What should be noted when selecting and installing current transformers for air-insulated switchgear?

07/12/2025

The selection and installation of current transformers for air-insulated switchgear (AIS CT) directly affect the measurement accuracy, protection reliability, and operational safety of power systems. It is necessary to comprehensively consider equipment characteristics, system requirements, and environmental conditions. The specific precautions are as follows:
1. Precautions for Selection
1.1 Matching of Electrical Parameters
  • Rated primary current: Determine based on the maximum continuous operating current of the circuit where it is located. Generally, it is selected as 1.2-1.5 times the rated current of the circuit to ensure no overheating or overload during long-term operation. For example, if the rated current of a 10kV line is 400A, a CT with 500A/5A can be selected.
  • Rated secondary current: It needs to match secondary equipment (instruments, relays, etc.), with common values being 5A or 1A (1A is suitable for long-distance transmission with smaller losses).
  • Accuracy class and accuracy limit factor (ALF):
    • Measurement-purpose CTs must meet the accuracy class (such as 0.2, 0.5) to ensure metering precision.
    • Protection-purpose CTs should focus on the accuracy limit factor (such as 5P20, 10P30) to ensure that the secondary current error is within the allowable range during short circuits (5P20 means that when the short-circuit current is 20 times the rated primary current, the error is ≤5%).
  • Rated voltage: It must be consistent with the rated voltage of the AIS equipment (such as 10kV, 35kV, 110kV) and meet the insulation level requirements (such as lightning impulse withstand voltage, power frequency withstand voltage).

1.2 Adaptability of Structural Form

  • Installation method: Select post-type, through-wall type, or busbar type according to the layout of AIS equipment. Post-type is suitable for outdoor open layout; through-wall type is used for passing through walls or switchgear partitions; busbar type is directly sleeved on the busbar, with a compact structure.
  • Number of windings: Choose single-winding (only for measurement or only for protection) or multi-winding (to meet functions such as measurement, protection, and metering simultaneously, with different windings corresponding to different accuracy classes) according to secondary needs.
  • Shell material: For outdoor use, materials with strong weather resistance (such as silicone rubber, porcelain) should be selected; for indoor use, epoxy glass fiber, etc., can be used to avoid rust or aging affecting insulation.

1.3 Environmental Adaptability

  • Climatic conditions: For outdoor installation, factors such as temperature range (-40℃~60℃), humidity, altitude (insulation needs to be strengthened in high-altitude areas, e.g., insulation strength needs to be increased by 20% at an altitude of 3000m), and pollution level (products with large creepage distance should be selected in heavily polluted areas, with creepage distance ≥25mm/kV) must be considered.
  • Mechanical strength: It must withstand mechanical stresses such as earthquakes and wind forces, especially for post-type CTs installed outdoors at high heights, which must meet anti-overturning and anti-seismic grade requirements.

2. Installation Precautions
2.1 Inspection Before Installation

  • Appearance and insulation: Check that the porcelain sleeve/shell is free of damage and cracks, and the insulation surface is clean; measure the insulation resistance with a 2500V megohmmeter, which should be ≥1000MΩ (at room temperature).
  • Parameter verification: Confirm that the CT's model, rated current, accuracy class, and other parameters are consistent with the design drawings, and the nameplate is clear and complete.
  • Test report: A factory test report (such as transformation ratio test, volt-ampere characteristic test, polarity test) must be provided to ensure qualified performance.

2.2 Installation Specifications

  • Correct polarity: The primary side "L1" (incoming end) and the secondary side "K1" (outgoing end) of the CT must maintain consistent polarity (subtractive polarity) to avoid misoperation of the protection device or reverse measurement. Polarity can be confirmed by the DC method or instrument testing.
  • Grounding requirements:
    • The shell must be reliably grounded (single-point grounding) with a grounding resistance ≤4Ω to prevent electric shock hazards from live shells.
    • The "K2" end of the secondary winding must be reliably grounded to avoid high voltage generated by an open secondary side (the secondary side of the CT is strictly prohibited from being open; the secondary winding must be short-circuited first during installation).
  • Installation position:
    • It should be as close as possible to the circuit breaker or disconnector to shorten the length of the connecting wire and reduce measurement errors.
    • Avoid arranging it in close proximity to strong magnetic field equipment (such as reactors) to prevent electromagnetic interference from affecting accuracy.
  • Connection tightness: The primary side terminal must be tightened (meeting torque requirements) to prevent heating; the cross-sectional area of the secondary side wire should be ≥2.5mm², and the wiring should be firm to avoid poor contact due to looseness.

