| Model |
|
DNH40 - 160 |
DNH40 - 200 |
DNH40 - 250 |
| Arus termal konvensional dan arus operasional nominal |
A |
160 |
200 |
250 |
| Tegangan operasional nominal (AC - 20/DC - 20) |
V |
1000 |
1000 |
1000 |
| Tegangan isolasi nominal (Kategori Pemasangan Ⅳ) |
Ui V |
1000 |
1000 |
1000 |
| Kekuatan dielektrik |
50Hz 1min kV |
10 |
10 |
10 |
| Tahanan impuls nominal |
Uimp kV |
12 |
12 |
12 |
| Arus operasional nominal (AC - 21A) |
690V A |
160 |
200 |
250 |
| Arus operasional nominal (AC - 22A) |
690V A |
160 |
200 |
250 |
| Arus operasional nominal (AC - 23A) |
690V A |
160 |
200 |
250 |
| Kehilangan daya per kutub (pada arus operasional nominal) |
W |
3.2 |
4 |
6.5 |
| Arus tahanan singkat nominal |
≤690V1s kA |
8 |
8 |
8 |
| Kapasitas pembuatan sirkuit pendek nominal |
≤ 690V kA |
30 |
30 |
30 |
| Umur mekanis |
Oper |
20000 |
20000 |
20000 |
| Torsi operasi (3 kutub) |
Nm |
7 |
7 |
7 |
| Spesifikasi sekrup terminal |
mm |
M8×25 |
M8×25 |
M8×25 |
| Torsi pengencangan terminal |
Torsi penguncian Nm |
15~22 |
15~22 |
15~22 |
| Kondisi Operasional Normal |
|
|
|
|
| Suhu Lingkungan |
Rentang: - 5℃ hingga + 40℃, dengan rata-rata suhu 24 jam tidak melebihi + 35℃ |
|
|
|
| Kelembaban |
Pada suhu maksimum (+ 40℃), kelembaban relatif ≤ 50%. Pada suhu lebih rendah (misalnya, + 20℃), kelembaban yang lebih tinggi (hingga 90%) diperbolehkan. Tindakan khusus harus diambil untuk mengatasi kondensasi sesekali yang disebabkan oleh fluktuasi suhu. |
|
|
|
| Ketinggian |
≤2000m |
|
|
|
| Derajat Polusi |
Ⅲ |
|
|
|
| Kategori Pemasangan |
Ⅳ |
|
|
|
| Persyaratan Pemasangan |
Saklar harus dipasang di lokasi yang bebas dari getaran signifikan, guncangan mekanis, atau paparan hujan/salju. Lokasi pemasangan harus bebas dari bahan berbahaya ledakan dan gas/bubuk korosif yang dapat merusak logam atau isolasi. |
|
|
|
| Catatan: Jika saklar dimaksudkan untuk digunakan pada suhu lingkungan yang melebihi + 40℃ atau di bawah - 5℃, pengguna harus berkonsultasi dengan produsen. |
|
|
|