-voltage systems, circuit breakers are indispensable primary components. Vacuum circuit breakers dominate the domestic market. Therefore, correct electrical design is inseparable from the proper selection of vacuum circuit breakers. In this section, we will discuss how to correctly select vacuum circuit breakers and common misconceptions in their selection.02 Interrupting Capacity for Short-Circuit Current Need Not Be Excessively HighThe short-circuit interrupting capacity of
James
10/18/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.