2.3 Safety Protection

  • Anti-open circuit measures: During installation or maintenance, the secondary winding must be short-circuited first (with a special shorting piece). It is strictly prohibited to disconnect the secondary circuit in a live state (an open secondary side will generate thousands of volts of high voltage, endangering equipment and personal safety).
  • Clear identification: Mark the polarity, transformation ratio, and winding purpose on the CT body and the secondary circuit end cover to avoid wrong wiring.

2.4 Calibration After Installation

  • Transformation ratio review: Confirm that the primary and secondary current transformation ratios are consistent with the design through tests.
  • Insulation test: Measure the insulation resistance again after installation to ensure that the insulation is not damaged during the installation process.
  • Overall debugging: Conduct linkage tests with AIS equipment and secondary protection devices to verify the correctness of protection actions (such as overcurrent protection, differential protection).

3. Subsequent Maintenance Points

  • Regularly clean the insulation surface (especially for outdoor equipment) to remove dirt, bird droppings, etc., to prevent flashover.
  • Check whether the grounding connection is loose and whether the shell is rusted or leaking oil (oil-immersed CT).
  • Conduct preventive tests (such as dielectric loss test, partial discharge test) every 3-5 years to evaluate the degree of insulation aging.
By strictly following the selection standards and installation specifications, AIS CT can achieve accurate measurement and reliable protection in the power system, and extend the service life of the equipment.

Professionalism builds strength. As an expert in the installation and operation of electrical equipment, I am proficient in the installation process and strictly adhere to standards. I skillfully master the operation essentials and can swiftly eliminate faults. With a heart that constantly explores new knowledge, I illuminate the path to the efficient operation of electrical equipment.

What Should Be Noted During the Installation Process of Indoor Load Switches?
What Should Be Noted During the Installation Process of Indoor Load Switches?
The installation quality of indoor load switches directly affects their operational safety and service life. It must be carried out focusing on four core principles: "safety protection, standardized wiring, mechanical compatibility, and insulation assurance." Specific precautions are as follows:1.Basic Preparation and Safety Protection Before Installation: Verify that the switch model and specifications (e.g., rated voltage, current) match the actual power distribution requirements to avoid "usi
08/27/2025
Process Details for the Selection and Installation of 10kV Pole-Mounted Drop-Out Fuses
Process Details for the Selection and Installation of 10kV Pole-Mounted Drop-Out Fuses
Fuses are connected in series in a circuit. When the current through the fuse element is less than or equal to its rated current, the element will not melt. Only when the current exceeds the rated value and reaches the fusing current will the element melt. When a short circuit (or overload) current occurs in the line, the current through the fuse element exceeds the specified value, causing the element to overheat and melt, thereby automatically interrupting the circuit. This prevents damage to
08/27/2025
Fundamentals of High-Voltage Fuses with High Breaking Capacity Used in Substations
Fundamentals of High-Voltage Fuses with High Breaking Capacity Used in Substations
In the power plants and substations of various voltage levels that we operate and maintain, high-voltage current-limiting fuses are widely used, primarily for protecting voltage transformers, small transformers, and small high-voltage motors. So why are they called high-breaking-capacity fuses? And why can't ordinary fuses be used? Today, let's learn about this topic together.High-breaking-capacity fuses, also known as high-voltage current-limiting fuses, differ from ordinary fuses in two main a
08/27/2025
Operational Safety Procedures and Maintenance Requirements for Low-Voltage Pole-Mounted Circuit Breakers
Operational Safety Procedures and Maintenance Requirements for Low-Voltage Pole-Mounted Circuit Breakers
Safe operation and regular maintenance of low-voltage pole-mounted circuit breakers are essential for long-term system reliability.1. Operational Safety ProceduresOperations must be strictly regulated under dispatch control, following the "Three Tickets and Two Systems" (work permit, operation ticket, emergency repair order; read-back and supervision systems). Operation tickets must use dual equipment identifiers (e.g., "XX kV XX Line XXX Circuit Breaker") and list detailed steps and safety meas
08/21/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!